Operating Instructions for Master-Bilt Alarm/Light Module (19-14009)
1598003200
19-14009
Walk-In Temp / Door /Alarm / Light Module
1. GENERAL WARNINGS
1.1 PLEASE READ BEFORE USING THIS MANUAL
• This manual is part of the product and should be kept close to the instrument for easy and quick
reference.
• The instrument shall not be used for purposes different from those described hereunder. It cannot be
used as a safety device.
• Check the application limits before proceeding.
1.2
SAFETY PRECAUTIONS
• Check if the supply voltage is correct before connecting the instrument.
• Do not expose to water or moisture: use the controller only within the operating limits avoiding sudden
Temperature changes with high atmospheric humidity to prevent the formation of condensation.
• Warning: disconnect all electrical connections before performing any maintenance operation.
• Fit the probe where it is not damaged by the end-user. The instrument must not be opened.
• In case of failure or faulty operation send the instrument back to the distributor (see address) with a
detailed description of the fault.
• Consider the maximum current that can be applied to each relay (see Technical Data).
• Ensure that the wires for probes, loads and the power supply are separated and far enough from each
other, without crossing or intertwining.
2. GENERAL DESCRIPTION
Model XWA11V, 100x64 mm format, is a microprocessor based controller, suitable for temperature
monitoring in a walk-in cooler or freezer. It is provided with two (2) relay outputs to control lights and
signal an alarm. It is also provided with one (1) NTC probe input for temperature measurement. One (1)
output allows the user to program the parameter list with the “Hot Key”.
3. INTERFACE
1
Operating Instructions for Master-Bilt Alarm/Light Module (19-14009)
1598003200
5. PROGRAMMING
5.1 HOW TO CHANGE A PARAMETER VALUE MAIN MENU
1. Enter the Programming Mode by pressing the SET and DOWN key for 3s ( and
start blinking).
2. Select the required parameter.
3. Press the “SET” key to display its value (now only the
LED is blinking).
4. Use “UP” or “DOWN” to change its value.
Press “SET” to store the new value and move to the following parameter.
To exit: Press SET + UP or wait 15 s without pressing a key.
NOTE: the set value is stored even when the procedure is exited, by waiting the time-out to expire.
5.2 THE HIDDEN MENU (PR2)
The hidden menu includes all the parameters of the instrument.
5.2.1 HOW TO ENTER THE HIDDEN MENU (PR2)
1. Enter the Programming Mode by pressing the Set + down key for 3s ( and
starts blinking).
2. When a parameter is displayed, release and re-press the SET + down for more than 7s.
3. The Pr2 label will be displayed immediately followed from the HY parameter. NOW YOU ARE IN
THE HIDDEN MENU.
4. Select the required parameter.
5. Press the “SET” key to display its value (Now only the
LED is blinking).
6. Use “UP” or “down” to change its value.
7. Press “SET” to store the new value and move to the following parameter.
To exit: Press SET + up or wait 15s without pressing a key.
NOTE: the set value is stored even when the procedure is exited by waiting the time-out to expire.
5.2.2 HOW TO MOVE A PARAMETER FROM THE HIDDEN MENU TO THE FIRST LEVEL AND
VICEVERSA
Each parameter present in the HIDDEN MENU can be removed or put into “THE FIRST LEVEL” (user
level) by pressing “SET + down”.
In HIDDEN MENU when a parameter is present in First Level the decimal point LED is on.
5.3 HOW TO LOCK THE KEYBOARD
1. Keep pressed for more than 3s the UP and DOWN keys.
2. The “POF” message will be displayed and the keyboard will be locked. At this point it will be possible
only to see the Set Point or the MAX o MIN Temp stored
3. If a key is pressed more than 3s the “POF” message will be displayed.
5.4 TO UNLOCK THE KEYBOARD
Keep pressed together for more than 3s the UP and DOWN keys.
6. LIGHT MANAGEMENT
6.1 TIMED REGULATION: I1L = Y
With i1L = y the light remains on at least for the LHt parameter.
The LHt timer is re-initialized every time the light button is pushed.
With LHt=0 the light remains on until the light button is pushed again.
The light is switched on every time one of the following conditions happens:
•
•
•
the door is open (i1F = dor)
the presence sensor is activated (i2F = LHt)
the light button is pushed
The light is switched off when all the following conditions happen:
•
•
•
the LHt timer is exhausted
the door is closed (i1F = dor)
the presence sensor is de-activated (i2F = LHt)
3
Operating Instructions for Master-Bilt Alarm/Light Module (19-14009)
1598003200
6.2 LIGHT BUTTON REGULATION: I1L = N
The light button has a higher priority than digital inputs therefore:
- if the light was switched on by button the digital input can not modify its status.
- if the light was switched on by digital input, the light button can modify its status.
7. INSTALLATION AND MOUNTING
7.1 MOUNTING OF XWA11V – PR10000
The XWA11V must be mounted on vertical
panel.
The Temp range allowed for correct
operation is 32 – 140°F. Avoid installation is
places subject to strong vibrations, corrosive
gases, excessive dirt or humidity. The same
recommendations apply to probes. Let the air
circulate by the cooling holes.
8. ELECTRICAL CONNECTIONS
The instrument is provided with screw terminal blocks to connect cables with a cross section up to 2,5
mm2 for the digital and analog inputs. Relays and power supply have a Faston connection (6,3mm). Heat-
resistant cables have to be used. Before connecting cables make sure the power supply complies with
the instrument requirements. Separate the probe cables from the power supply cables, from the outputs
and the power connections. Do not exceed the maximum current allowed on each relay and in case of
heavier loads use a suitable external relay.
N.B. Maximum current allowed for all the loads is 20A.
8.1 PROBE CONNECTIONS
The probe shall be mounted with the bulb upwards to prevent damages due to casual liquid infiltration. It
is recommended to place the thermostat probe away from air streams to correctly measure the average
room temperature.
9. USE OF THE PROGRAMMING “HOT KEY “
The Wing units can UPLOAD or DOWNLOAD the parameter list from its own E2 internal memory to the
“Hot Key” and vice-versa.
10. ALARM SIGNALS
Message
“P1”
Mode
Flashing
Cause
Outputs
Alarm output ON
Not changed
Thermostat probe failure
Keyboard locked
Keyboard un-locked
Maximum T° alarm
Minimum T° alarm
Door switch alarm
External alarm
PoF
Pon
“HA”
“LA”
“dA”
“EA”
“PAn”
dEF
Flashing (3s)
Flashing (3s)
Alternated with t
Alternated with t
Alternated with t
Alternated with t
Alternated with t
Alternated with t
Not changed
Alarm output ON;
Alarm output ON;
Alarm output ON;
Alarm output ON;
Alarm output ON;
Not changed
Serious external alarm
Defrost is running
The alarm message is displayed until the alarm condition is reset.
4
Operating Instructions for Master-Bilt Alarm/Light Module (19-14009)
1598003200
10.1 SILENCING BUZZER
Once the alarm signal is detected the buzzer can be silenced by pressing the UP key.
10.2 ALARM RECOVERY
Probe alarms : “P1” (probe1 faulty), “P2” ; they automatically stop 10s after the probe restarts normal
operation. Check connections before replacing the probe.
T° alarms “HA” and “LA” automatically stop as soon as the thermostat T° returns to normal values or
when the defrost starts.
Door switch alarm “dA” stops as soon as the door is closed.
External alarms “EAL”, “BAL” stops as soon as the external digital input is disabled.
11. TECHNICAL DATA
Housing: self extinguishing ABS
Case: face 100x64 mm; depth 45.5mm
Mounting: J-box or wall-mount option
Frontal protection: IP65
Connections: ¼” fastons for power, 18” fastons for probes and Digital Inputs
Power supply: 120Vac 10%, optional 230Vac 10%
Power absorption: 4VA max.
Display: 3 digits, red LED, 14,2 mm high.
Inputs: 1 NTC probe
Digital inputs: 2 free voltages
Relay outputs: Dry Contacts
Light: relay SPST 16A, 120Vac;
Alarm: relay SPST 8A, 120Vac
Other output: alarm buzzer
Data storing: on the non-volatile memory (EEPROM).
Measuring and regulation range:
NTC probe: -40÷110°C (-58÷230°F)
Resolution: 1 °F
Accuracy : ±1 °F
12. CONNECTIONS
Back up
(9VDC)
1
2
3
4
5
6
7
8
8A
250V
16A 250V
11 12 13 14 15 16 17 18 19
L
N
Alarm C. Light C.
Supply 120V~
Power supply: 230Vac 10% models, use the same terminals of the 120Vac version.
5
Operating Instructions for Master-Bilt Alarm/Light Module (19-14009)
1598003200
13. PARAMETER MAP
LABEL
DESCRIPTION
Thermostat probe
calibration
VALUE
LEVEL
RANGE
[-12,0°C <> 12,0°C] [-
0
Pr2
ot
21°F <> 21°F]
CF
rES
UT
T° measurement unit
Resolution (only °C)
Display update
F
in
60
y
Pr2
Pr2
Pr2
Pr2
°C(0) - °F(1)
dE(0) - in(1)
0 <> 255 (s)
n(0) - Y(1)
OnF
Off function enabling
°C[ ALL <> 150,0°] °F[
ALL <> 302°]
°C[ -50.0° <> ALU] °F[-
58 <> ALU]
50
30
Pr1
Pr1
ALU
ALL
High Tempalarm setting
Low Temp alarm setting
[0,1°C <>25,5°C] [1°F
<> 45°F]
2
Pr2
Pr1
Pr2
AFH
ALd
Temp alarm differential
Temp alarm delay
Delay of Temp alarm at
start-up
Alarm delay at the end
of defrost
Delay of Temp alarm
after closing the door
Light timer
Open door alarm delay
First relay configuration
Second relay
30
1.3
0 <> 255 (min.)
dAo
EdA
0 <> 24H0(144)
0 <> 255 (min.)
30
15
Pr2
Pr2
dot
LHt
doA
OA1
0 <> 255 (min.)
0 <> 255 (min.)
0 <> 255 (min.)
15
15
ALr
Pr1
Pr1
Pr2
ALr(0) - LHt(1) - OnF(2)
LHt
Pr2
oA2
AOP
i1P
configuration
ALr(0) - LHt(1) - OnF(2)
OP - CL
Alarm relay polarity
Digital input 1 polarity
Door switch to turn light
ON
Digital input 1 operating
mode
Digital input 2 polarity
Digital input 2 operating
mode
oP
oP
Pr2
Pr2
OP(0) - CL(1)
y
Pr2
i1L
n(0) - Y(1)
EAL(0) - dor(1) - dEr(2)
- LHt(3)
dor
Pr2
Pr2
Pr2
i1F
i2P
cL
PA
n
OP(0) - CL(1)
EAL(0) - Pan(1) -
dFr(2) - LHt(3)
i2F
Time interval/delay for
digital input alarm
Alarm relay disabling
Kind of probe
Real T° Probe 1
FW release
0
Pr2
did
tbA
PbC
dP1
rEL
Ptb
0 <> 255 (min.)
n(0) - Y(1)
PtC(0) - ntC(1)
(probe value)
read only
n
ntc
Pr2
Pr2
Pr2
Pr2
Pr2
Parameter map
read only
6
Operating Instructions for Master-Bilt Alarm/Light Module (19-14009)
1598003200
14. PARAMETER LIST
Ot
Thermostat probe calibration: (-12.0÷12.0°C/ -21÷21°F) allows to adjust possible offset of the
thermostat probe.
CF T measurement unit: °C = Celsius; °F = Fahrenheit. When the measurement unit is changed the
Set Point and the values of some parameters have to be modified.
rES Resolution (for °C): (in = 1°C; dE = 0.1 °C) allows decimal point display.
Ut
Display update: The time delay of the T readout (0÷255s)
onF Off function enabling: n = off function disabled; y = off function enabled;
ALU High T° alarm setting: (ALL ÷ 150°C or 302°F);
when this T° is reached and after the ALd delay time the HA alarm is enabled.
ALL Low T° alarm setting: (- 50°C or -58°F ÷ ALU)
when this T° is reached and after the ALd delay time, the LA alarm is enabled,.
AFH T° alarm differential: (0,1÷25,5°C; 1÷45°F) differential for T° alarm Set Point and fan regulation Set
Point, always a positive value
ALd T° alarm delay: (0÷255 min) time interval between the detection of an alarm condition and the
corresponding alarm signaling.
dAO Delay of T° alarm at start-up: (0min÷23h 50min) time interval between the detection of the T°
alarm condition after the instrument power on and the alarm signaling.
EdA Alarm delay at the end of defrost: (0÷255 min) Time interval between the detection of the T° alarm
condition at the end of defrost and the alarm signaling.
dot Delay of T° alarm after closing the door: (0÷255 min) Time delay to signal the T° alarm
condition after closing the door.
LHt Light timer: (0-255 min) The time the light will stay on after pressing the light switch on the
keyboard.
doA Open door alarm delay:(0÷255 min) delay between the detection of the open door condition and its
alarm signaling: the flashing message “dA” is displayed.
oA1 First relay configuration: (14-15): ALr = alarm; LHt = light; onF = on/off relay
oA2 Second relay configuration: (14-16): ALr = alarm; LHt = light; onF = on/off relay
AOP Alarm relay polarity: cL = closing contacts; oP = opening contacts.
i1P Digital input 1 polarity (1-2): CL : the digital input is activated by closing the contact;
OP the digital input is activated by opening the contact
i1L Door switch to turn light ON(1-2): (y / no) To turn the light ON automatically when the door is
open. The light will turn off based on LHt . Keyboard switch must be turned ON first.
i1F
Digital input 1 operating mode(1-2): EAL = external alarm; dor = door switch; dFr = A defrost is
running; LHt = keep light ON (signal from occupancy sensor) override LHt.;
i2P Digital input 2 polarity (1-3): CL : the digital input is activated by closing the contact;
OP the digital input is activated by opening the contact
i2F Digital input 2 operating mode: configure the digital input function:
EAL = External alarm;
PAn =Panic alarm;
dFr = A defrost is running;
LHt = Keep light ON (signal from occupancy sensor) override LHt.
did Time interval/delay for digital input alarm:(0÷255 min.) If I2F=EAL or PAn (external alarms), “did”
parameter defines the time delay between the detection and the successive signaling of the alarm.
tbA Alarm relay & Buzzer disabling: (y ; no)
Pbc Type of probe (PTC, NTC)
dP1 Probe 1 T
rEL Software release for internal use.
Ptb Parameter table code: read only.
15. PARTS LIST
M/B Part Number
19-14009
Description
WI therm, alarm, panic light, contl. #XWA11V-4N1F0
PROBE, 18NB-NTC-1.5M, (5')
19-14012
19-14013
PROBE, 18NB-NTC-1.5M, (50')
19-14014
PROBE, 18NB-NTC-1.5M, (75')
For more information, please contact our Technical Service Dept.
@ 1-800-684-8988
7
|