Honeywell Smoke Alarm IPGSM DP User Manual

IPGSM-DP  
Commercial Fire Communicator  
Installation and Setup Guide  
IPGSM-DP Commer  
cial Fire Comm  
unicator  
RADIO  
TR  
OUBLE  
LO  
W
B
A
TT  
A
A
C
C
LOSS  
ON  
800-08074 1/11 Rev. A  
 
IPGSM-DP Commercial Fire Communicator – Installation and Setup Guide  
General Information  
The IPGSM-DP Commercial Fire Communicator (henceforth referred to as IPGSM-DP) includes everything  
you need to upgrade a commercial fire system that previously reported by POTS to a system that uses the  
Internet as its primary reporting path, and uses a GSM cellular reporting path as a backup. In addition,  
this communicator utilizes a sophisticated power module (PowerBoost1) that monitors and reports AC power  
loss, low battery, and missing battery conditions.  
Package Contents  
Red Fire Cabinet and Back Plate Antenna and Mounting Adapter  
LED Display board  
Cam Lock with Key  
PowerBoost1  
Battery harness  
Wall Outlet Box (P/N K14358)  
Ferrite Filter  
Mounting Rails (for above)  
Hardware Bag  
Transformer, 18VAC (N8167)  
Dialer Capture Module  
iGSM Communications Module  
50 ohm cable assembly  
Compatible Fire Panels  
The IPGSM-DP works with Fire Panels that use the Contact ID communication format as described in the  
SIA DC-05 Standard. After completing the field installation, verify communications with the central station  
is successful by sending several events. Also, get confirmation that these events were received.  
Note: For a fire panel that has more than 9 active partitions, the first 9 partitions are reported to the  
central station uniquely. Beyond 9 partitions, only the 2nd digit of the partition is reported along with  
a leading zero (example partition 14 is reported as 04). The installer must inform the central  
station of this condition.  
Operation  
The IPGSM-DP replaces the fire panel's POTS communications path. When an event occurs, the fire panel  
goes off-hook to dial the central station. The IPGSM-DP detects the off-hook condition and provides the fire  
panel with a dial tone. When the fire panel detects the dial tone, it begins dialing the central station. The  
IPGSM-DP considers the three second period after dialing as the number dialing has been completed. After  
the dialing is completed, the Dialer Capture Module returns a handshake to the fire panel.  
The fire panel then sends the contact ID reports to the IPGSM-DP, which in turn sends a kiss-off after the  
report is successfully received from the fire panel. Within the IPGSM-DP, the Dialer Capture Module sends  
the contact ID reports over the ECP bus to the iGSM Communications Module. When all the reports are  
sent, the fire panel goes on-hook. The IPGSM-DP then transmits the messages to the central station (either  
over the internet or the GSM network).  
Installation  
UL Compliance  
To meet UL864/NFPA, ensure the following:  
IPGSM-DP must be installed in accordance with NFPA (National Fire Protection Association)  
standards 70 and 72.  
IPGSM-DP must be mounted in the same room and within 20 feet of the fire panel. The wiring must  
be routed through conduit.  
IPGSM-DP, and all equipment used for the IP connection (such as the router, hub, modem, etc.) shall  
be listed, must be powered from an un-switched branch circuit, and be provided with appropriate  
standby power.  
IPGSM-DP must use a 7AH battery (not supplied) to provide 24-hour backup capability.  
1 –  
 
IPGSM-DP Commercial Fire Communicator – Installation and Setup Guide  
STEP 1 – Activate the SIM and Setup the Customer Account  
The communicator requires a subscriber account (customer account) to be setup with AlarmNet Direct. This  
is accomplished by registering the communicator's iGSM communications module with AlarmNet.  
Registering, enables the fire panel to send reports.  
To setup the customer account you will need to contact the central monitoring station to get account  
information, and have access to the AlarmNet Direct website. To access the AlarmNet Direct website visit –  
If you do not wish to use the AlarmNet Direct website, you may call AlarmNet to setup the account, just  
phone 800-222-6525, then select option 1.  
(Monday–Friday 8:00 am to 9:00 pm, Saturday 9:00 am to 5:30 pm EST)  
Have the following information ready:  
Primary City ID (two digits), obtained from your  
monitoring station.  
Primary Subscriber ID (four digits), obtained  
from your monitoring station.  
Primary Central Station ID (two digits), obtained  
from your monitoring station.  
Communication Module's MAC ID, and MAC  
CRC number located on outside of box, and  
inside of the module.  
Note: The IPGSM-DP comes with a SIM (Subscriber Identity Module) that needs to be  
activated.  
1. To activate the SIM, log into the AlarmNet Direct website and choose “SIM Activation/Status”, then  
enter the required information. Click Activate SIM.  
2. Setup the customer account by choosing "Program New Device GSM/I", enter the required  
information. When complete, click DONE.  
STEP 2 – Register the Communications Module with AlarmNet  
Registering the module activates the account with AlarmNet and enables the fire system's control panel to  
send reports. There are three methods that can be used to register the communications module.  
Register the module by logging into AlarmNet Direct and choosing “Show Programmed Devices  
GSM/I”. Search for the account using the Account Information or MAC ID. Under the “Actions”  
column, use the pulldown menu and choose Register. OR  
After the IPGSM-DP is installed and programmed, you can register the module by clicking the  
Tamper Switch 3 times. OR  
After the IPGSM-DP is installed and programmed, you can register the module using the 7720P  
Programming tool. Simply: Press [Shift ] then press []. Please wait for "Registration SUCCESS"  
message.  
2 –  
 
IPGSM-DP Commercial Fire Communicator – Installation and Setup Guide  
STEP 3 – Determine the Signal Strength and Select a Location  
IMPORTANT - Do Not mount this device outdoors.  
RF Exposure  
Warning - The antenna(s) used for this transmitter must be installed to provide a separation  
distance of at least 20 cm from all persons and must not be collocated or operating in con-  
junction with any other antenna or transmitter.  
When choosing a suitable mounting location, understand that signal strength is very important for proper  
operation. For most installations using the supplied antenna, mounting the unit as high as practical, and  
avoiding large metal components provides adequate signal strength for proper operation.  
You will use the iGSM Communications Module to determine signal strength in order to find a suitable  
mounting location.  
Note: If the SIM is already activated, the RSSI signal strength indicators will indicate signal  
strength.  
If the SIM has not been activated, the firmware in the communications module enables it to  
communicate with the cellular network towers (without the SIM being activated) so that  
signal strength measurements can be determined. In this case, you can display the signal  
strength by simultaneously pressing the MODE and TAMPER switches.  
1. For this procedure you will need a fully charged 12V battery.  
2. Attach the Antenna (see illustration on page 5).  
3. Temporarily wire the battery's negative [–] terminal to TB1–4 on the iGSM communications module,  
then wire the battery's plus [+] terminal to TB1–2 on the communications module. Wait about one  
minute for the module to initialize.  
4. Position the assembly near a suitable mounting position and observe  
the RSSI display.  
3 BARS MIN.  
5. Look for a mounting position that yields at least 3 bars lit solid. Four  
R
Y
Y
G
G
G
or five bars are better.  
7845i-GSM-025-V0  
6. Verify the signal strength remains steady for a few minutes, then mark that mounting position.  
Disconnect the battery.  
STEP 4 – Mount and Wire  
For UL compliant installations, refer to the topic on UL Compliance in this manual.  
For Dry/Indoor use only.  
Unless otherwise specified, use 18AWG.  
External cabinet wiring may be routed in conduit if desired.  
This communicator comes partially assembled with all the components mounted except the Antenna, LED  
Display board, and PowerBoost1. To protect certain components on the PowerBoost1, it is shipped un-  
mounted but fully wired.  
Note: Refer to the diagram on page 5, and to the Wiring Diagram on the inside of the back cover of  
this manual for wiring and component identification.  
1. Remove knockouts from cabinet to accommodate the power input wires, and wiring to the control  
panel. Then mount the cabinet securely to the wall using 4 screws or bolts. Use mounting screws or  
bolts that are suitable for the material being anchored to.  
2. Ensure the cabinet door lock is installed.  
3 –  
 
IPGSM-DP Commercial Fire Communicator – Installation and Setup Guide  
3. Install the two plastic mounting rails for the LED Display board. They simply snap into the back  
plate holes.  
4. Connect the LED Display board to its connector, then slide the board into the mounting rails.  
(Yellow LED and Buzzer are on top.)  
5. Carefully remove the packaging material that surrounds the PowerBoost1.  
6. Mount the PowerBoost1 on the three unused standoffs. Use the plastic screw (prevents shorting)  
to secure the upper right corner of the PowerBoost1 and the two metal screws and lock washers to  
fasten the left side of the circuit board. Ensure the lock washers are located between the circuit  
board and the head of the two metal screws.  
7. Mount the Wall Outlet Box to an un-switched facility power outlet and run a conduit to the cabinet.  
8. In this step DO NOT plug the transformer in. Route 16AWG wire from the transformer,  
through the conduit. Pass the wires through the Ferrite Filter, then loop the wires back through  
again making a loop. Connect the wires to the PowerBoost1 AC terminals.  
9. Connect and route 16AWG insulated wire from facility power ground (typically a cold water pipe) to  
the cabinet's ground post. Ensure all ground connections are tight.  
10. Connect the Ethernet cable and the Telco 1 and Telco 2 lines. If you choose to use an optional  
Cabinet Tamper Switch (if the control panel supports it) mount and wire it.  
Note: The Ethernet cable, Telco 1, Telco 2 lines, and the optional cabinet Tamper Switch (if used)  
must be run through conduit.  
11. Verify the PowerBoost1 module DIP switches are configured as shown below.  
PowerBoost1  
ON  
1 2 3  
5
4
ON  
(Switch handle = white)  
1
2
3
4
5
12. Ensure the following:  
LED Display board is fully seated.  
All wiring terminals and connectors are tight.  
All wiring has been completed and secured with cable ties.  
13. Install the battery (not supplied). Plug the power transformer in, and attach the battery cable.  
4 –  
 
IPGSM-DP Commercial Fire Communicator – Installation and Setup Guide  
ANTENNA  
WALL OUTLET  
BOX (K14358)  
TRANSFORMER  
(N8167)  
NUT,  
WASHER  
ANTENNA  
MOUNTING  
ADAPTER  
CABINET  
DOOR  
ON  
1
2
3
4
5
RED  
GREEN  
Dialer Capture Module  
FOR EXTERNAL ANTENNA  
50 OHM MMCX ONLY  
7720P PROGRAMMER PORT  
NOT FOR TELEPHONE SERVICE USE!  
PRIMARY POWER:  
9
-
16.5 VAC  
BATTERY  
FUSE  
CURRENT: 900mA PEAK, 70mA STANDBY  
BATTERY: 8V. 3.1 AHr FOR 24 Hr BACKUP  
TO Facility  
Ground  
FCC:XXXXXXXXXX IC: YYYYYYYYYY  
TB 1  
1
2
3
4
5
6
7
8
9
+
10  
11  
CONDUIT  
BATTERY  
7AH  
(not supplied)  
iGSM Comm Module  
Wiring for Grounds, Power, and RF  
5 –  
 
IPGSM-DP Commercial Fire Communicator – Installation and Setup Guide  
STEP 5 – Program the Communications Module  
You must use the 7720P Programming tool to program the IPGSM-DP.  
When using the 7720P Programming tool, the values given below are for most installations. Press the [#]  
key to accept the displayed default value (xxx) or enter the new value and press the [#] key for the next  
prompt. Use the [Space] key to scroll through a list of options.  
(no display)  
1.  
2.  
3.  
4.  
5.  
6.  
7.  
8.  
Connect the 7720P.  
7720P PROGRAMMER  
Strt Prog Mode? Y/N  
Program Device? Y/N  
Com Path Choice (IP&GSM)  
Primary City ID (??)  
Press [#].  
Press [Shift] then [Y], then [#].  
Press [Shift] then [Y], then [#].  
Press [Space] to scroll choices; IP&GSM, IP, or GSM. At choice, press [#].  
Enter number 01-99, then press [#].  
Enter number 01-FE, then press [#].  
Enter number 0001-9999, then press [#].  
Primary CS ID (??)  
Primary Sub ID (????)  
Note: If a Com Path Choice of IP&GSM or IP was selected, prompt 9 will  
appear.  
Use DHCP? Y/N (Y)  
9.  
If your router is configured for DHCP, press [Shift] then [Y], then press [#].  
Note: If DHCP is not selected (your router is set for a static IP), prompts 10  
through 13 will appear.  
NIC IP Address:  
255.255.255.255  
10.  
11.  
12.  
13.  
14.  
15.  
16.  
17.  
Enter choice, then press [#]. Follow the prompts.  
Enter choice, then press [#]. Follow the prompts.  
Enter choice, then press [#]. Follow the prompts.  
Enter choice, then press [#]. Follow the prompts.  
Enter choice, then press [#]. Follow the prompts.  
Enter choice, then press [#]. Follow the prompts.  
Press [Shift] then [Y], then press [#].  
Subnet Mask:  
255.255.255.255  
Gateway IP Address:  
255.255.255.255  
DNS Serv IP Addr:  
255.255.255.255  
Review? Y/N  
Create Password? Y/N  
Exit Prog Mode? Y/N  
DONE  
Note: If an error in programming occurs, set the factory defaults (see next topic) and  
reprogram the IPGSM-DP.  
6 –  
 
IPGSM-DP Commercial Fire Communicator – Installation and Setup Guide  
To exit the programming mode, press [N] in response to the "Review?" prompt. Then press [Y] to the "Exit  
Prog Mode?" prompt. Upon exiting, the root file is updated to log the changes made. A message is displayed  
telling the user that this step is being executed. When complete, the message "DONE" is displayed to  
indicate the file was successfully uploaded.  
Note: If critical configuration changes were made, such as the mode of operation, the  
communications module will reset to ensure that the programming features are enabled.  
If the file is not successfully uploaded, one of the following prompts will be displayed. Follow the steps  
shown below until the upload is successful.  
Display  
Description  
What to do  
Module is not yet initialized.  
Wait for RSSI indicator LEDs to be lit.  
Press [Y].  
Cannot Upload  
Try Again? Y/N_  
Network problem, or you answered "N"  
to "Cannot Upload Try Again?" prompt.  
Initiate the Force Server Update  
Command by pressing the [0] key.  
Failed to Update  
Root File!  
Setting Factory Defaults  
To reset the programming options to factory-default values, at the "Exit Prog Mode?" prompt press [Shift]  
plus [ESC]. Note, setting the factory defaults will also erase any password that may have been entered.  
Press [Y] to reset factory default values.  
Press [N] to cancel this function.  
Set Default?  
Y/N_  
Press [Shift] then [Y], then [#]. The Create Password prompt appears, follow the prompts then exit.  
STEP 6 – Configure the Fire Panel  
1. Ensure the Telco Fault on the panel is enabled. Then choose a setting that is no higher than 90  
seconds (or as close to that) as the panel allows.  
2. Ensure no more than 1 pause character (usually a comma) is programmed into the dialing string  
(usually 2 seconds). Note, this is necessary since the Dialer Capture Module waits only 3 seconds  
after the phone number is dialed. Having more than 3 seconds of pause time will cause it to think  
the phone number is complete and cause it to generate the high-low tones at an incorrect moment.  
STEP 7 – Test the System  
1. Close the Wall Outlet Box, then close and lock the cabinet cover.  
2. Refer to the fire panel's installation/operation guide the testing procedure.  
3. (Notify the monitoring station that a test will be conducted.) Test the system to ensure it is  
operating.  
7 –  
 
IPGSM-DP Commercial Fire Communicator – Installation and Setup Guide  
IPGSM-DP Trouble Detection Information  
Telco 1 is used for the Fire Panel to output contact ID messages to the IPGSM-DP, and Telco 2 is used by the  
IPGSM-DP to report faults to the Fire Panel. If Telco 1 is not operational, the Fire Panel will use Telco 2 to  
report events if there are no faults in the iGSM Communications module.  
Fault Condition  
Indication to Fire Panel  
PowerBoost1 fault  
Telco 2 is cut.  
iGSM Communications Module fault  
Telco 2 is cut.  
Failure of one of the two  
communications paths.  
Telco 1 and 2 are cut.  
Failure of both communications  
paths.  
Dialer Capture Module buffer is full.  
Hang up. (Panel will retry, giving the buffer a chance to empty.)  
Dialer Capture Module Information  
LED Indicator  
STATUS  
RED – Steady ON  
Messages exist in buffer.  
RED – Flashing  
No messages to be sent. Waiting for messages.  
Normal Indication.  
GREEN – Steady ON  
GREEN – Blinks every 2 sec.  
GREEN – Blinks twice every sec.  
GREEN – Blinks 10 times every sec.  
PowerBoost1 communication problem.  
Communication Module connection is lost.  
PowerBoost1 and Communications Module connection is lost.  
Note: Telco ports 1 (primary dialer)  
and 2 (secondary dialer) may be  
used instead of the terminal board.  
Whichever connection method is  
used, both Telco paths must be  
connected to the Fire Panel.  
RED  
GREEN  
Dialer Capture Module  
LED Display Information  
Panel Status  
LED Indicator  
RADIO TROUBLE  
Yellow – ON when radio trouble is present.  
Buzzer – Upon loss of AC power, this will  
beep once every 10 seconds.  
LOW BATTERY  
Yellow – ON when battery is low.  
Yellow – (not used)  
AC LOSS  
AC ON  
Yellow – ON when no AC is present.  
Green – ON when AC is present.  
8 –  
 
IPGSM-DP Commercial Fire Communicator – Installation and Setup Guide  
Violet  
Black  
White  
Note: If a wire pulled out of the LED Board Connector  
refer to the diagram on right and reinsert wire, ensuring  
the connector pin is locked in.  
LED Board  
Connector  
Wires  
NC  
NC  
Red  
Brown  
Yellow  
Gray  
PowerBoost1 Module Information  
LED Indicator  
STATUS  
AC  
AC power available.  
(green)  
ACTIVE  
(green)  
Cyclical flashing – normal communications.  
Repetition of 3 flashes – loss of communications.  
LOW BATT (yellow)  
TROUBLE (yellow)  
Missing or low battery.  
One or more trouble conditions exist, such as; overload, output supervision,  
ground fault, or charger failure.  
Notes:  
If AC power is lost and the battery voltage falls below 10v, the module's output voltage will be  
turned off. The output power is turned back on when AC power is restored.  
You must use the DIP switch settings shown below.  
PowerBoost1  
LOW BATT LED  
INDICATOR  
TROUBLE LED  
INDICATOR  
Confiure DIP switch  
as shown:  
ON  
1
2
3
4
5
ON  
1 2 3  
5
4
(Switch handle = white)  
AC LED  
INDICATOR  
ACTIVE LED  
INDICATOR  
iPGSM-COM-003-V0  
9 –  
 
IPGSM-DP Commercial Fire Communicator – Installation and Setup Guide  
iGSM Communications Module Information  
ON – NOT registered with AlarmNet.  
OFF – Registered with AlarmNet.  
FAST BLINK – Download session with Compass  
in progress.  
GRN  
PRIMARY POWER: 9 - 16.5 VAC  
SLOW BLINK – In unison with yellow LED,  
registration in progress.  
CURRENT: 900mA PEAK, 70mA STANDBY  
BATTERY: 8V. 3.1 AHr FOR 24 Hr BACKUP  
7720P  
Programmer  
Port  
FCC:XXXXXXXXXX IC: YYYYYYYYYY  
ON – Message transmission pending.  
QUICK PERIODIC BLINK – Normal.  
FAST BLINK – Message waiting for network ACK.  
SLOW BLINK – Idle power abnormal.  
SLOW BLINK – In unison with green LED,  
registratration in progress.  
YEL  
RED  
TB 1  
1
2
3
4
5
6
7
8
RSSI / Mode  
and  
status LEDs  
Tamper  
Switch  
ON – No contact with network.  
OFF – Normal.  
SLOW BLINK – Loss of communication with the  
Dialer Capture Module (ECP fault).  
Mode  
Switch  
9
10  
11  
FAST BLINK – No network contact AND loss of communi-  
cation with the Dialer Capture Module  
.
Note: If all LEDs FAST BLINK in unison with  
the RSSI LEDs this indicates a Hardware Error.  
Network Collision  
YELLOW  
BLINKING – Network collision detected.  
OFF – Normal.  
ON – 100 MB/S link to Internet.  
OFF – 10 MB/S link to Internet.  
Link Speed  
GREEN  
ON – Ethernet Link detected.  
OFF – No link detected.  
FAST BLINK – Transmitting/Receiving Data.  
Ethernet Link/Activity  
GREEN  
MODULE'S RECEIVED SIGNAL STRENGTH (RSSI)  
When the Mode Switch is NOT depressed, LED 1 will illuminate red.  
The remaining LEDs indicate RSSI (Received Signal Strength).  
MODULE'S OPERATION MODE  
When the Mode Switch IS depressed, LED 1 will be OFF.  
LEDs 2 and 3 indicate the module's communication mode with the Dialer Capture Module.  
Mode  
LED 2 (yellow)  
LED 3 (yellow)  
OFF  
ON  
OFF  
OFF  
ON  
ECP  
Zone (NOT USED)  
4204 (NOT USED)  
2 - 4204 (NOT USED)  
OFF  
ON  
ON  
MODULE'S STATUS  
When the Mode Switch IS depressed, LED 1 will be OFF.  
LEDs 4, 5, and 6 indicate the module's Status.  
LED 4 (green)  
LED 5 (green)  
LED 6 (green)  
ON - Connected to  
Internet.  
ON - GPRS service  
available.  
ON - Module registered, no second  
site available.  
OFF - Not connected  
to Internet.  
OFF - No GPRS service OFF - Module not registered with  
available network carrier.  
FAST BLINK - GPRS in SLOW BLINK - Module registered, second  
use.  
site available, and low signal strength.  
NORMAL BLINK - Module registered, second  
site available, acceptable signal strength.  
FAST BLINK - Module registered, second  
site available, excellent signal strength.  
10 –  
 
IPGSM-DP Commercial Fire Communicator – Installation and Setup Guide  
RF Specifications  
Transmission  
Frequency  
Transmit  
Power  
Receive  
Frequency  
Receive  
Sensitivity  
(dBm)  
Number  
of  
Channels  
Channel  
Spacing  
(MHz)  
Duplex  
Separation  
Band  
(MHz)  
(dBm)  
(MHz)  
(kHz)  
GSM 850  
GSM 900  
GSM 1800  
GSM 1900  
824-849  
890-915  
33  
33  
30  
30  
869-894  
935-960  
-107  
-107  
124  
124  
374  
299  
200  
200  
200  
200  
45  
45  
95  
80  
1710-1785  
1850-1910  
1805-1880  
1930-1990  
-106  
-105.5  
IPGSM-DP Specifications  
ITEM  
SPECIFICATION  
Width = 12 3/4 inches  
Height = 14 7/8 inches  
Depth = 3 inches  
Cabinet Dimensions:  
Primary – 120VAC, 60Hz  
Secondary – 18VAC, 50VA  
Transformer: N8167  
12V, 7Ah sealed lead acid type (not supplied)  
Battery:  
Use a Honeywell 712BNP, Yuasa NP7-12 or equivalent.  
maximum 1A  
Battery Charging Current:  
Supervision:  
The AC power, backup battery, IP communications, and GSM  
communications are monitored.  
11 –  
 
IPGSM-DP Commercial Fire Communicator – Installation and Setup Guide  
NOTES  
12 –  
 
Wiring Diagram  
The wiring diagram below is depicted for point-to-point electrical connection checks used for troubleshooting  
or component replacement. It is not intended to show the physical routing of wires. When replacing a wire  
or component, ensure the wire is routed in the same manner as the original factory wire.  
WALL OUTLET  
BOX (K14358)  
TRANSFORMER  
(N8167)  
ANTENNA  
(Buzzer)  
OPTIONAL CABINET  
TAMPER SWITCH  
WHT (LO BATT)  
CABINET  
DOOR  
LED Display  
RADIO  
PowerBoost1  
Buzzer  
TROUBLE  
TROUBLE  
LOW  
BATT  
VIO  
BLK  
WHT  
RED  
BRN  
YEL  
GRA  
LOW BATT  
(not used)  
AC LOSS  
AC ON  
ON  
1
2
3
4
5
RED  
GREEN  
Dialer Capture Module  
AC  
ERTH GND  
GND  
TX  
BLK  
GRN  
(RADIO TROUBLE)  
RX  
YEL  
OUT+  
DC+  
OUT-  
DC-  
RED  
RED  
BLK  
N/U  
OUT+  
DC+  
OUT-  
DC-  
N/U  
iGSM Comm  
(AC ON)  
GRA  
Module  
STATUS  
MESSAGE  
FAULT  
FOR EXTERNAL ANTENNA  
50 OHM MMCX ONLY  
BATTERY  
7720P PROGRAMMER PORT  
NOT FOR TELEPHONE SERVICE USE!  
FUSE  
7720P  
PRIMARY POWER:  
9
-
16.5 VAC  
CURRENT: 900mA PEAK, 70mA STANDBY  
BATTERY: 8V. 3.1 AHr FOR 24 Hr BACKUP  
PROGRAMMER  
FCC:XXXXXXXXXX IC: YYYYYYYYYY  
PORT  
TB 1  
1
BATTERY  
2
3
4
5
6
7
8
9
+
RSSI/MODE  
+12V In  
GND  
ECP In  
INDICATORS  
7AH  
(not supplied)  
MODE & STATUS  
SWITCH  
ECP Out  
TAMPER  
SWITCH  
Use a Honeywell 712BNP,  
10  
Yuasa NP7-12, or equivalent.  
INTERNET  
CONNECTIVITY  
INDICATORS  
11 FLT Out  
CONDUIT  
To Router  
To Fire Panel  
To Fire Panel  
NOTES All circuits are power limited except the backup battery which is non-power limited.  
Non-power limited wiring must be separated from the power limited wiring by at least 1/4 inch.  
If desired, use a Honeywell 955WH Tamper Switch with the 28-2 bracket.  
 
FCC STATEMENT  
Note: This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to part  
15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when  
the equipment is operated in a commercial environment.  
This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance  
with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a  
residential area is likely to cause harmful interference in which case the user will be required to correct the interference  
at his own expense.  
FCC / IC STATEMENT  
This device complies with Part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This  
device may not cause harmful interference (2) This device must accept any interference received, including  
interference that may cause undesired operation.  
The user shall not make any changes or modifications to the equipment unless authorized by the Installation  
Instructions or User's Manual. Unauthorized changes or modifications could void the user's authority to operate the  
equipment.  
DOCUMENTATION AND ONLINE SUPPORT  
For the latest documentation and online support information, please go to:  
WARRANTY  
For the latest warranty information, please go to:  
2 Corporate Center Drive, Suite 100,  
P.O. Box 9040, Melville, NY 11747  
Copyright 2011 Honeywell International Inc.  
Ê800-08074AŠ  
800-08074 1/11 Rev. A  
 

Graco Inc Paint Sprayer 232610 User Manual
Grindmaster Coffeemaker 70752 User Manual
Grizzly Kitchen Utensil T25225 User Manual
Haan Iron TS 30 User Manual
Haier Water Heater FCD JTSA50 III User Manual
Harbor Freight Tools Air Compressor 93657 User Manual
Harbor Freight Tools Automobile Parts 92840 User Manual
Heath Zenith Door 598 1123 02 User Manual
Hotpoint Food Warmer C150E User Manual
IBM All in One Printer TDS800 User Manual