VR8104, VR8204, and VR8304
Intermittent Pilot Combination
Gas Controls
INSTALLATION INSTRUCTIONS
These gas controls are available in a range of valve
capacities, see Table 1. (Table 2 provides gas capacity
conversion factors.) The suffix letter indicates
APPLICATION
These intermittent pilot gas controls are used in gas-fired
appliances with up to 415 ft3/hr capacity at 1 in. wc
pressure drop (8.5 m3/hr at 0.25 kPa) on natural gas.
They include safety shutoff, a manual valve, two
automatic operators, a pressure regulator and a pilot
adjustment.
temperature range and regulator type, see Table 3.
For CE-approved models, the relevant sections of these
instructions and Table 4 are applicable.
a
Table 1. Valve Capacity
AGA Certified Maximum
Regulation for
AGA Certified Capacity for
AGA Certified Minimum
Regulation for Natural Gas
Size
Inlet-Outlet
Natural Gas
Natural Gas
3
3
3
3
3
3
Model
VR8104
(in.)
ft /hr
m /hr
ft /hr
m /hr
ft /hr
m /hr
d
e
f
1/2 x 1/2
85
2.3
4.2
6.8
7.6
8.5
0.4
0.6
0.8
120
200
340
370
415
3.4
5.7
9.6
10
20
30
VR8204
150
240
270
300
3
b,c
b,c
b,c
VR8304
VR8304
VR8304
1/2 x 3/4
3/4 x 3/4
1.05
11.8
a
3
Capacity based on 1000 Btu/ft , 0.64 sp gr natural gas at 1 in. wc pressure drop (37.3 MJ/m , 0.64 sp gr natural gas
at 0.25 kPa pressure drop).
b
c
d
e
f
Capacity is reduced by 5 percent when using an outlet screen.
Valves are guaranteed at only 77 percent of the rating.
Minimum regulation for LP gas is 15,000 Btuh.
Minimum regulation for LP gas is 40,000 Btuh.
Minimum regulation for LP gas is 50,000 Btuh.
Table 2. Gas Capacity Conversion Factor.
CE-Only Models
Multiply Listed
Capacity By
These gas controls are used in appliances up to 121kW
or 415 kBTUH on natural gas and approved on EN126,
which consists of one automatic safety shutoff valve,
Class B or C, one servo-operated shutoff valve, Class D,
pressure governor, Class C, manually-operated valve,
with or without pilot outlet. Only the A, H and U models
are available CE-approved.
Gas
Specific Gravity
Manufactured
Mixed
0.60
0.70
1.53
0.516
0.765
1.62
Propane
Table 4 shows the additional specifications for the
CE-only models.
® U.S. Registered Trademark
Copyright © 2000 Honeywell Inc. • All Rights Reserved
69- 1225- 4
VR8104, VR8204 AND VR8304 INTERMITTENT PILOT COMBINATION GAS CONTROLS
Table 6. Flange Adapter Part Numbers.
SPECIFICATIONS
a,b
Part Number
Inlet/Outlet
Body Pattern: Straight through; see Table 1 for inlet and
outlet size.
Pipe Size
(in. NPT)
Flange Without Hex
With Hex
Wrench
Type
Straight
Elbow
Wrench
393690-1
393690-2
393690-6
393690-3
393690-4
393690-5
3/8
393690-11
393690-12
393690-16
393690-13
393690-14
393690-15
Electrical Ratings:
Voltage and Frequency: 24 Vac, 60 Hz.
Current Draw: 0.5A with both operators energized.
3/8
1/2
1/2
3/4
3/4
Straight
Elbow
Capacity: See Table 1.
Straight
Elbow
Conversion: Use conversion factors in Table 2 to con-
vert capacities for other gases.
a
Flange kits include one flange, one O-ring and four
mounting screws.
Regulation Range: See Table 1.
b
Do not use flanges on control models with 3/4 in. inlet
and 3/4 in. outlet. On models with 1/2 in. inlet and
3/4 in. outlet, use flanges only on the 1/2 in. inlet side.
Natural-LP Gas Conversion Kits: See Table 5.
Table 5. Natural-LP Gas Conversion Kits.
Heavy demands are made on the controls when
intermittent pilot systems are used on central heating
equipment in barns, greenhouses, and commercial
properties and on heating appliances such as
commercial cookers, agricultural equipment, industrial
heating equipment and pool heaters.
Model No.
Suffix Letter Natural Gas to LP
Kit to Convert
Kit to Convert LP
to Natural Gas
H, K, M
P
393691
394588
Not field
convertible.
Not field
convertible.
Q
R
396021
396025
Special steps may be required to prevent nuisance
shutdowns and control failure due to frequent cycling,
severe environmental conditions related to moisture,
corrosive chemicals, dust or excessive heat. These
applications require Honeywell Home and Building
Control Engineering review; contact your Honeywell
Sales Representative for assistance.
Not required,
convertible valve.
Not required,
convertible valve.
Pipe Adapters:
Angle and straight adapters available for 3/8-, 1/2- and
3/4-in. pipe. See Table 6. Flange kits include one
flange with attached O-ring, four mounting screws, a
9/64 in. hex wrench and instructions.
Review the following conditions that can apply to your
specific installation and follow the precautions
suggested.
Approvals:
American Gas Association Design Certificate: L2025006.
Canadian Gas Association Design Certificate: L2025006.
Australian Gas Association Design Certificate: 4214.
Approved for Delta C applications.
Frequent Cycling
European Community (CE) Certificate: Pending.
This control is designed for use on appliances that
typically cycle three to four times an hour only during the
heating season. In year-around applications with greater
cycling rates, the control can wear out more quickly.
Perform a monthly checkout.
PLANNING THE INSTALLATION
WARNING
Can cause property damage, severe injury,
Water or Steam Cleaning
Fire or Explosion Hazard.
If a control gets wet, replace it. If the appliance is likely to
be cleaned with water or steam, protect (cover) the
control and wiring from water or steam flow. Mount the
control high enough above the bottom of the cabinet so it
does not get wet during normal cleaning procedures.
or death.
Follow these warnings exactly:
1. Plan the installation as outlined below.
2. Plan for frequent maintenance as described in
the Maintenance section.
High Humidity or Dripping Water
Dripping water can cause the control to fail. Never install
an appliance where water can drip on the control. In
addition, high ambient humidity can cause the control to
corrode and fail. If the appliance is in a humid
atmosphere, make sure air circulation around the control
is adequate to prevent condensation. Also, regularly
check out the system.
3
69-1225—4
VR8104, VR8204 AND VR8304 INTERMITTENT PILOT COMBINATION GAS CONTROLS
Corrosive Chemicals
CAUTION
Can burn out valve coil terminals.
Never apply a jumper across (or short) the valve
coil terminals, even temporarily.
Corrosive chemicals can attack the control, eventually
causing a failure. If chemicals are used for routine
cleaning, avoid contact with the control. Where
chemicals are suspended in air, as in some industrial or
agricultural applications, protect the control with an
enclosure.
Equipment Damage.
Follow the appliance manufacturers instructions if
available; otherwise, use these instructions as a guide.
Dust or Grease Accumulation
Heavy accumulations of dust or grease can cause the
control to malfunction. Where dust or grease can be a
problem, provide covers for the control to limit
contamination.
IMPORTANT
These gas controls are shipped with protective
seals over the inlet and outlet tappings. Do not
remove the seals until ready to install adapters
or connect the piping.
Heat
Converting Gas Control from Natural Gas
to LP Gas (or LP Gas to Natural Gas)
Excessively high temperatures can damage the control.
Make sure the maximum ambient temperature at the
control does not exceed the rating of the control. If the
appliance operates at very high temperatures, use
insulation, shielding, and air circulation, as necessary, to
protect the control. Proper insulation or shielding should
be provided by the appliance manufacturer; verify proper
air circulation is maintained when the appliance is
installed.
WARNING
Fire Or Explosion Hazard.
Can cause property damage, severe injury
or death.
1. Do not attempt to convert step-opening models
(suffix letter P).
2. Always change the main and pilot burner
orifices when converting from natural to LP gas
or from LP to natural gas. Carefully follow
appliance manufacturer specifications and
instructions to assure proper appliance
conversion.
3. Gas controls are factory-set for natural (and
manufactured) or LP gas. Do not attempt to
use a gas control set for natural
INSTALLATION
When Installing this Product...
1. Read these instructions carefully. Failure to follow
them could damage the product or cause a
hazardous condition.
2. Check the ratings given in the instructions and on
the product to make sure the product is suitable for
your application.
(manufactured) gas on LP gas, or a gas control
set for LP gas on natural (manufactured) gas.
3. Installer must be a trained, experienced service
technician.
Controls with standard, slow-opening, and two-stage
regulators (model numbers with suffix H, K, M, or Q) can
be converted from one gas to the other with a conversion
kit (ordered separately). See Table 4 for the correct
conversion kit.
4. After installation is complete, check out product
operation as provided in these instructions.
WARNING
Fire or Explosion Hazard.
Convertible Pressure Regulators
Can cause property damage, severe injury
or death.
Follow these warnings exactly:
Controls with suffix letter R are convertible pressure
regulator models. They can be converted from natural
gas to LP gas or from LP gas to natural gas without a
conversion kit.
1. Disconnect power supply before wiring to
prevent electrical shock or equipment damage.
2. To avoid dangerous accumulation of fuel gas,
turn off the gas supply at the appliance service
valve before starting installation, and perform
Gas Leak Test after installation is complete.
3. Do not bend pilot tubing at gas control or pilot
burner after compression fitting is tightened, or
gas leakage at the connection can result.
4. Always install a sediment trap in the gas
supply line to prevent contamination of the gas
control.
5. Do not force the gas control knob. Use only
your hand to turn the gas control knob. Never
use any tools. If the gas control knob will not
operate by hand, the gas control should be
replaced by a qualified service technician.
Force or attempted repair may result in fire or
explosion.
Before converting the control from one gas to another,
check the control label and the appliance manufacturer’s
rating plate to determine if the pressure regulator setting
(factory set) will meet the appliance manifold
requirements after conversion.
NOTE: Convertible pressure regulator models (suffix
letter R) do not have field-adjustable regulators.
If the factory pressure regulator setting meets the
appliance manifold requirement, convert the control as
follows:
1. Remove the pressure regulator cap, Fig. 1.
2. Invert the cap so that the letters appear that
represent the gas type appropriate for the
appliance. NAT for natural manufactured gas, LP
for liquid petroleum gas.
3. Replace the cap and tighten firmly.
69-1225—4
4
VR8104, VR8204 AND VR8304 INTERMITTENT PILOT COMBINATION GAS CONTROLS
OR
OTHER SIDE
OF CAP
PRESSURE
REGULATOR
CAP
1
VALVE OUTLET
FLANGE
M11678
9/64 INCH HEX SCREWS (4)
Fig. 1. Top view of convertible
pressure regulator cap.
DO NOT OVERTIGHTEN SCREWS. TIGHTEN TO
25 INCH-POUNDS.
1
M9046
Fig. 2. Firmly fasten flange to valve, but
do not overtighten screws.
Install Adapters To Control
If adapters are being installed on the control, mount them
as follows:
Location
The combination gas control is mounted in the appliance
vestibule on the gas manifold. If this is a replacement
application, mount the gas control in the same location
as the old control.
Flanges
1. Choose the appropriate flange for your application.
2. Remove the seal over the gas control inlet or
outlet.
3. Make sure that the O-ring is fitted in the groove of
the flange. If the O-ring is not attached or is
missing, do not use the flange.
4. With the O-ring facing the control, align the screw
holes on the gas control with the holes in the
flange. Insert and tighten the screws provided with
the flange. See Fig. 2. Tighten the screws to 25
inch-pounds of torque to provide a gas-tight seal.
Locate the combination gas control where it cannot be
affected by steam cleaning, high humidity, or dripping
water, corrosive chemicals, dust or grease accumulation
or excessive heat. To assure proper operation, follow
these guidelines:
•
•
Locate gas control in a well-ventilated area.
Mount gas control high enough above cabinet bottom
to avoid exposure to flooding or splashing water.
Assure the ambient temperature does not exceed the
ambient temperature ratings for each component.
Cover gas control if appliance is cleaned with water,
steam, or chemicals or to avoid dust and grease
accumulation.
•
•
Bushings
1. Remove the seal over the control inlet or outlet.
2. Apply a moderate amount of good quality pipe
compound to the bushing, leaving two end threads
bare. On an LP installation, use compound that is
resistant to LP gas. Do not use Teflon tape.
•
Avoid locating gas control where exposure to
corrosive chemical fumes or dripping water are likely.
3. Insert the bushing in the control and carefully
thread the pipe into the bushing until tight.
Install Piping to Control
All piping must comply with local codes and ordinances
or with the National Fuel Gas Code (ANSI Z223.1,
NFPA No. 54), whichever applies. Tubing installation
must comply with approved standards and practices.
Complete the instructions below for installing the piping,
installing the control, connecting the pilot gas tubing and
the wiring. Make sure the leak test you perform on the
control after completing the installation includes leak
testing the adapters and screws. If you use a wrench on
the valve after the flanges are installed, use the wrench
only on the flange, not on the control. See Fig. 5.
1. Use new, properly reamed pipe that is free from
chips. If tubing is used, make sure the ends are
square, deburred and clean. All tubing bends must
be smooth and without deformation.
2. Run pipe or tubing to the control. If tubing is used,
obtain a tube-to-pipe coupling to connect the
tubing to the control.
3. Install a sediment trap in the supply line to the
control. See Fig. 3.
5
69-1225—4
VR8104, VR8204 AND VR8304 INTERMITTENT PILOT COMBINATION GAS CONTROLS
4. Apply a moderate amount of good quality pipe
compound (do not use Teflon tape) only to the
pipe, leaving two end threads bare. On LP
installations, use a compound resistant to LP gas.
See Fig. 4.
DROP
PIPED
GAS
SUPPLY
GAS
CONTROL
HORIZONTAL
5. Remove the seals over the control inlet and outlet if
RISER
necessary.
GAS
CONTROL
6. Connect the pipe to the control inlet and outlet. Use
a wrench on the square ends of the control. If a
flange is used, place the wrench on the flange
rather than on the gas control. Refer to Fig. 5
and 6.
PIPED
GAS
SUPPLY
3 IN.
(76 MM)
MINIMUM
2
DROP
Connect Pilot Gas Tubing
HORIZONTAL
3 IN.
1. Cut tubing to the desired length and bend as
necessary for routing to the pilot burner. Do not
make sharp bends or deform the tubing. Do not
bend the tubing at the gas control after the
compression nut is tightened, because this can
result in gas leakage at the connection.
2. Square off and remove burrs from the end of the
tubing.
(76 MM)
MINIMUM
TUBING
GAS
SUPPLY
1
2
GAS
CONTROL
RISER
3 IN.
(76 MM)
MINIMUM
3. Unscrew the brass compression fitting from the
pilot outlet (Fig. 6). Slip the fitting over the tubing
and slide out of the way. See Fig. 7.
2
ALL BENDS IN METALLIC TUBING SHOULD BE SMOOTH.
1
2
NOTE: When replacing a control, cut off the old
compression fitting and replace with the
compression fitting provided on the combination
gas control. Never use the old compression
fitting because it may not provide a gas-tight
seal.
CAUTION: SHUT OFF THE MAIN GAS SUPPLY BEFORE REMOVING
END CAP TO PREVENT GAS FROM FILLING THE WORK AREA. TEST
FOR GAS LEAKAGE WHEN INSTALLATION IS COMPLETE.
M3077
Fig. 3. Sediment trap installation.
4. Push the tubing into the pilot gas tapping on the
outlet end of the control until it bottoms. While
holding the tubing all the way in, slide the fitting
into place and engage the threads; then turn until
finger tight. Tighten one more turn with a wrench,
but do not overtighten.
5. Connect the other end of the tubing to the pilot
burner according to the pilot burner manufacturer’s
instructions.
Install Control
1. Mounted 0 to 90 degrees in any direction, including
vertically, from the upright position of the gas
control knob.
2. Mount so the gas flow is in the direction of the
arrow on the bottom of the control.
3. Thread the pipe the amount shown in Table 7 for
insertion into control or adapters. Do not thread
pipe too far. Valve distortion or malfunction can
result if the pipe is inserted too deeply.
TWO IMPERFECT
GAS CONTROL
THREADS
Table 7. NPT Pipe Thread Length (in.).
PIPE
Pipe
Size
Thread Pipe Maximum Depth Pipe can
this Amount
be Inserted into Control
THREAD PIPE THE AMOUNT
SHOWN IN TABLE FOR
INSERTION INTO GAS CONTROL
APPLY A MODERATE AMOUNT OF
PIPE COMPOUND TO PIPE ONLY
(LEAVE TWO END THREADS BARE).
3/8
9/16
3/8
1/2
3/4
3/4
1/2
3/4
M3075B
13/16
Fig. 4. Use moderate amount of pipe compound.
69-1225—4
6
VR8104, VR8204 AND VR8304 INTERMITTENT PILOT COMBINATION GAS CONTROLS
WHEN FLANGE IS USED
WHEN FLANGE IS NOT USED
APPLY WRENCH
FROM TOP OR
BOTTOM OF GAS
CONTROL TO
APPLY WRENCH
TO FLANGE ONLY
EITHER SHADED AREA
M3079
Fig. 5. Proper use of wrench on gas control with and without flanges.
HI-LO
ADJUSTMENT SCREWS
(UNDER CAP)
PRESSURE REGULATOR
ADJUSTMENT
(UNDER CAP SCREW)
WIRING
TERMINALS (3)
REGULATOR
VENT COVER
OUTLET
PRESSURE
TAP
INLET
PRESSURE TAP
LO
HI
OUTLET
INLET
TWO-STAGE
PRESSURE
REGULATOR
MODEL
PILOT OUTLET
INLET
GAS
PILOT ADJUSTMENT
CONTROL
KNOB
(UNDER CAP SCREW)
M10968A
Fig. 6. Top view of gas control.
All wiring must comply with applicable electrical codes
and ordinances.
GAS CONTROL
TIGHTEN NUT ONE TURN
BEYOND FINGER TIGHT.
Disconnect power supply before making wiring
connections to prevent electrical shock or equipment
damage.
TO PILOT
BURNER
FITTING BREAKS OFF AND CLINCHES
TUBING AS NUT IS TIGHTENED.
1. Check the power supply rating on the gas control
and make sure it matches the available supply.
Install a transformer, thermostat and other controls
as required.
M3076A
Fig. 7. Always use new compression fitting.
2. Connect control circuit to the gas control terminals.
See Fig. 8.
Wiring
Follow the wiring instructions furnished by the appliance
manufacturer, if available, or use the general instructions
provided below. When these instructions differ from the
appliance manufacturer, follow the appliance
manufacturer instructions.
7
69-1225—4
VR8104, VR8204 AND VR8304 INTERMITTENT PILOT COMBINATION GAS CONTROLS
Turn On Main Burner
S8600
Follow appliance manufacturer instructions or turn up
VENT
DAMPER
PLUG
thermostat to call for heat.
5
GND
TH-W
(OPT)
24V
24V
GND
(BURNER)
(OPT)
MV MV/PV PV
SENSE SPARK
Perform Gas Leak Test
3
5
WARNING
PV
Fire or Explosion Hazard.
Can cause property damage, severe injury
or death.
2
PV/MV
MV
4
Perform Gas Leak Test every time work is done
on a gas system.
THERMOSTAT
GAS CONTROL
TERMINALS
IMPORTANT
LIMIT
Do not spray soap and water solution on the
gas control. Do not use an excessive amount of
soap and water solution to perform the gas leak
test. These can damage the control.
CONTROLLER
Q345, Q346,
Q348, Q362, Q381
PILOT BURNER/
IGNITER-SENSOR
GROUND
L1 L2
(HOT)
PILOT GAS
SUPPLY
1
Gas Leak Test
1. Paint pipe connections upstream of the gas control
with rich soap and water solution. Bubbles indicate
a gas leak.
2. If a leak is detected, tighten the pipe connections.
3. Light the main burner. Stand clear of the main
burner while lighting to prevent injury caused from
hidden leaks that could cause flashback in the
appliance vestibule.
1
POWER SUPPLY. PROVIDE DISCONNECT MEANS
AND OVERLOAD PROTECTION AS REQUIRED.
2
3
4
ALTERNATE LIMIT CONTROLLER LOCATION.
MAXIMUM WIRE LENGTH 3 ft [.9 m].
CONTROLS IN 24V CIRCUIT MUST NOT BE IN
GROUND LEG TO TRANSFORMER.
5
FOR MODULE WITH TH-W TERMINAL AND VENT DAMPER
PLUG, CONNECT THERMOSTAT TO TH-W. LEAVE
24V OPEN. DO NOT REMOVE VENT DAMPER PLUG.
4. With the main burner in operation, paint the pipe
joints (including adapters) and the control inlet and
outlet with rich soap and water solution.
M9056
5. If another leak is detected, tighten the adapter
screws, joints, and pipe connections.
6. Replace the part if a leak cannot be stopped.
Fig. 8. Typical wiring connections for 24 volt control
in intermittent ignition system with S8600.
Check and Adjust Pilot Flame
STARTUP AND CHECKOUT
The pilot flame should envelop 3/8 to 1/2 in. (10 to 13
mm) of the tip of the igniter-sensor. See Fig. 9. If the pilot
flame is small or lazy, the inlet gas pressure may be too
low, or the pilot orifice may be partially clogged. Check
and repair as necessary. If the pilot flame is hard and
noisy, the inlet gas pressure may be too high. The gas
control has a pilot adjustment mechanism to reduce the
pilot flow if necessary. If pilot adjustment is necessary,
proceed as follows:
WARNING
Fire or Explosion Hazard.
Can cause property damage, severe injury
or death.
1. Do not force the gas control knob on the
appliance. Use only your hand to turn the gas
control knob. Never use any tools.
2. If the knob does not operate by hand, the
control should be replaced by a qualified
service technician.
1. Remove pilot adjustment cover screw. See Fig. 6.
2. The pilot adjustment is shipped at the full pilot gas
flow rate. Turn the inner adjustment screw
clockwise
if the inlet pressure is too high.
Turn the inner adjustment screw clockwise
Gas Control Knob Settings
Gas control knob settings are as follows:
OFF: Prevents pilot and main gas flow through the
control.
ON: Permits gas to flow into the control body. Under
control of the thermostat and intermittent pilot module,
gas can flow to the pilot and main burners.
to decrease or counterclockwise
pilot flame.
to increase
3. Replace the cover screw after the adjustment to
prevent gas leakage.
PROPER FLAME
ADJUSTMENT
3/8 TO 1/2 INCH
(10 TO 13 mm)
NOTE: Controls are shipped with the gas control knob
in the ON position.
IGNITER-
SENSOR
Turn On System
Rotate the gas control knob counterclockwise
ON.
to
M3080A
Fig. 9. Proper flame adjustment.
69-1225—4
8
VR8104, VR8204 AND VR8304 INTERMITTENT PILOT COMBINATION GAS CONTROLS
NOTE: If the burner firing rate is above 150,000 Btuh
Check and Adjust Gas Input
and Burner Ignition
on VR8304 models (see Table 1 for VR8304
capacities), it may not be possible to deliver the
desired outlet pressure. This is an application
issue, not a control failure. Take whatever steps
are required to correct the situation.
IMPORTANT
1. Do not exceed input rating stamped on
appliance nameplate, or manufacturer’s
recommended burner orifice pressure for size
orifice(s) used. Make certain primary air supply
to main burner is properly adjusted for complete
combustion. Follow appliance manufacturer
instructions.
Step-Opening (P) Models
Step-opening models require that you check and adjust
the full-rate pressure first and then check the step
pressure. The step pressure is not field adjustable.
2. IF CHECKING GAS INPUT BY CLOCKING
GAS METER: Make certain there is no gas flow
through the meter other than to the appliance
being checked. Other appliances must remain
off with the pilots extinguished (or deduct their
consumption from the meter reading). Convert
flow rate to Btuh as described in form 70-2602,
Gas Controls Handbook, and compare to Btuh
input rating on appliance nameplate.
1. Carefully check the main burner lightoff. Make sure
that the main burner lights smoothly and that all
ports remain lit.
2. Check the full rate manifold pressure listed on the
appliance nameplate. Gas control full rate outlet
pressure should match this rating.
3. With main burner operating, check the gas control
flow rate using the meter clocking method or check
pressure using a manometer connected to the
outlet pressure tap on the gas control. See Fig. 6.
4. If necessary, adjust the pressure regulator to
match the appliance rating. See Tables 8A and 8B
for factory-set nominal outlet pressure and
adjustment range.
3. IF CHECKING GAS INPUT WITH
MANOMETER: Make sure the gas control knob
is in the OFF position before removing outlet
pressure tap plug to connect manometer
(pressure gauge). Also move the gas control
knob to the OFF position when removing the
gauge and replacing the plug. Before removing
inlet pressure tap plug, shut off gas supply at
the manual valve in the gas piping to the
appliance or, for LP, at the tank. Also shut off
gas supply before disconnecting manometer
and replacing plug. Repeat Gas Leak Test at
plug with main burner operating.
a. Remove the pressure regulator adjustment cap
screw.
Using a screwdriver, turn the inner adjustment screw
(Fig. 6) clockwise
counterclockwise
to the burner.
to increase or
to decrease the gas pressure
b. Always replace the cap screw and tighten
firmly to prevent gas leakage.
5. If the desired outlet pressure or flow rate cannot be
achieved by adjusting the gas control, check the
gas control inlet pressure using a manometer at
the inlet pressure tap of the control. If the inlet
pressure is in the nominal range (see Tables 8A
and 8B), replace the control. Otherwise, take the
necessary steps to provide proper gas pressure to
the control.
6. Carefully check the burner lightoff at step pressure.
Make sure the burner lights smoothly and without
flashback to the orifice. Make sure all ports remain
lit. Cycle the burner several times, allowing at least
60 seconds between cycles for the regulator to
resume the step function. Repeat after allowing the
burner to cool. Readjust the full rate outlet
pressure, if necessary, to improve lightoff
characteristics.
NOTE: Check the inlet pressure before adjusting the
pressure regulator.
Standard and Slow-Opening
(H, K and M) Models
1. Carefully check the main burner lightoff. Make sure
that the main burner lights smoothly and that all
ports remain lit.
2. Check the full rate manifold pressure listed on the
appliance nameplate. Gas control full rate outlet
pressure should match this rating.
3. With main burner operating, check the control flow
rate using the meter clocking method or check
pressure using a manometer connected to the
outlet pressure tap on the control. See Fig. 6.
4. If necessary, adjust the pressure regulator to
match the appliance rating. See Tables 8A and 8B
for factory-set nominal outlet pressure and
adjustment range.
Two-Stage (Q) Models
Two-stage models require that you check and adjust both
high and low pressure regulator settings. Two-stage
appliance operating sequences vary. Consult the
appliance manufacturer instructions for the specific
operating sequence and regulator adjustment procedure
for the appliance in which the control is installed.
a. Remove the pressure regulator adjustment cap
screw.
b. Using a screwdriver, turn the inner adjustment
screw (Fig. 6) clockwise
counterclockwise
to increase or
to decrease the gas
pressure to the burner.
c. Always replace the cap screw and tighten
firmly to prevent gas leakage.
1. Set appliance to operate on high.
2. Carefully check the main burner lightoff. Make sure
that the main burner lights smoothly and that all
ports remain lit.
3. Check the full rate (high) manifold pressure listed
on the appliance nameplate for high pressure. The
gas control full rate outlet pressure should match
this rating.
5. If the desired outlet pressure or flow rate cannot
be achieved by adjusting the gas control, check the
gas control inlet pressure using a manometer at
the inlet pressure tap of the gas control. If the inlet
pressure is in the nominal range (see Tables 8A
and 8B), replace the gas control. Otherwise, take
the necessary steps to provide proper gas
pressure to the control.
9
69-1225—4
VR8104, VR8204 AND VR8304 INTERMITTENT PILOT COMBINATION GAS CONTROLS
4. With main burner operating, check the gas control
flow rate using the meter clocking method or check
pressure using a manometer connected to the
outlet pressure tap on the gas control. See Fig. 6.
5. If necessary, adjust the high pressure regulator to
match the appliance rating. See Tables 8A and 8B
for factory-set nominal outlet pressure and
adjustment range.
flow rate cannot be achieved by adjusting the gas
control, check the control inlet pressure using a
manometer at the inlet pressure tap of the control.
If the inlet pressure is in the nominal range
(see Tables 8A and 8B), replace the gas control.
Otherwise, take the necessary steps to provide
proper gas pressure to the control.
a. Remove the pressure regulator adjustment cap
(Fig. 6).
b. Using a screwdriver, turn the inner adjustment
Check Safety Shutdown Performance
screw for HI pressure clockwise
increase or counterclockwise
to
to
WARNING
Can cause property damage, severe injury
or death.
Perform the safety shutdown test any time work
is done on a gas system.
decrease the gas pressure to the burner.
6. After high pressure has been checked, check low
pressure regulation. Two-stage appliance
operating sequences vary. Consult the appliance
manufacturers instructions for the specific
operating sequence and regulator adjustment
procedure for the appliance in which the control is
installed and for instructions on how to prevent the
control from moving to high stage while checking
the low pressure regulator setting.
7. Check the low rate manifold pressure listed on the
appliance nameplate. Gas control low rate outlet
pressure should match this rating.
8. With main burner operating, check the gas control
flow rate as before (using the meter clocking
method or check pressure using a manometer
connected to the outlet pressure tap on the
control).
Fire or Explosion Hazard.
NOTE: Read steps 1 through 7 before starting, and
compare to the safety shutdown or safety
lockout tests recommended for the intermittent
pilot (IP) ignition module. Where different, use
the procedure recommended for the module.
1. Turn off gas supply.
2. Set thermostat or controller above room
temperature to call for heat.
3. Watch for ignition spark or for glow at hot surface
igniter either immediately or following prepurge.
See IP module specifications.
9. If necessary, adjust the low pressure regulator to
match the appliance rating. See Tables 8A and 8B
for factory-set nominal outlet pressure and
adjustment range.
a. Remove the pressure regulator adjustment cap
(Fig. 6).
Using a screwdriver, turn the inner adjustment screw for
4. Time the length of the spark operation. See the IP
module specifications.
5. After the module locks out, open the manual gas
cock and make sure no gas is flowing to the pilot or
main burner. With modules that continue to spark
until the pilot lights or the system shuts down
manually, the pilot should light when the manual
gas control knob is opened.
LO pressure clockwise
counterclockwise
the burner.
to increase or
to decrease the gas pressure to
6. Set the thermostat below room temperature and
wait one minute.
7. Operate system through one complete cycle to
make sure all controls operate properly.
10. Once high and low pressure have been checked
and adjusted, replace pressure regulator
adjustment cap. If the desired outlet pressure or
Table 8A. Pressure Regulator Specification Pressures (in. wc).
Factory Set Nominal Outlet
Pressure
Setting Range
Full Rate
Type of Nominal Inlet
Model Type
Gas
Pressure Range
Step
Full Rate
3.5
Step
Standard,
Slow
NAT
5.0 to 7.0
—
—
3.0 to 5.0
LP
12.0 to 14.0
5.0 to 7.0
—
10.0
3.5
—
8.0 to 12.0
0.7 to 1.7
1.4 to 5.5
Step
NAT
LP
0.9
2.2
—
None
None
—
12.0 to 14.0
5.0 to 7.0
10.0
a
Two-Stage
NAT
1.7 Low
3.5 High
0.9 to 3.0 Low
3.0 to 5.0 High
LP
121.0 to 14.0
—
4.9 Low
—
3.5 to 5.5 Low
10.0 High
8.0 to 11.0 High
a
Low Fire setting range for VR8304Q 1/2 in. by 1/2 in. and 1/2 in. by 3.4 in. is 1.5 to 3.0 in. wc.
69-1225—4
10
VR8104, VR8204 AND VR8304 INTERMITTENT PILOT COMBINATION GAS CONTROLS
Table 8B. Pressure Regulator Specification Pressures (kPa).
Factory Set Nominal Outlet
Pressure
Setting Range
Type of
Gas
Nominal Inlet
Pressure Range
Model Type
Step
Full Rate
Step
Full Rate
Standard,
Slow
NAT
1.2 to 1.7
—
0.9
—
0.7 to 1.2
LP
2.9 to 3.9
1.2 to 1.7
2.9 to 3.9
1.2 to 1.7
—
2.5
0.9
2.5
—
2.0 to 3.0
Step
NAT
LP
0.2
0.5
—
None
None
—
0.17 to 0.48
1.4 to 1.37
a
Two-stage
NAT
0.48 Low
0.9 High
0.22 to 0.75 Low
0.75 to 1.2 High
LP
2.9 to 3.9
—
1.2 Low
2.5 High
—
0.9 to 1.4 Low
2.0 to 2.5 High
a
Low Fire setting range for VR8304Q 1/2 in. by 1/2 in. and 1/2 in. by 3.4 in. is 0.37 to 0.75 kPa.
•
Dusty, wet, or corrosive environments. Since these
environments can cause the gas control to deteriorate
more rapidly, the system should be checked more
often.
Non-Regulating On-Off (U) Models
Non-regulating VR8204U Valves are designed for
application in various parts of Europe where a separate,
distinct, pressure regulator is required. The VR8204U is
similar to the VR8204A in all other aspects and should be
installed accordingly.
The system should be replaced if:
•
•
•
It does not perform properly on checkout or
troubleshooting.
The gas control is likely to have operated for more
than 200,000 cycles.
MAINTENANCE
The control is wet or looks as if it has been wet.
WARNING
Can cause property damage, severe injury,
or death.
SERVICE
Fire or Explosion Hazard.
Do not disassemble the gas control; it contains
no replaceable components. Attempted
disassembly, repair, or cleaning can damage the
control, resulting in gas leakage.
WARNING
Can cause property damage, severe injury
or death.
Fire or Explosion Hazard.
Do not disassemble the control; it contains no
replaceable components. Attempted
disassembly, repair, or cleaning can damage
the gas control, resulting in gas leakage.
Regular preventive maintenance is important for
applications in the commercial cooking and agricultural
and industrial industries that place a heavy load on
system controls because:
•
In many such applications, particularly commercial
cooking, the equipment operates 100,000 to 200,000
cycles per year. Such heavy cycling can wear out the
gas control in one to two years.
Exposure to water, dirt, chemicals and heat can
damage the gas control and shut down the control
system.
CAUTION
Can burn out valve coil terminals.
Never apply a jumper across (or short) the valve
coil terminals, even temporarily.
Equipment Damage.
•
The maintenance program should include regular
checkout of the control as outlined in the Startup and
Checkout section, and the control system as described in
the appliance manufacturer literature.
After servicing, verify proper system operation.
If Main Burner Does Not Come
On With Call For Heat
Maintenance frequency must be determined individually
for each application. Some considerations are:
1. Confirm the gas control knob is in the ON position.
2. Adjust thermostat several degrees above room
temperature.
•
Cycling frequency. Appliances that may cycle 20,000
times annually should be checked monthly.
Intermittent use. Appliances that are used seasonally
should be checked before shutdown and again before
the next use.
3. Using ac voltmeter, check for 24V at gas control:
•
•
•
If pilot lights, measure across MV/PV and MV.
If pilot does not light, measure across MV/PV
and PV before safety lockout occurs.
•
Consequence of unexpected shutdown. Where the
cost of an unexpected shutdown would be high, the
system should be checked more often.
4. If voltage is incorrect or not present, check control
circuit for proper operation.
5. If 24V is present, replace gas control.
11
69-1225—4
VR8104, VR8204 AND VR 8304 INTERMITTENT PILOT COMBINATION GAS CONTROLS
STOP: Read the Warnings Above Before
INSTRUCTIONS TO THE
HOMEOWNER
Proceeding.
The pilot flame is lit automatically. If the appliance does
not turn on when the thermostat is set several degrees
above room temperature, follow these instructions:
1. Set the thermostat to its lowest setting to reset the
safety control.
WARNING
Fire or Explosion Hazard.
2. Disconnect all electric power to the appliance.
3. Remove the burner access panel if provided on
your appliance.
Can cause property damage, severe injury,
or death.
Follow these warnings exactly:
4. Turn the gas control knob clockwise
to the
1. Pilot flame is lit automatically. Do not light the
pilot flame manually.
OFF position.
5. Wait five minutes to clear out any unburned gas.
Then if you smell gas, STOP! Follow Step 2 in the
Warning above. If you do not smell gas, continue
with the next step.
2. Before lighting the pilot burner flame, smell
around the appliance for gas. Be sure to smell
next to the floor because LP gas is heavier
than air. If you smell gas:
6. Turn the gas control knob counterclockwise
to the ON position.
7. Replace the burner access panel.
8. Reconnect all electric power to the appliance.
9. Set the thermostat to the desired setting.
10. If the appliance does not turn on, turn the gas
control knob to the OFF position and contact a
qualified service technician for assistance.
•
Turn off the gas supply at the appliance
service valve. On LP gas systems, turn off
the gas supply at the gas tank.
Do not light any appliances in the house.
Do not touch electrical switches or use the
phone.
Leave the building and use a neighbor’s
phone to call your gas supplier.
If you cannot reach your gas supplier, call
the fire department.
•
•
•
•
Turning Off the Appliance
Vacation Shutdown
Set the thermostat to the desired room temperature while
you are away.
3. Replace the gas control in the event of any
physical damage, tampering, bent terminals,
missing or broken parts, stripped threads, or
evidence of exposure to heat.
IMPORTANT
Follow the operating instructions provided by
the heating appliance manufacturer. The
information below describes a typical control
application, but the specific controls used and
the procedures outlined in your appliance
manufacturer instructions can differ, requiring
special instructions.
Complete Shutdown
Turn off power to the appliance. Turn off the gas supply
to the appliance. Turn the gas control knob to OFF. The
appliance will completely shut off. Follow the procedure
in the Instructions to the Homeowner section above to
resume normal operation.
Home and Building Control
Home and Building Control
Honeywell Inc.
1985 Douglas Drive North
Golden Valley, Minnesota 55422
Honeywell Limited-Honeywell Limitée
35 Dynamic Drive
Scarborough, Ontario
M1V 4Z9
Printed in U.S.A. on recycled
paper containing at least 10%
post-consumer paper fibers.
69-1225—4 G.R. Rev. 9-00
|