Greenheck Fan Smoke Alarm SMD 203 User Manual

Model SMD-203  
Smoke Dampers  
Steel 3V Blades  
UL 555S Leakage Class III  
Application  
Model SMD-203 is a leakage rated smoke damper with 3V style  
blades. The SMD-203 has been qualified to 2,000 fpm (10.2 m/s) and  
4 in. wg (1 kPa) for operational closure in emergency smoke control  
situations. Model SMD-203 may be installed vertically (with blades  
running horizontally) or horizontally and is rated for airflow and leakage  
in either direction.  
Model SMD-203 meets the requirements for smoke  
dampers established by:  
National Fire Protection Association  
NFPA Standards 92A, 92B, 101 & 105  
IBC International Building Codes  
New York City (MEA listing #260-91-M)  
CSFM California State Fire Marshal  
Leakage (Smoke) Damper Listing (#3230-0981:104)  
Ratings  
Leakage:  
Pressure:  
UL 555S leakage class III  
4 in. wg (1 kPa) - differential pressure  
Consult factory for sizes available in  
6 in. wg (1.5 kPa)  
Velocity:  
Operational rated to 2000 fpm  
(10.2 m/s). Rating is for airflow in  
either direction through damper.  
350°F (177°C) depending on the  
actuator  
“UL CLASSIFIED (see complete marking on  
product)”  
“UL CLASSIFIED to Canadian safety standards  
(see complete marking on product)”  
Standard 555S (Listing #R13317)  
Temperature:  
Standard Construction  
Greenheck Fan Corporation certifies that the  
model SMD-203 shown herein is licensed to bear  
the AMCA Seal. The ratings shown are based on  
tests and procedures performed in accordance  
with AMCA Publication 511 and comply with  
the requirements of the AMCA Certified Ratings  
Programs. The AMCA Certified Ratings Seal  
applies to air performance ratings only.  
Frame:  
5 in. x 1 in. (127mm x 25mm)  
galvanized steel hat channel with  
reinforced corners. A low profile  
head and sill are used on sizes less  
than 17 in. 432mm) high to maximize  
free area and performance.  
R
Blades:  
16 ga. (1.5mm) galvanized steel,  
reinforced with 3 longitudinal  
structurally designed vee’s.  
Flexible stainless steel jamb seals.  
Concealed in jamb.  
Seals:  
Linkage:  
Axles:  
12 in. (13mm) dia. plated steel  
Bearings:  
Bronze sleeve type  
W*  
Size Limitations  
Minimum Size:  
8 in. W x 6 in. H  
(203mm W x 152mm H)  
Maximum Size:  
Single Section -  
32 in. W x 50 in. H  
(813mm W x 1270mm H)  
36 in. W x 48 in. H  
(914mm W x 1219mm H)  
144 in. W x 100 in. H  
(3658mm W x 2540mm H)  
288 in. W x 50 in. H  
LH  
Multiple Section -  
(7315 mm W x 1270mm H)  
Optional Features  
• Galvanized steel sleeves.  
• Stainless steel bearings  
H*  
• OCI (Open closed indication switches)  
RH  
• Electric or pneumatic actuators to accomplish smoke  
management and system functions.  
Transitions (R, C, O)  
• POC retaining angles  
• Momentary Switch  
• Smoke detectors  
* W&H dimensions furnished approximately 1/4 in. (6mm) undersize.  
Add sleeve thickness for overall sleeved damper dimension)  
Right hand drive is shown. Left hand drive is available upon request.  
• Sealed transition and sleeves  
• Fail open  
 
AMCA 5.2 Pressure Drop  
SMD-203  
5D  
Figure 5.2  
12 in. x 12 in. (305mm x 305mm)  
Pressure Drop  
24 in. x 24 in. (610mm x 610mm)  
Pressure Drop  
36 in. x 36 in. (914mm x 914mm)  
Pressure Drop  
12 in. x 48 in. (305mm x 1219mm)  
Pressure Drop  
48 in. x 12 in. (1219mm x 305mm)  
Pressure Drop  
Velocity (fpm)  
(in. wg)  
Velocity (fpm)  
Velocity (fpm)  
Velocity (fpm)  
Velocity (fpm)  
(in. wg)  
(in. wg)  
(in. wg)  
(in. wg)  
500  
1000  
1500  
2000  
2500  
3000  
3500  
4000  
0.04  
0.14  
0.31  
0.55  
0.86  
1.24  
1.69  
2.20  
500  
1000  
1500  
2000  
2500  
3000  
3500  
4000  
0.02  
0.07  
0.16  
0.29  
0.45  
0.65  
0.89  
1.16  
500  
0.01  
0.04  
0.09  
0.16  
0.25  
0.36  
0.49  
0.64  
500  
0.01  
0.06  
0.13  
0.23  
0.36  
0.52  
0.70  
0.92  
500  
0.03  
0.10  
0.23  
0.41  
0.63  
0.91  
1.24  
1.62  
1000  
1500  
2000  
2500  
3000  
3500  
4000  
1000  
1500  
2000  
2500  
3000  
3500  
4000  
1000  
1500  
2000  
2500  
3000  
3500  
4000  
Greenheck Fan Corporation certifies that the  
model SMD-203 shown herein is licensed to bear  
the AMCA Seal. The ratings shown are based on  
tests and procedures performed in accordance  
with AMCA Publication 511 and comply with  
the requirements of the AMCA Certified Ratings  
Programs. The AMCA Certified Ratings Seal  
applies to air performance ratings only.  
R
 
AMCA 5.3 Pressure Drop  
SMD-203  
5D  
6D  
Figure 5.3  
12 in. x 12 in. (305mm x 305mm)  
Pressure Drop  
24 in. x 24 in. (610mm x 610mm)  
Pressure Drop  
36 in. x 36 in. (914mm x 914mm)  
Pressure Drop  
12 in. x 48 in. (305mm x 1219mm)  
Pressure Drop  
48 in. x 12 in. (1219mm x 305mm)  
Pressure Drop  
Velocity (fpm)  
(in. wg)  
Velocity (fpm)  
(in. wg)  
Velocity (fpm)  
(in. wg)  
Velocity (fpm)  
(in. wg)  
Velocity (fpm)  
(in. wg)  
500  
1000  
1500  
2000  
2500  
3000  
3500  
4000  
0.02  
0.09  
0.20  
0.36  
0.56  
0.81  
1.10  
1.44  
500  
1000  
1500  
2000  
2500  
3000  
3500  
4000  
0.01  
0.04  
0.09  
0.16  
0.25  
0.35  
0.48  
0.63  
500  
1000  
1500  
2000  
2500  
3000  
3500  
4000  
0.01  
0.03  
0.06  
0.11  
0.17  
0.24  
0.33  
0.42  
500  
1000  
1500  
2000  
2500  
3000  
3500  
4000  
0.01  
0.04  
0.10  
0.17  
0.27  
0.39  
0.53  
0.70  
500  
1000  
1500  
2000  
2500  
3000  
3500  
4000  
0.02  
0.07  
0.16  
0.29  
0.45  
0.64  
0.88  
1.14  
Greenheck Fan Corporation certifies that the  
model SMD-203 shown herein is licensed to bear  
the AMCA Seal. The ratings shown are based on  
tests and procedures performed in accordance  
with AMCA Publication 511 and comply with  
the requirements of the AMCA Certified Ratings  
Programs. The AMCA Certified Ratings Seal  
applies to air performance ratings only.  
R
 
AMCA 5.5 Pressure Drop  
SMD-203  
12 in. x 12 in. (305mm x 305mm)  
24 in. x 24 in. (610mm x 610mm)  
36 in. x 36 in. (914mm x 914mm)  
12 in. x 48 in. (305mm x 1219mm)  
48 in. x 12 in. (1219mm x 305mm)  
Pressure Drop  
Pressure Drop  
Pressure Drop  
Pressure Drop  
Pressure Drop  
Velocity (fpm)  
(in. wg)  
Velocity (fpm)  
(in. wg)  
Velocity (fpm)  
(in. wg)  
Velocity (fpm)  
(in. wg)  
Velocity (fpm)  
(in. wg)  
500  
1000  
1500  
2000  
2500  
3000  
3500  
4000  
0.04  
0.17  
0.38  
0.67  
1.04  
1.50  
2.05  
2.67  
500  
1000  
1500  
2000  
2500  
3000  
3500  
4000  
0.06  
0.22  
0.50  
0.89  
1.39  
2.00  
2.72  
3.55  
500  
1000  
1500  
2000  
2500  
3000  
3500  
4000  
0.03  
0.14  
0.31  
0.54  
0.85  
1.22  
1.66  
2.17  
500  
1000  
1500  
2000  
2500  
3000  
3500  
4000  
0.03  
0.12  
0.26  
0.46  
0.73  
1.05  
1.42  
1.86  
500  
1000  
1500  
2000  
2500  
3000  
3500  
4000  
0.03  
0.13  
0.30  
0.53  
0.83  
1.19  
1.62  
2.11  
Greenheck Fan Corporation certifies that the  
model SMD-203 shown herein is licensed to bear  
the AMCA Seal. The ratings shown are based on  
tests and procedures performed in accordance  
with AMCA Publication 511 and comply with  
the requirements of the AMCA Certified Ratings  
Programs. The AMCA Certified Ratings Seal  
applies to air performance ratings only.  
R
 
Application Data  
Damper Sleeve Dimensional Data  
The drawings below and corresponding table show the position of the SMD-203 damper when mounted in a factory sleeve.  
The standard mounting locations provide enough space for the mounting of actuators, controls and allow space for installa-  
tion of retaining angles and duct connections.  
The standard location of a damper mounted in a factory sleeve ("A" dimension) is shown below. The damper can be posi-  
tioned at other locations within a range of 6 in. (152mm) to 12 in. (305mm) for the "A" dimension.  
11/2 in.  
max.  
"A" Dimension  
in. (mm)  
Standard  
7 3/16 in. (183)  
12 (305)  
Maximum  
12 (305)  
12 (305)  
All Dampers*  
33/4  
in.  
When Height is  
11 in. (279) or less  
with OCI  
6 in.  
RH  
Varies  
*With the exception of dampers 10 in. high (254mm) or less.  
53/8 in.  
NOTE: Entire damper frame is not required to be installed  
within the wall.  
LH  
Right hand drive is shown  
Left hand drive available upon request  
A
5 in.  
Sleeve Length  
Actuators and Accessories Space  
T*  
S
Envelopes  
Externally mounted actuators always require space out-  
side of the damper sleeve. The “S” dimension illustrates  
the clearance required for various available actuators.  
On dampers less than 18 in. (457mm) high, actuators may  
also require clearances above and/or below the sleeve.  
“B” and “T” dimensions are worst case clearance require-  
ments for some dampers less than 18 in. (457mm) high.  
All damper sizes under 18 in. (457mm) high do not require  
these worst case clearances. If space availability above  
or below the damper sleeve is limited, each damper size  
should be individually evaluated.  
B*  
Actuator  
Type/Model  
B*  
T*  
S
With OCI  
With OCI  
120 Volt AC  
5 1/4 in. (133mm) 3/4 in. (19mm)  
ML4XXX Series Honeywell  
MS4XXX Series Honeywell  
MS4120 Series Honeywell  
6 in. (152mm)  
6 in. (152mm)  
6 in. (152mm)  
6 in. (152mm)  
6 in. (152mm)  
3/8 in. (10mm)  
3/8 in. (10mm)  
24 Volt AC  
5 1/4 in. (133mm) 3/4 in. (19mm)  
ML8XXX Series Honeywell  
MS8XXX Series Honeywell  
MS8120 Series Honeywell  
6 in. (152mm)  
6 in. (152mm)  
6 in. (152mm)  
6 in. (152mm)  
6 in. (152mm)  
3/8 in. (10mm)  
3/8 in. (10mm)  
Pneumatic (psi)  
331-4551 Siemens  
331-2976 Siemens  
MK2-7121 Invensys  
1 in. (25mm)  
6 1/4 in. (159mm)  
6 1/2 in. (165mm)  
2 3/8 in. (60mm)  
3 3/4 in. (95mm)  
12 1/8 in. (308mm) 9 1/4 in. (235mm)  
16 1/2 in. (419mm) 10 in. (254mm)  
* For dampers 18 in. (457mm) or more in height these dimensions are 0 in. .  
 
Damper Sizing Information  
Dampers larger than maximum single section size are supplied as a factory assembly of two or more sections of equal size.  
The following figures show maximum damper section size and assembly configurations for multi-section dampers.  
Double Section  
Single Section  
50 in.  
(1270mm)  
(
50 in.  
(1270mm)  
32 in. (813mm)  
64 in. (1626mm)  
32 in. (813mm)  
When a fire/smoke damper is being used in conjunction with round or oval ductwork, the  
SMD-203 can be supplied in a factory sleeve with round or oval transitions on both ends  
of the sleeve. Dampers should be ordered to the duct dimensions. Drawings below show  
overall damper size.  
Transitioned Damper  
Dimensions  
D*+  
2 in. (51mm) +T  
s
W*+ 2 in. (51mm)+T  
s
W*+ 2 in. (51mm)+T  
s
D*+ 2 in. (51mm)+T  
s
H*+ 2 in. (51mm)+T  
H*+ 2 in. (51mm)+T  
s
s
H*  
H*  
21/8in.  
21/8in.  
(54mm)  
21/8in.  
(54mm)  
(54mm)  
*
W
W*  
D*  
16 in. (406mm)  
Min.  
16 in. (406mm)  
Min.  
16 in. (406mm)  
Min.  
TYPE R  
TYPE O  
TYPE C  
These dimensions are furnished approximately 1/4 in. (6mm) undersize, except round and oval dimensions which are approximately 1/8 in. (3mm) undersize.  
*
T
= (2)(Sleeve Thickness)  
s
Specifications  
Smoke Dampers meeting the following specifications shall be fur-  
nished and installed where shown on plans and/or as described in  
schedules. Dampers shall meet the requirements of NFPA 92A, 92B,  
101 & 105 and further shall be tested, rated and labeled in accor-  
dance with the latest edition of UL Standards 555S. Dampers shall  
have a low leakage design qualified to UL555S Leakage Class III.  
Jamb seals shall be stainless steel compression type. Blades shall be  
completely symmetrical relative to their axle pivot point, presenting  
identical resistance to airflow in either direction or pressure on either  
side of the damper.  
The Damper Manufacturer's submittal data shall certify all air perfor-  
mance pressure drop data is licensed in accordance with the AMCA  
Certified Ratings Program for Test Figures 5.2, 5.3, and 5.5. Damper  
air performance data shall be developed in accordance with the lat-  
est edition of AMCA Standard 500-D. Dampers shall be labeled with  
the AMCA Air Performance Seal.  
Each damper/actuator combination shall have a UL555S elevated  
temperature rating of 250°F (121°C) minimum and shall be opera-  
tional at maximum design air flow at its installed location. Each  
damper shall be supplied with an appropriate actuator installed by  
the damper manufacturer at the time of damper fabrication. Damper  
actuator shall be (specifier select one of the following) electric type  
for 120 (24 or 230) Volt operation or pneumatic type for 25 psi mini-  
mum (30 psi maximum) operation.  
Damper must be rated for mounting vertically (with blades running  
horizontal) or horizontally and be UL 555S rated for leakage and  
airflow in either direction through the damper.  
The basis of design is Greenheck Model SMD-203.  
Damper blades shall be 16 ga. (1.5mm) galvanized steel 3V type with  
three longitudinal grooves for reinforcement. Damper frame shall  
be galvanized steel formed into a structural hat channel shape with  
reinforced corners. Bearings shall be sintered bronze sleeve type  
rotating in extruded holes in the damper frame. Blade edge seals  
shall be silicone rubber designed to inflate and provide a tighter seal  
against leakage as pressure on either side of the damper increases.  
Copyright ©2006 Greenheck Fan Corporation  
SMD-203 Rev 4 June 2006  
 

Harbor Freight Tools Portable Generator 69672 User Manual
Honeywell DVR HD DVR 1004 User Manual
Hoshizaki Ice Maker KM 800MAE User Manual
HP Hewlett Packard Computer Accessories 230859 004 User Manual
HP Hewlett Packard Network Hardware 4400 User Manual
Hubbell Switch 2040 1 User Manual
Hubbell Switch LMTS User Manual
Husqvarna Trimmer 333RJ 335RJX Series User Manual
Ikelite Digital Camera Coolpix P1 User Manual
Image Hot Tub IMSB63910 User Manual