GE Monogram GPS Receiver ZV881WSS User Manual

GE Monogram®  
Installation  
Instructions  
Professional  
Vent Hoods  
48" Models  
ZV881WSS, ZV891YSS  
ZV880WSS, ZV890YSS  
36" Models  
ZV671WSS, ZV681YSS  
ZV670WSS, ZV680YSS  
30" Models  
ZV370YSS,  
ZV371YSS  
 
Design Information  
Professional Vent Hoods  
These hoods can be installed into a soffit, or  
when there is no soffit, they can be installed  
directly onto a wall.  
48" Wide Models:  
ZV881WSS, ZV880WSS – with tapered sides  
ZV891YSS, ZV890YSS – with straight sides  
Models  
Available  
36" Wide Models:  
ZV671WSS, ZV670WSS – with tapered sides  
ZV681YSS, ZV680YSS – with straight sides  
48" and 36" wide models are available with  
different appearances. Model numbers with  
“YSS” have straight sides. Model numbers  
ending with “WSS” have sides which taper  
inwards from the bottom to the top.  
30" Wide Models:  
ZV371YSS, ZV370YSS – with straight sides  
Before you begin:  
should determine the installation height of  
the hood and order the correct size duct  
cover.  
Duct  
Cover  
Accessories  
Decorative duct covers are available in 6" or  
12" heights. The duct covers conceal the  
ductwork running from the top of the hood to  
the ceiling or soffit. Before you begin, you  
Be sure to order the duct cover which corre-  
sponds to your model.  
Optional Accessory Duct Covers  
6" Duct Cover  
Style  
Hood Model  
12" Duct Cover  
A-Oval  
A-Oval  
ZV881WSS, ZV880WSS ZX6DC48WSS  
ZV671WSS, ZV670WSS ZX6DC36WSS  
6"Hx27-3/8"Wx10-1/4"D ZX12DC48WSS 12"Hx27-3/8"Wx10-1/4"D  
6"Hx22-1/2"Wx9-3/16"D ZX12DC36WSS 12"Hx22-1/2"Wx9-3/16"D  
B-Square  
B-Square  
B-Square  
ZV891YSS, ZV890YSS  
ZV681YSS, ZV680YSS  
ZV371YSS, ZV370YSS  
ZX6DC49YSS  
ZX6DC38YSS  
ZX6DC30YSS  
6"Hx47-7/8"Wx12"D  
6"Hx35-7/8"Wx12"D  
6"Hx29-7/8"Wx12"D  
ZX12DC49YSS  
ZX12DC38YSS  
ZX12DC30YSS  
12"Hx47-7/8"Wx12"D  
12"Hx35-7/8"Wx12"D  
12"Hx29-7/8"Wx12"D  
Optional 6" or 12"  
Duct Cover  
Style B-Square Shape  
Style A-Oval Shape  
Optional 6" or 12"  
Duct Cover  
Duct covers for models:  
Duct covers for models:  
ZV881WSS, ZV880WSS, ZV671WSS and  
ZV670WSS.  
ZV891YSS, ZV890YSS, ZV681YSS, ZV680YSS,  
ZV371YSS and ZV370YSS.  
Transition duct pieces are available for 48"  
wide models. These pieces fit over the outlet  
on top of the hood. These transition pieces fit  
into a soffit or when there is no soffit, a 12"  
duct cover should be used.  
Accessories  
(For 48" Wide  
Models Only)  
12"  
6-5/8"  
C
to  
L
C
L
8-1/4"  
4-3/4"  
19-1/4"  
10"  
8-3/4"  
ZX48BY, transition to 10" round for horizontal  
exhaust.  
18-1/2"  
4-1/2"  
ZX48AY, transition to 10" round vertical  
exhaust.  
3
 
Design Information  
Professional Vent Hoods  
These vent hoods must be installed 30" Min.  
and 36" Max. above the cooking surface.  
Installation will be easier if the vent hood  
is installed before the range or cooktop  
installation.  
The rating plate is located behind filter  
cutouts. To verify your model number, remove  
filters.  
Product  
Dimensions  
& Clearances  
12"  
35"  
12"  
47-7/8"  
18"  
18"  
25"  
12"  
47-7/8"  
ZV881WSS, ZV880WSS  
25"  
47-7/8"  
ZV891YSS, ZV890YSS  
12"  
35-7/8"  
23"  
18"  
18"  
35-7/8"  
25"  
35-7/8"  
25"  
ZV681YSS, ZV680YSS  
ZV671WSS, ZV670WSS  
12"  
29-7/8"  
18"  
29-7/8"  
25"  
ZV371YSS, ZV370YSS  
SOFFIT INSTALLATION  
SOFFIT  
WALL MOUNT INSTALLATION  
Ceiling  
30" MIN.  
36" MAX."  
30" MIN.  
36" MAX."  
4
 
Design Information  
Professional Vent Hoods  
Installation Framing for adequate support  
These vent hoods are heavy. Adequate struc-  
tural support must be provided. Hoods must be  
secured to vertical studs or to studs in the  
soffit.  
Additional studs may be required for a soffit  
or wall mount installation. See Step 3, pages 8  
and 9.  
We recommend that the vent hood and/or  
duct cover be on site before final framing and  
wall finishing. This will also help to accurately  
locate the ductwork and electrical service.  
Installation will be much easier if the vent  
hood is installed before the range or cooktop  
below.  
Ductwork planning  
Advance  
Planning  
Determine the exact location of the vent hood.  
Plan the route for venting exhaust to the  
outdoors.  
Use the shortest and straightest duct route  
possible. For satisfactory performance, duct  
run should not exceed 100 feet equivalent  
length for any duct configurations.  
Refer to “Duct Fittings” chart to compute the  
maximum permissable length for duct runs to  
the outdoors. See page 6.  
Use metal ductwork. For 48" models,  
3-1/4" x 24" or 10" round. For 30" and 36"  
models, 7" to 10' round or 3-1/4" x 12" to  
3-1/4" x 24".  
Install a wall cap with damper or roof cap at  
the exterior opening.  
Decorative Duct Covers  
Decorative duct covers are available for all  
models. The duct covers conceal the ductwork  
running from the top of the hood to the  
ceiling or soffit. Duct covers are available in  
6" or 12" heights.  
You should:  
Determine the installation height from the  
cooking surface.  
Determine the size of the wall or roof cap for  
your model and installation.  
Order the caps and any transitions needed in  
advance. See “Duct and Duct Fittings” listed in  
your local yellow pages. Be sure to include  
equivalent lengths of caps and transitions when  
calculating the total duct run. See “Duct  
Fittings”, page 6.  
– 36" max., 30" min.  
Measure 18" hood height.  
48" Wide Model Duct Transitions  
Select 6" or 12" duct cover to meet ceiling or  
soffit height.  
Transition duct pieces are available for 48"  
wide models. See illustrations of ZX48BY and  
ZX48AY transition pieces on page 3.  
Connect the wiring to the house wiring in  
accordance with local codes.  
WARNING  
Electrical  
Supply  
Warning, for  
Personal Safety:  
Remove house fuse or open  
circuit breaker before beginning  
installation.  
House wiring location  
The junction box is located on the top of the  
hood. See illustrations, page 10 to determine  
exact placement.  
Route house wiring through the ceiling, soffit  
or back wall as close to the installation location  
as possible.  
Do not use an extension cord or adapter  
plug with this appliance. Follow National  
electrical codes or prevailing local codes  
and ordinances.  
Grounding Instruction  
Electrical supply  
This hood must be connected to a ground metal,  
permanent wiring system, or an equipment-  
grounding terminal or lead on the hood.  
This vent hood must be supplied with 120V,  
60Hz., and connected to an individual,  
properly grounded branch circuit, protected  
by a 15 or 20 ampere circuit breaker or time  
delay fuse.  
•Wiring must be 2 wire with ground.  
If the electrical supply does not meet the  
above requirements, call a licensed electri-  
cian before proceeding.  
W
ARNING  
Warning: The improper connec-  
tion of the equipment-grounding  
conductor can result in a risk of  
electric shock. Check with a  
qualified electrician or service  
representative if you are in doubt whether  
the appliance is properly grounded.  
5
 
Installation Preparation  
Professional Vent Hoods  
Use this chart to  
compute maximum  
permissable lengths  
for duct runs to  
outdoors.  
Total  
Duct  
fittings  
Equivalent Quantity Equivalent  
Duct Piece Dimensions  
Length*  
Used  
Length  
Round,  
straight  
1 ft.  
(per foot  
length)  
Note: Do not exceed maximum  
permissable equivalent lengths!  
3-1⁄4" x 12" or  
3-1/4" x 24"  
straight  
1 ft.  
(per foot  
length)  
Maximum duct length:  
100 foot for range hoods.  
90° elbow  
45° elbow  
15 ft.  
9 ft.  
Flexible ducting:  
If flexible metal  
ducting is used, all  
the equivalent feet  
values in the table  
should be doubled.  
The flexible metal  
duct should be  
straight and smooth  
and extended as  
much as possible.  
3-1⁄4" x 12" or  
3-1/4" x 24"  
90° elbow  
15 ft.  
9 ft.  
3-1⁄4" x 12" or  
3-1/4" x 24"  
45° elbow  
3-1⁄4" x 12" or  
3-1/4" x 24"  
90° flat elbow  
20 ft.  
1 ft.  
Do NOT use flexible  
plastic ducting.  
7" round to  
3-1⁄4" x 12" or 10" round  
to 3-1/4" x 24" transition  
Note: Any home ventilation  
system, such as a ventilation  
hood, may interrupt the proper  
flow of combustion air and  
exhaust required by fireplaces,  
gas furnaces, gas water heaters  
and other naturally vented  
3-1⁄4" x 12" to 7" round  
or 3-1/4" x 24" to 10"  
round transition  
5 ft.  
7" round to  
3-1/4" x 12" or 10" round  
to 3-1/4" x 24"  
systems. To minimize the chance  
of interruption of such naturally  
vented systems, follow the heating  
equipment manufacturer’s  
guidelines and safety standards  
such as those published by NFPA  
and ASHRAE.  
transition 90° elbow  
5 ft.  
3-1⁄4" x 12" to 7" round  
or 3-1/4" x 24" to 10"  
round transition 90° elbow 15 ft.  
Round  
wall cap  
with damper  
30 ft.  
30 ft.  
26 ft.  
3-1⁄4" x 12" or  
3-1/4" x 24" wall cap  
with damper  
48" Hoods Must Use  
10" Round Duct  
or 3-1/4" x 24"  
Round  
roof cap  
Note: Outlet on top of 48" hood  
is 4-1/2" x 18-1/2".  
Round  
roof vent  
24 ft.  
30" and 36" Hoods  
May Use 7" to 10"  
Round, or 3-1/4" x 12"  
to 3-1/4" x 24"  
Total Duct Run  
* Actual length of straight duct plus duct fitting  
equivalent. Equivalent length of duct pieces are based  
on actual tests conducted by GE Evaluation Engineer-  
ing and reflect requirements for good venting  
performance with any ventilation hood.  
6
 
Installation  
Professional Vent Hoods  
Wall Mount Installation:  
Six, 5/16" lag screws, 2" long with washers,  
all models (provided).  
Tape measure  
Spirit level  
Wire Cutter  
Wire stripper  
Electric drill  
and appropriate bits  
Torx screwdriver  
Tools &  
Materials  
Required  
(not supplied)  
Soffit Installation:  
Six, 5/16" lag screws, 2" long with washers,  
all models (provided).  
Optional for wall mount installations: (See page 9)  
48" x 18" plywood for 48" model,  
36" x 18" plywood for 36" model,  
120V 60Hz 15 or 20 Amp, 2 wire with  
ground. Properly grounded branch circuit.  
Metal ductwork, 3-1/4" x 24" or 10" round  
for 48" wide model. 7" to 10" round or  
3-1/4" x 12" to 3-1/4" x 24" for 30" and 36"  
models.  
30" x 18" plywood for 30" model.  
Cut and remove the plastic banding on the  
crate and one holding the parts box.  
Remove the top of the crate by backing out  
screws.  
Break-away crate sides.  
Remove the parts box and set aside.  
Remove plastic wrapping and padding.  
male/female plug. Set aside.  
Remove 4 screws along inside front, 5 screws  
along the inside back and 3 screws on each  
side (30 and 36" models have fewer screws).  
Remove the inner liner, disconnect the  
male/female plugs, one to the heat lamp  
and one to the blower. Set aside.  
Step  
1
Remove the  
Packaging  
and  
For easier handling during installation, the hood  
can be separated into 3 assemblies. The hood is  
laying on its back, bolted to the skid in 4 loca-  
tions.  
CAUTION: Control panel is held in place  
with set screws and may fall out when inner  
liner is removed.  
Disassemble  
Remove the assemblies shown for easier access  
to the hold-down bolts.  
Remove the 4 bolts holding the hood to the  
skid.  
Remove 8 screws located on the inside front.  
(30" models have fewer screws.) Lift off the  
halogen light assembly and disconnect the  
Inner Liner  
Disconnect  
Through Junction Box on  
Rough-In-Kit, Connect to  
House Wiring  
To Blower Motor  
Hood Inner Liner  
Light  
Assembly  
Remove Screws That  
Hold Inner Liner in Place.  
7
 
Installation  
Professional Vent Hoods  
Locate the hardware accessory box packed  
with range hood and check contents.  
Step  
2
Check  
Installation  
Hardware  
Filter(s)  
Grease  
Tray(s)  
Heat Lamp(s)  
(on some models)  
Halogen  
Bulbs  
We recommend that the vent hood  
and/or duct cover be on site before  
final framing and wall finishing to  
more accurately locate the ductwork  
and electrical service.  
Step  
3
Construct  
Soffit  
NOTE: If the top of the installation  
location does not meet the soffit, use  
a 6" or 12" duct cover accessory to  
conceal the duct run.  
Framing  
Shims  
INSTALLATION  
UNDER A SOFFIT  
(SKIP THIS STEP  
IF SOFFIT IS NOT  
USED.)  
The soffit should be constructed  
with 2x4’s.  
• Determine the installation location.  
Finished Drywall  
Cut 2 wood shims, 2" x 10" X  
(drywall thickness). Secure to the  
bottom of the horizontal studs,  
flush with the front, as illustrated.  
NOTE: If drywall is present, cutaway  
enough to expose studs.  
B
“A” “A”  
Hood Width  
“A”  
“B”  
Opening Depth  
for Ductwork  
Centerline to  
Stud Inner Edge  
48" Models  
36" Models  
30" Models  
11-1/4"  
8-3/4"  
10-11/16"  
10" Min.  
7" Min.  
7" Min.  
Refer to step 4 for mounting screw  
locations.  
Mark the centerline of the installation.  
Add additional 2 x 4 studs at the loca-  
tions illustrated.  
For 48" models, allow 10" deep mini-  
mum opening below the soffit to accom-  
modate ductwork. For 30" and 36"  
models, allow 7" deep minimum opening.  
8
 
Installation  
Professional Vent Hoods  
7" Min. (30" and 36" Models)  
10" Min. (48" Models)  
NOTE: A decorative duct cover is available  
for wall mount installations. The duct cover  
conceals the duct run from the top of the  
hood to the ceiling. Choose the 6" or 12"  
cover based upon installation height of the  
vent hood.  
Step  
3
WALL MOUNT  
INSTALLATION  
(SKIP THESE  
STEPS IF SOFFIT  
IS USED.)  
A
Construct  
Wall Mount  
Framing  
Hood  
Width  
We recommend that the vent hood and  
decorative duct cover be on site before final  
framing and wall finishing in order to accu-  
rately locate the ductwork and electrical  
service.  
• Determine the location for installation.  
• Mark the centerline of the installation.  
Plywood Sheet  
(Wall Hole Cut  
Out x Drywall  
Thickness)  
No Additional  
Wall Studs needed  
Rear View of Vent Hood (48" Model Shown)  
Ceiling Drywall  
6" or 12"  
Duct  
Cover  
Cut a sheet of plywood, 48" wide (or 36" wide)  
and 18" high. If drywall is installed, cut away  
enough to expose 2 vertical studs, 1 on each  
side of the cutout. Secure the plywood to the  
studs.  
6-1/2"  
6-1/2"  
Hood Centerline  
2-1/2"  
18"  
C
L
C
C
OR  
If drywall is installed, cut away enough to  
expose 2 vertical studs.  
Install additional aligning wall studs as  
illustrated.  
“C” – Hood Centerline  
13" for 48" wide models  
9" for 36" wide models  
8-15/16" for 30" wide models  
7" Min. (30" and 36" Models)  
10" Min. (48" Models)  
Hood  
Width  
Additional  
Wall Studs  
Installed  
Centerline of  
Installation  
Space  
9
 
Installation  
Professional Vent Hoods  
Drill 3/16" pilot holes through the shims and  
into the soffit studs.  
Step  
Hold the hood against the soffit and secure  
with 6 lag screws with washers.  
SOFFIT INSTALLATION  
4
For additional support and to minimize  
vibration during operation, we recommend  
that the hood be secured to the back wall.  
Drive lag screws through the rear panel of  
the hood and into the wall studs.  
Install Hood  
Below Soffit  
INSTALLATION  
UNDER A SOFFIT  
(SKIP THIS STEP  
IF SOFFIT IS NOT  
USED.)  
ZV881WSS, ZV880WSS  
48" Hood Top View - Front Side  
ZV671WSS, ZV670WSS  
36" Hood Top View - Front Side  
4"  
6-1/4"  
8-1/4"  
2-3/4"  
6-1/8"  
8-1/4"  
6-1/8"  
1"  
3-1/8"  
Junction  
Box  
4-1/4"  
7"  
6-1/4"  
5-3/4"  
6-1/4"  
4-1/2"  
3-1/2"  
3"  
3"  
12"  
12"  
8"  
8"  
Junction  
Box  
3-1/2"  
2-1/4"  
2-7/8"  
3/4"  
10-1/2"  
10-1/2"  
Back Side  
35"  
4-1/2"  
4-1/2"  
23"  
Back Side  
ZV891YSS, ZV890YSS  
ZV681YSS, ZV680YSS  
36" Hood Top View - Front Side  
5-1/2"  
48" Hood Top View - Front Side  
14-11/16"  
2-3/4"  
8-1/2"  
5-1/2"  
6-1/4"  
6-1/8"  
14-11/16"  
5-1/8"  
6-1/8"  
3-1/8"  
3"  
Junction  
Box  
4-1/4"  
7"  
4-1/2"  
3-1/2"  
12"  
12"  
5-7/8"  
Junction  
Box  
14-7/16"  
14-7/16"  
3-1/2"  
2-1/4"  
3"  
2-7/8"  
3/4"  
12-7/16"  
12-7/16"  
Back Side  
47-7/8"  
35-7/8"  
10-15/16"  
10-15/16"  
Back Side  
ZV371YSS, ZV370YSS  
30" Hood Top View - Front Side  
2-1/2"  
5-1/2"  
3-1/8"  
Junction  
Box  
4-1/4"  
7"  
5-1/2"  
3"  
3"  
12"  
11-7/16"  
11-7/16"  
2-7/8"  
3/4"  
12-7/16"  
12-7/16"  
29-7/8"  
Back Side  
10  
 
Installation  
Professional Vent Hoods  
WALL MOUNT INSTALLATION  
Drill 3/16" pilot holes, approximately 1-1/2"  
deep, in all mounting screw locations.  
Hold the hood in position and drive lag  
screws in top left and right mounting holes.  
Step  
Ceiling  
4
A
Install Hood  
Onto Wall  
NOTE: 5/16" hanger bolts can be used in the  
two top locations. Place the hood onto the  
hanger bolts and secure with nuts and washers.  
WALL MOUNT  
INSTALLATION  
(SKIP THESE  
STEPS IF SOFFIT  
IS USED.)  
Install lag screws with washers in remaining  
mounting holes.  
ZV881WSS, ZV880WSS, ZV891YSS, ZV890YSS  
ZV671WSS, ZV670WSS, ZV681YSS, ZV680YSS  
48" Hood Rear View  
36" Hood Rear View  
Ceiling Drywall  
Ceiling Drywall  
6" or 12"  
Duct  
6" or 12"  
Duct  
Cover  
Cover  
Mounting  
Screw  
Mounting  
Screw  
6-1/2"  
6-1/2"  
18"  
Holes  
2-1/2"  
2-1/2"  
18"  
Holes  
6-1/2"  
C
L
6-1/2"  
C
L
8-15/16”  
9”  
9”  
8-15/16”  
13”  
10-15/16”  
10-15/16”  
13”  
35-7/8”  
47-7/8”  
ZV371YSS, ZV370YSS  
30" Hood Rear View  
Ceiling Drywall  
6" or 12"  
Duct  
Cover  
Mounting  
Screw  
6-1/2"  
18"  
Holes  
2-1/2"  
6-1/2"  
C
L
6”  
8-15/16”  
29-7/8”  
6”  
8-15/16”  
11  
 
Installation  
Professional Vent Hoods  
Connect white lead to branch circuit white  
lead.  
Connect black lead to branch circuit black  
lead.  
Connect green lead to branch circuit green  
or bare ground lead.  
Secure all connections with wire nuts on  
each electrical connector.  
Verify that power is turned off at the source.  
W
A
R
N
I
NG  
Step  
If house wiring is not 2-wire with a  
ground wire, a ground must be  
provided by the installer.  
5
Connect  
When house wiring is aluminum,  
be sure to use U.L. approved anti-  
oxidant compound and alumi-  
num-to-copper connectors.  
Electrical  
Step  
Cut a length of duct to connect hood flange to  
the ductwork.  
Duct Tape  
Over Seam and Screw  
Install ductwork, making connections in  
direction of airflow as illustrated.  
Secure joints in ductwork with sheetmetal  
screws.  
Air  
6
Flow  
Connect  
Ductwork  
Screw  
Wrap joints with duct tape for airtight seal.  
Transition duct pieces are available for 48"  
wide models.  
ZX48AY, 4-1/2" x 18-1/2" transition to 10"  
round straight up exhaust.  
ZX48BY, 4-1/2" x 18-1/2" transition to 10"  
round direct to rear exhaust.  
Call your GE Dealer to order.  
Hold the liner below the installed hood.  
Reconnect the male/female connector plug  
to heat lamp and one to blower.  
Carefully, slide liner into installed hood.  
While holding in place, re-install the original  
screws. Make sure that all screws have been  
re-installed.  
Step  
7
Reassemble  
Hood  
Re-install light assembly with original screws.  
Connect to  
Reconnect Male/Female  
Junction Box  
Connector Plug  
To Blower Motor  
Hood Inner Liner  
Replace Screws That  
Hold Inner Liner in Place.  
12  
 
Installation  
Professional Vent Hoods  
“WSS” Duct Covers  
Fasten the duct cover to the top of the hood  
with 2 screws.  
Step  
8
Install  
Duct Cover  
Secure  
with Screws  
“YSS” Duct Covers  
Install one side piece to the top of the hood  
with 2 screws. Install opposite side piece.  
• Secure front panel to the side panels with 2  
torx screws on each side (provided).  
Place the filter drip trays into the bottom  
of the opening.  
Step  
9
Install  
Filters  
Grasp the filter by handles, tip the top  
portion into the opening, move upwards  
and drop into drip trays.  
13  
 
Notes  
Professional Vent Hoods  
14  
 
Notes  
Professional Vent Hoods  
15  
 
Note: While performing installations described in this book,  
safety glasses or goggles should be worn.  
To obtain specific information concerning any  
Monogram product or service, call GE Answer Center®  
consumer information service at 800.626.2000—any  
time, day or night.  
For Monogram local service in your area, call  
1-800-444-1845.  
Pub. No. 49-8816-1  
Dwg. No. 164D3333P060  
ꢀ1999 GE Appliances  
(N.D. 173) 5/99  
10657-1  
NOTE: Product improvement is a continuing endeavor at General  
Electric. Therefore, materials, appearance and specifications are subject  
to change without notice.  
®
Monogram.  
General Electric Company  
Louisville, KY 40225  
 

Eiki Cassette Player 5090A User Manual
Electro Voice Portable Speaker FRX 122 User Manual
Fender Musical Toy Instrument Bassman 500 User Manual
Fender Stereo Amplifier 1970 Relic Stratocaster User Manual
Festool High Chair Zigzag Chair User Manual
Franke Consumer Products Cooktop FNE 905 XS ECS User Manual
Frigidaire Microwave Oven FMT144G1W1 User Manual
Gemini Industries Turntable DJ Q1300 User Manual
Generac Power Systems Portable Generator 5626 User Manual
GE Oven PSB1200 User Manual