GE Air Conditioner AZ29E12DAC User Manual

AZ29E12DAC  
GE Zoneline® Deluxe Series Cooling and Electric Heat Unit  
Wall Case Dimensions  
Dimensions and Installation Information (in inches)  
Electrical Wiring  
Maximum Cord Extension (in inches)  
All wiring, including installation of receptacle, must  
be made in accordance with local electrical codes  
and regulations.  
A
Note: Aluminum wiring may pose special problems –  
consult a qualified electrician.  
C
Grille Options  
Stamped Aluminum Grille – RAG60  
Exterior Architectural Louvers Durable Polycarbonate:  
21  
58  
B
RAG61 (Beige)  
RAG62 (Maple)  
RAG63 (Bittersweet)  
RAG67 (Extruded Aluminum)  
RAB71 Wall Sleeve  
Wall Opening Dimensions  
Retrofit Kits:  
Heavy-gauge galvanized steel, with insulation.  
A – 42", B – 13-3/4", C – 16"  
Add 1/4" to A and C dimensions for all cut-out size.  
RAB71 16-1/4" Min. H x 42-1/4" Min. W  
RAK901L – Wall Case Insulation for use with heat pumps.  
RAK40 – Deflector Kit to adapt chassis for use with  
existing exterior architectural louvered grilles.  
RAB71 available in 16", 24", 28" and 31" depths  
RAB77 16-1/2" Min. H x 42-3/8" Min. W  
RAB77 Wall Sleeve  
Molded SMC fiberglass-reinforced polyester  
compound.  
A – 42-1/8", B– 13-7/8", C – 16-1/4  
Ducted Applications  
2900 and 3900 series can be used with ductwork to heat or cool more than one room. RAK6052  
Duct Adaptor is applied to top of case over air discharge/RAK601 Duct Extension is applied  
to right or left of adaptor. Locally fabricated ductwork may be added to extend to maximum  
recommended distance of 15 feet.  
230/208 Volt Line Cord Connected Units  
Min. Circuit  
Protection  
(Amps)  
Line Cord Electric Heat  
Electric  
Electric  
Kit  
RAK3153  
RAK3203  
RAK3303  
(Btuh)  
Heater Watts Heat Amps  
Electrical Connection  
8,600/7,100  
11,700/9,600  
2,550/2,090  
3,450/2,820  
11.6/10.6  
15.5/14.1  
22.3/20.3  
15  
20  
30  
230/208 volt units may be plugged into a receptacle. 265 volt units are provided with a junction box  
and require direct connection. (NEC Requires 265V Direct Connection) See Architects and Engineers  
Design Data Manual for electrical connection information including use of sub-base for direct  
connected units. Installation must comply with local electrical codes and regulations.  
17,000/13,900 5,000/4,090  
230/208 Volt Sub-Base Connected Units  
Power Connection kits required on all Zoneline chassis.  
Min. Circuit  
Protection  
Heater Watts Heat Amps (Amps)  
Electric Heat  
(Btuh)  
Electric  
Electric  
Sub-Base  
For answers to your Monogram,® GE Profileor  
GE® appliance questions, visit our website at  
ge.com or call GE Answer Center® service,  
800.626.2000.  
RAK204D15P 8,600/7,100  
RAK204D20P 11,700/9,600  
2,550/2,090  
3,450/2,820  
11.6/10.6  
15.5/14.1  
22.3/20.3  
15  
20  
30  
RAK204D30P 17,000/13,900 5,000/4,090  
Specification Created 2/08  
390578  
 

Conair Styling Iron CD117X User Manual
Cooper Lighting Landscape Lighting HMC40SC23E User Manual
Desa Tech Indoor Fireplace CGD3924P User Manual
Dyson Patio Heater AM 04 User Manual
Eureka Water System Aquaguard User Manual
Everpure Water System 7DM User Manual
Frigidaire Dehumidifier 66166042 User Manual
Frigidaire Ventilation Hood HV2730B User Manual
Glem GasEmilia Range S76GGESIB User Manual
Global Machinery Company Sander SA350 User Manual