OPERATING MANUAL
MODE D’EMPLOI
MANUAL DE FUNCIONAMIENTO
HEAT&COOLING MODEL
(REVERSE CYCLE)
ROOM AIR CONDITIONER
WALL MOUNTED TYPE
Indoor Unit
ASU15RLQ
ASU18RLQ
Outdoor Unit
AOU15RLQ
AOU18RLQ
KEEP THIS OPERATION MANUAL
FOR FUTURE REFERENCE
P/N9314969027-01
FUJITSU GENERAL LIMITED
Fig. 1
1
D
2
Fig. 2
3
C
COIL DRY
AIR CLEAN
OPERATION
TIMER
=
AB
5
6
4
7
8
@
#
Fig. 3
Fig. 5
9
I
G
H
J
Fig. 4
Fig. 6
K
–
≠
Ÿ
¤
)
(
⁄
_
+
¡
¢
™
›
fl
‹
fi
‡
£
∞
§
•
¶
º
°
ª
Fig. 7
To facilitate explanation, the accompanying illustra-
tion has been drawn to show all possible indicators;
in actual operation, however, the display will only
show those indicators appropriate to the current op-
eration.
FEATURES AND FUNCTIONS
INVERTER
SWING OPERATION
At the start of operation, a large power is used to bring the
room quickly to the desired temperature. Afterwards, the
unit automatically switches to a low power setting for eco-
nomic and comfortable operation.
TheAir Flow Direction Louvers swings automatically up and
down so that the air speeds to every nook and corner of
your room.
REMOVABLE OPEN PANEL
COIL DRY OPERATION
The indoor unit’s Open Panel can be removed for easy clean-
ing and maintenance.
The Indoor unit can be dried by pressing the COIL DRY but-
ton on the Remote Control Unit so as to avoid going moldy
and restrain the breed of bacterium.
MILDEW-RESISTANT FILTER
AUTO CHANGEOVER
The AIR FILTER has been treated to resist mildew growth,
thus allowing cleaner use and easier care.
The operation mode (cooling, dry, heating) is switched au-
tomatically to maintain the set temperature, and the tem-
perature is kept constant at all times.
SUPER QUIET OPERATION
When the FAN CONTROL button is used to select QUIET, the
unit begins super-quiet operation; the indoor unit’s airflow
is reduced to produce quieter operation.
PROGRAM TIMER
The program timer allows you to integrate OFF timer and
ON timer operations in a single sequence. The sequence
can involve one transition from OFF timer to ON timer, or
from ON timer to OFF timer, within a twenty-four hour pe-
riod.
AIR CLEANING MODE
Relies on the air conditioner’s power to quickly purify the air
in the room.
SLEEP TIMER
When the SLEEP button is pressed during Heating mode,
the air conditioner’s thermostat setting is gradually lowered
during the period of operation; during cooling mode, the
thermostat setting is gradually raised during the period of
operation. When the set time is reached, the unit automati-
cally turns off.
ELECTRONIC AIR CLEAN FILTER
Install for use inside of the dust collection unit. For details
on how to install the filter, please refer to page 15.
Electrical power is used to charge the filter to remove con-
taminants from the air and to effectively collect dust and
remove odors. It also helps to reduce the bacterial activity.
WIRELESS REMOTE CONTROL UNIT
The Wireless Remote Control Unit allows convenient con-
trol of air conditioner operation.
WIRED REMOTE CONTROL UNIT (OPTION)
The optional wired remote control unit (model No.: UTB-UUB) can be used.
When you use remote control unit, there are following different points as compared with using wireless remote control unit.
[The additional functions for wired ones]
• Weekly timer
•Temperature set back timer
[The restricted functions for wired ones]
• Air-cleaning function can't be turned ON/OFF. (During operation, it is always ON)
• QUIET can't be selected in FAN MODE.
• Sleep-timer can't be used.
And you can't use both wired remote control unit and wireless simultaneously.
(Only one kind can be selected)
En-2
NAME OF PARTS
Fig. 1 Indoor Unit
Fig. 6 Remote Control Unit
1Operating Control Panel (Fig. 2)
2MANUAL AUTO button
KSignal Transmitter
LMASTER CONTROL button
MFAN CONTROL button
NSTART/STOP button
OAIR CLEAN button
PCOIL DRY button
ꢀ When kept on pressing the MANUAL
AUTO button for more than 10 seconds,
the forced cooling operation will start.
ꢀ The forced cooling operation is used at the
time of installation.
Only for authorized service personnel’s
use.
QSET button
RSET TEMP. button (
SSLEEP button
/
)
ꢀ When the forced cooling operation starts
by any chance, press the START/STOP
button to stop the operation.
TSWING button
UTIMER MODE button
VTIMER SET (
WTEST RUN button
/
)buttons
3Indicator (Fig. 3)
4Remote Control Signal Receiver
5OPERATION Indicator Lamp (red)
6TIMER Indicator Lamp (green)
ꢀ
ꢀ
ꢀ
This button is used when installing the
conditioner, and should not be used un-
der normal conditions, as it will cause the
air conditioner’s thermostat function to op-
erate incorrectly.
If this button is pressed during normal op-
eration, the unit will switch to test opera-
tion mode, and the Indoor Unit’s OPERA-
TION Indicator Lamp and TIMER Indicator
Lamp will begin to flash simultaneously.
To stop the test operation mode, press the
START/STOP button to stop the air condi-
tioner.
ꢀ If the TIMER indicator lamp flashes when
the timer is operating, it indicates that a
fault has occurred with the timer setting
(See Page 17 Auto Restart).
7AIR CLEAN Indicator Lamp (green)
8COIL DRY Indicator Lamp (orange)
9Intake Grille (Fig. 4)
0Air Filter
AAir Flow Direction Louver
BRight-Left Louver
XCLOCK ADJUST button
YRESET button
ZRemote Control Unit Display (Fig. 7)
[Temperature SET Display
\Transmit Display
]Operating Mode Display
`Fan Speed Display
aAIR CLEAN Display
bSWING Display
(behind Air Flow Direction Louver)
CDrain Hose
DElectrical Air Cleaning Filter
EPower Supply Cord
FPower Supply Plug
cCOIL DRY Display
dTimer Mode Display
eSLEEP Display
Fig. 5 Outdoor Unit
GIntake Port
HOutlet Port
fClock Display
IPipe Unit
JDrain port (bottom)
ꢀ Refer to the folded out page on the cover.
En-3
PREPARATION
CAUTION!
Turn on the Power
ꢀ Take care to prevent infants from
accidentally swallowing batteries.
ꢀ When not using the Remote Control Unit
for an extended period, remove the
batteries to avoid possible leakage and
damage to the unit.
Connect the Power Supply Plug (Fig. 1 F) to an electri-
cal outlet; in the case of a direct line connection, turn
on the circuit breaker.
1
ꢀ If leaking battery fluid comes in contact
with your skin, eyes, or mouth, immedi-
ately wash with copious amounts of
water, and consult your physician.
ꢀ Dead batteries should be removed
immediately and disposed of properly,
either in a battery collection receptacle
or to the appropriate authority.
Load Batteries (AAA/R03/LR03 × 2)
Press and slide the battery compartment lid on the re-
1
verse side to open it.
ꢀ Do not attempt to recharge dry batteries.
Slide in the direction of the arrow while pressing the
mark.
Never mix new and used batteries, or
batteries of different types.
Batteries should last about one year
under normal use. If the Remote Con-
trol Unit’s operating range becomes ap-
preciably reduced, replace the batteries
and press the RESET button with the tip
of a ballpoint pen or other small object.
Insert batteries.
Be sure to align the battery polarities (
2
3
) correctly.
Close the battery compartment lid.
Set the Current time
Press the CLOCK ADJUST button (Fig. 6 X).
1
2
Use the tip of a ball-point pen or other small object to press the button.
Use the TIMER SET (
/
) buttons (Fig. 6 V) to ad-
just the clock to the current time.
button: Press to advance the time.
button: Press to reverse the time.
(Each time the buttons are pressed, the time will be advanced/reversed in
one-minute increments; hold the buttons depressed to change the time
quickly in ten-minute increments.)
Press the CLOCK ADJUST button (Fig. 6 X) again.
This completes the time setting and starts the clock.
3
To Use the Remote Control Unit
ꢀ The Remote Control Unit must be pointed at signal receiver (Fig. 3 4) to operate
correctly.
ꢀ Operating Range: About 23 ft.
ꢀ When a signal is properly received by the air conditioner, a beeping sound will
be heard.
ꢀ If no beep is heard, press the Remote Control Unit button again.
Remote Control Unit Holder
Insert
Slide up
Pull out
Press in
Screws
1
Mount the Holder. 2 Set the Remote Control
3
To remove the Remote
Control Unit (when use at
hand).
Unit.
En-4
OPERATION
To Select Mode Operation
Press the START/STOP button (Fig.6 N).
1
2
The indoor unit’s OPERATION Indicator Lamp (red) (Fig. 3 5) will light.
The air conditioner will start operating.
Press the MASTER CONTROL button (Fig.6 L) to se-
lect the desired mode.
Each time the button is pressed, the mode will change in the following
order.
s
s
s
AUTO
COOL
DRY
t
t
HEAT
FAN
About three seconds later, the entire display will reappear.
Example: When set to COOL.
To Set the Thermostat
Press the SET TEMP. button (Fig. 6 R).
button: Press to raise the thermostat setting.
button: Press to lower the thermostat setting.
ꢀThermostat setting range:
AUTO .................................. 64 °F to 88 °F
Heating ............................... 60 °F to 88 °F
Cooling/Dry ........................ 64 °F to 88 °F
The thermostat cannot be used to set room temperature during the FAN mode (the
temperature will not appear on the Remote Control Unit’s Display).
About three seconds later, the entire display will reappear.
The thermostat setting should be considered a standard value, and may differ
somewhat from the actual room temperature.
Example: When set to 80 °F.
To Set the Fan Speed
Press the FAN CONTROL button (Fig. 6 M).
Each time the button is pressed, the fan speed changes in the following order:
s
AUTO
s
s
s
s
HIGH
MED
LOW
QUIET
About three seconds later, the entire display will reappear.
When set to AUTO:
Heating : Fan operates so as to optimally circulate warmed air.
However, the fan will operate at very low speed when the temperature
of the air issued from the indoor unit is low.
Cooling : As the room temperature approaches that of the thermostat setting,
the fan speed becomes slower.
Fan
: The fan runs at the low fan speed.
Example: When set to AUTO.
The fan will operate at a very low setting during Monitor operation
and at the start of the Heating mode.
SUPER QUIET Operation
SUPER QUIET operation begins. The indoor unit’s airflow will be reduced for qui-
eter operation.
ꢀ SUPER QUIET operation cannot be used during Dry mode. (The same is true
when dry mode is selected during AUTO mode operation.)
ꢀ During Super Quiet operation, Heating and Cooling performance will be reduced
somewhat. If the room does not warm up/ cool down when using SUPER QUIET
Operation, please adjust the air conditioner’s Fan Speed.
En-5
To Stop Operation
Press the START/STOP button (Fig.6 N).
The OPERATION Indicator Lamp (red) (Fig. 3 5) will go out.
About AUTO CHANGEOVER Operation
AUTO:
ꢀ When AUTO CHANGEOVER operation first selected, the fan will oper-
ate at very low speed for about one minute, during which time the unit
detects the room conditions and selects the proper operating mode.
If the differance between thermostat setting and actual room tempera-
ture is more than +4 °F → Cooling or dry operation
If the difference between thermostat setting and actual room tempera-
ture is within 4 °F → Monitor operation
If the difference between thermostat setting and actual room tempera-
ture is more than –4 °F → Heating operation
ꢀ When the air conditioner has adjusted your room’s temperature to near
the thermostat setting, it will begin monitor operation. In the monitor
operation mode, the fan will operate at low speed. If the room tem-
perature subsequently changes, the air conditioner will once again
select the appropriate operation (Heating, Cooling) to adjust the tem-
perature to the value set in the thermostat.
(The monitor operation range is 4 °F relative to the thermostat set-
ting.)
ꢀ If the mode automatically selected by the unit is not what you wish,
select one of the mode operation (HEAT, COOL, DRY, FAN).
About Mode Operation
Heating: ꢀ Use to warm your room.
ꢀ When Heating mode is selected, the air conditioner will operate at very
During Heating mode:
Set the thermostat to a temperature set-
ting that is higher than the current room
temperature. The Heating mode will not
operate if the thermostat is set lower than
the actual room temperature.
low fan speed for about 3 to 5 minutes, after which it will switch to the
selected fan setting. This period of time is provided to allow the indoor
unit to warm up before begin full operation.
ꢀ When the room temperature is very low, frost may form on the outside
unit, and its performance may be reduced. In order to remove such
frost, the unit will automatically enter the defrost cycle from time to
time. During Automatic Defrosting operation, the OPERATION Indica-
tor Lamp (red) (Fig. 3 5)will flash, and the heat operation will be inter-
rupted.
During Cooling/Dry mode:
Set the thermostat to a temperature set-
ting that is lower than the current room
temperature. The Cooling and Dry modes
will not operate if the thermostat is set
higher than the actual room temperature
(in Cooling mode, the fan alone will oper-
ate).
Cooling: ꢀ Use to cool your room.
Dry:
ꢀ Use for gently cooling while dehumidifying your room.
ꢀ You cannot heat the room during Dry mode.
During Fan mode:
You can not use the unit to heat and cool
your room.
ꢀ During Dry mode, the unit will operate at low speed; in order to adjust
room humidity, the indoor unit’s fan may stop from time to time. Also,
the fan may operate at very low speed when adjusting room humidity.
ꢀ The fan speed cannot be changed manually when Dry mode has been
selected.
Fan:
ꢀ Use to circulate the air throughout your room.
En-6
AIR CLEANING OPERATION
If you wish to eliminate dirt,dust,cigarette smoke, pollen, or just simply purify the
air of the room, use the Air Cleaning Mode.
Press the START/STOP button (Fig. 6 N).
1
The OPERATION Indicator Lamp (red) (Fig. 3 5) will light.
(If the unit is already in operation, please proceed to step 2.)
Press the AIR CLEAN button (Fig. 6 O).
2
The AIR CLEAN Indicator Lamp (green) (Fig. 3 7) will light up.
ꢀ Air conditioning and Air Cleaning will function simultaneously.
If you wish to stop Air Clean
Press the AIR CLEAN button (Fig. 6 O) once again.
The AIR CLEAN Indicator Lamp (green) (Fig. 3 7) will go out.
ꢀ This will only stop the Air Cleaning, the air conditioner will continue operating.
To also stop the air conditioner
Press the START/STOP button (Fig. 6 N).
The OPERATION Indicator Lamp (red) (Fig. 3 5) will go out.
ꢀThe next time the START / STOP button (Fig. 6 N) is pressed air conditioning
and air cleaning will both resume operating.
Air cleaning
ꢀ During operation, the unit produces a small amount of ozone that can be smelled.
ꢀ When this unit is used in combination with the ultrasonic humidifier, white parti-
cles may become attached to the plasma filter unit. If this happens, clean the
plasma filter unit as soon as possible. (Refer to page 13, 14.)
ꢀ The air cleaning operation cannot remove gases such as carbon monoxide and
alcohol from the air. During operation, ventilate the room often to prevent as-
phyxiation or suffocation.
ꢀ If the intake filter is removed during operation, a safety device will stop the op-
eration of the plasma filter unit. If this happens, the AIR CLEAN Indicator Lamp
(green) on the indoor unit will flash after some time has passed. Use the START/
STOP button on the remote controller to stop the operation, install the intake
filter, and then use the START/STOP button to restart the operation.
ꢀ Use the FAN CONTROL button to change the fan speed. (Refer to page 5.) The
plasma filter unit operates most effectively at the highest fan speed.
ꢀ The AIR CLEAN Indicator Lamp (green) will flash to inform you that the periodic
cleaning of the plasma filter unit is required. (Refer to page 13, 14.)
En-7
TIMER OPERATION
Before using the timer function, be sure that the Remote Control Unit is set to the correct current time (ꢁ P. 4).
To Use the ON timer or OFF timer
To Cancel the Timer
Press the START/STOP button (Fig. 6 N)
(if the unit is already operating, proceed to step 2).
The indoor unit’s OPERATION Indicator Lamp (red) (Fig. 3 ) will light.
1
Use theTIMER MODE button to select
“CANCEL”.
The air conditioner will return to normal
operation.
5
To Change the Timer Settings
Press the TIMER MODE button (Fig. 6 U) to select the
OFF timer or ON timer operation.
Each time the button is pressed the timer function changes in the follow-
ing order:
2
Perform steps 2 and 3.
To Stop Air Conditioner Operation
while the Timer is Operating
Press the START/STOP button.
s
s
s
ON
CANCEL
OFF
To Change Operating Conditions
t
PROGRAM(OFF → ON, OFF ← ON)
If you wish to change operating conditions
(Mode, Fan Speed, Thermostat Setting,
SUPER QUIET mode) after making the
timer setting, wait until the entire display
reappears, then press the appropriate
buttons to change the operating condition
desired.
The indoor unit’s greenTIMER Indicator Lamp (Fig. 3 6) will light.
Use the TIMER SET buttons (Fig. 6 V) to adjust the
desired OFF time or ON time.
Set the time while the time display is flashing (the flashing will continue
for about five seconds).
3
button: Press to advance the time.
button: Press to reverse the time.
About five seconds later, the entire display will reappear.
To Use the Program timer
Press the START/STOP button (Fig. 6 N).
(if the unit is already operating, proceed to step 2).
The indoor unit’s OPERATION Indicator Lamp (red) (Fig. 3 5) will light.
To Cancel the Timer
1
Use the TIMER MODE button to select
“CANCEL.”
The air conditioner will return to normal
operation.
Set the desired times for OFF timer and ON timer.
To Change the Timer Settings
2
See the section “To Use the ON timer or OFF timer” to set the desired
1. Follow the instructions given in the section
“To Use the ONTimer or OFFTimer” to se-
lect the timer setting you wish to change.
mode and times.
About three seconds later, the entire display will reappear.
The indoor unit’sTIMER Indicator Lamp (green) (Fig. 3 6) will light.
2. Press the TIMER MODE button to select
either OFF
ON or OFF
ON.
Press the TIMER MODE button (Fig. 6 U) to select the
To Stop Air Conditioner Operation
while the Timer is Operating
3
PROGRAM timer operation (OFF
will display).
ON or OFF
ON
Press the START/STOP button.
The display will alternately show “OFF timer” and “ON timer”, then change
to show the time setting for the operation to occur first.
To Change Operating Conditions
If you wish to change operating conditions
(Mode, Fan Speed, Thermostat Setting,
SUPER QUIET mode), after making the timer
setting wait until the entire display reap-
pears, then press the appropriate buttons to
change the operating condition desired.
ꢀ The program timer will begin operation. (If the ON timer has been se-
lected to operate first, the unit will stop operating at this point.)
About five seconds later, the entire display will reappear.
About the Program timer
ꢀ The program timer allows you to integrate OFF timer and ON timer operations in
a single sequence. The sequence can involve one transition from OFF timer to
ON timer, or from ON timer to OFF timer, within a twenty-four hour period.
ꢀ The first timer function to operate will be the one set nearest to the current time.
The order of operation is indicated by the arrow in the Remote Control Unit’s
Display (OFF → ON, or OFF ← ON).
ꢀ One example of Program timer use might be to have the air conditioner auto-
matically stop (OFF timer) after you go to sleep, then start (ON timer) automati-
cally in the morning before you arise.
En-8
SLEEP TIMER OPERATION
Unlike other timer functions, the SLEEP timer is used to set the length of time until air conditioner operate is stopped.
To Use the SLEEP Timer
To Cancel the Timer:
While the air conditioner is operating or stopped, press the
SLEEP button (Fig. 6 S).
The indoor unit’s OPERATION Indicator Lamp (red) (Fig. 3 5) lights and theTIMER
Use the TIMER MODE button to select
“CANCEL”.
The air conditioner will return to normal
operation.
Indicator Lamp (green) (Fig. 3 6) light.
To Stop the Air Conditioner During
Timer Operation:
To Change the Timer Settings
Press the START/STOP button.
Press the SLEEP button (Fig. 6 S) once again and set the time
using the TIMER SET(
/
) buttons (Fig. 6 V).
Set the time while the Timer Mode Display is flashing (the flashing will continue
about five seconds).
button: Press to advance the time.
button: Press to reverse the time.
About five seconds later, the entire display will reappear.
About the SLEEP Timer
To prevent excessive warming or cooling during sleep, the SLEEP timer function automatically modifies the thermostat setting
in accordance with the set time setting. When the set time has elapsed, the air conditioner completely stops.
During Heating operation:
During Cooling/Dry operation:
When the SLEEP timer is set, the thermostat setting is
automatically lowered 2 °F every thirty minutes.When the ther-
mostat has been lowered a total of 8 °F, the thermostat setting
at that time is maintained until the set time has elapsed, at
which time the air conditioner automatically turns off.
When the SLEEP timer is set, the thermostat setting is auto-
matically raised 2 °F every sixty minutes. When the thermo-
stat has been raised a total of 8 °F, the thermostat setting at
that time is maintained until the set time has elapsed, at which
time the air conditioner automatically turns off.
SLEEP timer setting
SLEEP timer setting
2 °F
4 °F
6 °F
8 °F
Set time
30
minutes
1 hour
1 hour
4 °F
2 °F
1 hour
30 minutes
Set time
En-9
ADJUSTING THE DIRECTION OF AIR CIRCULATION
Vertical (up-down) direction of airflow is adjusted by pressing the Remote Control Unit’s SET button. Horizontal (right-left)
airflow direction is adjusted manually, by moving the Air Flow Direction Louvers.
Whenever making horizontal airflow adjustments, start air conditioner operation and be sure that the vertical air direction
louvers are stopped.
R
Vertical Air Direction Adjustment
DANGER!
ꢀ Never place fingers or foreign objects in-
side the outlet ports, since the internal fan
operates at high speed and could cause
personal injury.
Press the SET button (Fig. 6 Q).
Each time the button is pressed, the air direction range will change as follows:
1 2 3 4 5 6 7
ꢀ Always use the Remote Control Unit’s
SET button to adjust the vertical airflow
louvers. Attempting to move them
manually could result in improper op-
eration; in this case, stop operation and
restart. The louvers should begin to
operate properly again.
Types of Air flow Direction Setting:
1,2,3
:
During Cooling/Dry modes
4,5,6,7: During Heating mode
1,2,3,4,5,6,7: During Fan mode
The Remote Control Unit’s display does
not change.
ꢀ During use of the Cooling and Dry
modes, do not set the Air Flow Direc-
tion Louvers in the Heating range (4-
7) for long periods of time, since wa-
ter vapor may condense near the out-
let louvers and drops of water may drip
from the air conditioner. During the
Cooling and Dry modes, if the Air Flow
Direction Louvers are left in the heat-
ing range for more than 30 minutes,
they will automatically return to posi-
tion 3.
ꢀ Use the air direction adjustments within the ranges shown above.
ꢀ The vertical airflow direction is set automatically as shown, in accordance with
the type of operation selected.
During Cooling/Dry mode : Horizontal flow 1
During Heating mode
: Downward flow 7
ꢀ When used in a room with infants, chil-
dren, elderly or sick persons, the air
direction and room temperature
should be considered carefully when
making settings.
ꢀ During AUTO mode operation, for the first minute after beginning operation,
airflow will be horizontal 1; the air direction cannot be adjusted during this pe-
riod.
Right-Left Adjustment
R
DANGER!
ꢀ When adjusting the Right-Left Louvers, it
is necessary to stop the Air-Conditioner
first and make sure that it stops completely
before adjusting the direction.
Adjust the Right-Left louvers.
ꢀ Move the Right-Left louvers to adjust air flow in the direction you prefer.
knob
knob(three places)
En-10
SWING OPERATION
Begin air conditioner operation before performing this procedure.
To select SWING Operation
Press the SWING button (Fig. 6 T).
The SWING Display (Fig. 7 b) will light.
In this mode, the Air Flow Direction Louvers will swing automatically to direct the
air flow both up and down.
To stop SWING Operation
Press the SWING button (Fig. 6 T) once again.
The SWING Display (Fig. 7 b) will go out.
Airflow direction will return to the setting before swing was begun.
About Swing Operation
During cooling/Dry mode : Swings between 1and 3.
During heating mode
: Swings between 3and 7.
ꢀ The SWING operation may stop temporarily when the air conditioner’s fan is not
operating, or when operating at very low speeds.
COIL DRY OPERATION
The Indoor unit can be dried by pressing the COIL DRY button on the Remote Control Unit so as to avoid going moldy and
restrain the breed of bacterium.
The COIL DRY Operation will operate for 30 minutes after pressing the COIL DRY button and it will stop automatically.
To select COIL DRY Operation
Press the COIL DRY button (Fig. 6 P) during operation or when
it stops.
The COIL DRY Indicator Lamp (orange) (Fig. 3 8) and the COIL DRY Display (Fig. 7
c) will light. Then it will disappear after 30 minutes.
To cancel COIL DRY Operation
Press the START/STOP button (Fig. 6 N) during COIL DRY
Operation.
The COIL DRY Indicator Lamp (orange) (Fig. 3 8) and the COIL DRY Display (Fig. 7
c) will go out . Then the operation stops.
About COIL DRY Operation
ꢀ Press the COIL DRY button again during COIL DRY Operation, COIL DRY Opera-
tion can be reset.
ꢀ The COIL DRY Operation cannot get rid of the existed mould or bacterium, and it
has no sterilization effect either.
MANUAL AUTO OPERATION
Use the MANUAL AUTO operation in the event the Remote Control Unit is lost or otherwise unavailable.
How To Use the Main Unit Controls
ꢀ When the air conditioner is operated
with the controls on the Main Unit, it
Press the MANUAL AUTO button (Fig. 2 2) on the main unit
will operate under the same mode as
the AUTO mode selected on the Re-
mote Control Unit (see page 6).
control panel.
To stop operation, press the MANUAL AUTO button (Fig. 2 2) once again.
ꢀ The fan speed selected will be“AUTO”
and the thermostat setting will be
standard.(76 °F)
(Controls are located inside the Open Panel)
En-11
CLEANING AND CARE
ꢀ Before cleaning the air conditioner, be sure to turn it off and disconnect the Power Supply Cord.
CAUTION!
ꢀ Be sure the Intake Grille (Fig. 4 9) is installed securely.
ꢀ When removing and replacing the air filters, be sure not to touch the heat exchanger, as per-
sonal injury may result.
Cleaning the Intake Grille
1. Remove the Intake Grille.
Cleaning the Air Filter
1. Open the Intake Grille, and remove the air
1Place your fingers at both lower ends of the grille
panel, and lift forward; if the grille seems to catch
partway through its movement, continue lifting up-
ward to remove.
filter.
Lift up the air filter’s handle, disconnect the two lower
tabs, and pull out.
2Pull past the intermediate catch and open the Intake
Grille wide so that it become horizontal.
Air filter handle
Intake Grille
2. Remove dust with a vacuum cleaner or by
washing.
Intake Grille
After washing, allow to dry thoroughly in a shaded place.
3. Replace the Air Filter and close the Intake
Grille.
Mounting
shaft
1Align the sides of the air filter with the panel, and push
in fully, making sure the two lower tabs are returned
properly to their holes in the panel.
Knob
2. Clean with water.
Remove dust with a vacuum cleaner; wipe the unit with
warm water, then dry with a clean, soft cloth.
3. Replace the Intake Grille.
2Close the Intake Grille.
1Pull the knobs all the way.
(For purposes of example, the illustration shows the unit
without Intake Grille installed.)
2Hold the grille horizontal and set the left and right
mounting shafts into the bearings at the top of the
panel.
ꢀ Dust can be cleaned from the air filter either with a vacuum
cleaner, or by washing the filter in a solution of mild de-
tergent and warm water. If you wash the filter, be sure to
allow it to dry thoroughly in a shady place before rein-
stalling.
3Press the place where the arrow on the diagram indi-
cates and close the Intake Grille.
Mounting shaft
Intake
Grille
Bearing
Knob
ꢀ If dirt is allowed to accumulate on the air filter, air flow
will be reduced, lowering operating efficiency and increas-
ing noise.
ꢀ During periods of normal use, the Air Filters should be
cleaned every two weeks.
Intake Grille
Mounting
shaft
Knob
ꢀ When used for extended periods, the unit may accumulate dirt inside, reducing its performance.We recommend that the
unit be inspected regularly, in addition to your own cleaning and care. For more information, consult authorized service
personnel.
ꢀ When cleaning the unit’s body, do not use water hotter than 104 °F, harsh abrasive cleansers, or volatile agents like
benzene or thinner.
ꢀ Do not expose the unit body to liquid insecticides or hairsprays.
ꢀ When shutting down the unit for one month or more, first allow the fan mode to operate continuously for about one-half
day to allow internal parts to dry thoroughly.
En-12
CLEANING THE PLASMA AIR CLEANING FILTER
Before cleaning the plasma filter unit, be sure to turn off the power supply to the air conditioner.
Electric shock may result.
WARNING!
CAUTION!
ꢀ Make sure the plasma filter unit is properly mounted before cleaning or performing other tasks
on it. If the unit is not properly mounted, it could fall off and cause damage or injury.
ꢀ You can be injured if you touch the heat exchanger when removing or installing the plasma filter
unit. Do not insert your fingers between the plasma filter unit and the heat exchanger.
Regarding the Air Cleaning check function
ꢀ This function is illustrated by the flashing of the AIR CLEAN Indicator Lamp (green), indicating that the unit requires
maintenance.
After Air Cleaning Mode has been in use for approximately 400 hours, the AIR CLEAN Indicator Lamp (green) will begin to
slowly flash (approximately once every 7 seconds). When this occurs, the unit requires maintenance.
After Air Cleaning Mode has been in use for approximately 500 hours, the AIR CLEAN Indicator Lamp (green) will begin to
flash quickly (approximately once every 3 seconds). At this point, Air Cleaning will cease functioning. Please carry out
appropriate maintenance for the unit.
ꢀ Please carry out unit maintenance every 6 months.
ꢀ If a squeaking or chirping sound is heard, unit maintenance needs to be carried out, even if the AIR CLEAN Indicator Lamp
(green) is not flashing.
Cleaning the dust collection unit
1. Open the intake grille and remove the air
filter on the right.
4. Wash with water and dry.
1Soak the plasma filter unit in warm water (104 to
113˚F) for 10 to 15 minutes. If the plasma filter unit is
extremely dirty, extremely dilute a mild synthetic laun-
dry detergent (low alkalinity or isotope detergent) to
15 times the standard concentration and allow the
plasma filter unit to soak in it.
ꢀ
Please consult the instructions for cleaning the air
filter on page 12.
2. Remove the dust collection unit.
2Gently move up and down and to the right and left. A
soft sponge can also be used to wipe the surface.
3Rinse with clean water.
4Shake the plasma filter unit to drain off the water. (If
the plasma filter unit is extremely dirty, repeat Steps
1through 4two or three more times.)
5Place the plasma filter unit in the shade and allow it
to dry completely.
handle
Securely grasp the dust collection unit by the handle and
pull it out (as shown by the arrow).
(The above figure is only for reference, so the intake grille
is not included).
3. Remove the air cleaning & deodorizing fil-
ter from the cleaning unit.
1Open the filter case at the rear of cleaning unit.
ꢀ Only use a mild synthetic laundry detergent (low
alkalinity or isotope detergent).
ꢀ Never disassemble the plasma filter unit.
Claw
Claw
ꢀ Never soak the plasma filter unit in hot water.
Filter case
ꢀ Never wipe the plasma filter unit with a scrub brush
or other hard or abrasive items. This will damage
the honey comb filter.
ꢀ Never insert a brush into the inside of plasma filter
unit for washing. This will damage the internal parts
and cause malfunctioning of the plasma filter unit.
2Remove the air cleaning & deodorizing filter.
ꢀ Never use dryer or other device to blow hot air on
the plasma filter unit. This will cause deformation
or other damage.
ꢀ Before re-installing the unit, please wait until it is
completely dry. If the unit is installed when still wet
and then put into operation, the OPERATION Indi-
cator Lamp (red) and the TIMER Indicator Lamp
(green) will flash and Air Cleaning will stop.
Air cleaning &
deodorizing filter
En-13
Cleaning the dust collection unit
5. Install the unit.
6. Install the air filter.
(The above figure is only for reference, so the intake grille
is not included.)
ꢀ Please consult instructions for cleaning the air filter
on page 12.
7. Close the intake grille.
Push the intake grill in at 4 points (the two ends of its
lower side as well as two center points of the lower side,
as shown in the figure) to close it.
Align the two ends of the dust collection
unit with the guide rail and slide in.
1
Please ensure that the intake grille is
closed properly.
Guide rail
ꢀ If, after cleaning the dust collection unit, the
operation indicator lamp and the timer indicator
lamp flash during Air Cleaning, please ensure that
the unit is not damp and that the intake grille is
properly closed.
ꢀ If, after having checked that the unit is fully dry and
that the intake grille is closed properly, the indicator
lamps continue to flash, the dust collection unit may
be damaged. Please consult an authorised dealer
to obtain a replacement.
2Slide in until it clicks.
“Click”
“Click”
WARNING!
ꢀBe sure the Intake Grille (Fig. 4 9) is installed
securely.
ꢀ Please ensure that the dust collection unit is
completely dry before installing.
ꢀ After installing the dust collection unit, please
ensure that it has been inserted fully into its place.
If it has not been installed correctly, the OPERATION
Indicator Lamp (red) and the TIMER Indicator Lamp
(green) will flash, and Air Cleaning will stop.
En-14
How to install or remove the Air-
cleaning and Deodorizing filter
Air-cleaning and Deodorizing filter
maintenance
As well as ensuring the maintenance of the dust collecting
unit, please also take care of the filter.
(Please carry out maintenance on the filter every 6 months.)
1. Remove the dust-collecting unit.
ꢀ
Please consult steps 1 and 2 of cleaning the dust-
collecting unit on page 13.
1. Open the intake grille and remove the air
filter from the right side.
2. Install or remove the Air-cleaning and
Deodorizing filter into the unit.
1Open the filter case inside the dust-collecting unit.
ꢀ
Please consult step 1 of cleaning the air filter on page 12.
2. Take out the unit and remove the Air-
Hook
Hook
cleaning and Deodorizing filter.
ꢀ Please consult steps 2 and 3 of cleaning the air filter
on page 13.
Filter case
3. Air-dry after washing.
1Wash using lukewarm or warm water. If quite dirty,
wash using a mild detergent.
Please do not rub the filter, it may cause its Air-
cleaning performance to be reduced.
2Insert or remove the Air-cleaning and Deodorizing filter
into the dust-collecting unit.
2Rinse it under running water.
Install
3Allow it to dry thoroughly in a shaded place.
4. Install the Air-cleaning and Deodorizing
filter.
ꢀ
Please consult the instructions on how to install the
filter on page 15.
Filter
Remove
5. Install the air filter and close the intake
grille.
ꢀ Please place the air cleaning & deodorizing
filter, with the black surface upward.
ꢀ
Please consult step 3 of cleaning the air filter on
page 12.
3Close the filter case.
Regarding the Air-cleaning and Deodorizing filter
Filter Case
ꢀ Please change the filter approximately every 2 years to
ensure good Air-cleaning performance. (This is only
possible if the filter is cleaned once every six months)
“Click”
“Click”
Hook
Hook
When changing the filter, please make sure you purchase
the correct model (UTR–FA14).
ꢀ Please ensure that the filter case is properly
closed. If the filter case is not properly closed,
the filter could fall out.
ꢀ Please only install filters that are licensed by our
company.
ꢀ Regarding storage and care of the filter, please avoid
exposing it to high temperatures and high humidity.
Also, use it as soon as possible after opening its
packaging.
3. Install the dust-collection unit.
ꢀ Please consult steps 5, 6 and 7 of cleaning the dust-
collection unit on page 14.
❇ When removing the filter, please follow these
steps backwards.
En-15
TROUBLESHOOTING
In the event of a malfunction (burning smell, etc.), immediately stop operation, disconnect the
Power Supply Plug, and consult authorized service personnel.
WARNING!
Merely turning off the unit’s power switch will not completely disconnect the unit from the power
source. Always be sure to disconnect the Power Supply Plug or turn off your circuit breaker to
ensure that power is completely off.
Before requesting service, perform the following checks:
Symptom
See Page
Problem
NORMAL
FUNCTION
Doesn’t operate immedi-
ately:
ꢀ If the unit is stopped and then immediately started again, the com-
pressor will not operate for about 3 minutes, in order to prevent
fuse blowouts.
—
ꢀ
Whenever the Power Supply Plug is disconnected and then re-
connected to a power outlet, the protection circuit will operate for
about 3 minutes, preventing unit operation during that period.
Noise is heard:
ꢀ During operation and immediately after stopping the unit, the
sound of water flowing in the air conditioner’s piping may be
heard. Also, noise may be particularly noticeable for about 2 to 3
minutes after starting operation (sound of coolant flowing).
—
ꢀ During operation, a slight squeaking sound may be heard. This is
the result of minute expansion and contraction of the front cover
due to temperature changes.
ꢀ
During Heating operation, a sizzling sound may be heard occasional.
This sound is produced by the Automatic Defrosting operation.
17
—
Smells:
ꢀ Some smell may be emitted from the indoor unit. This smell is
the result of room smells (furniture, tobacco, etc.) which have
been taken into the air conditioner.
Mist or steam are
emitted:
ꢀ During Cooling or Dry operation, a thin mist may be seen emitted
from the indoor unit. This results from the sudden Cooling of
room air by the air emitted from the air conditioner, resulting in
condensation and misting.
—
ꢀ During Heating operation, the outdoor unit’s fan may stop, and
steam may be seen rising from the unit. This is due to Automatic
Defrosting operation.
17
Airflow is weak or stops:
ꢀ When Heating operation is started, fan speed is temporarily very
low, to allow internal parts to warm up.
ꢀ During Heating operation, if the room temperature rises above
the thermostat setting, the outdoor unit will stop, and the indoor
unit will operate at very low fan speed. If you wish to warm the
room further, set the thermostat for a higher setting.
—
ꢀ During Heating operation, the unit will temporarily stop opera-
tion (between 7 and 15 minutes) as the Automatic Defrosting mode
operates. DuringAutomatic Defrosting operation, the OPERATION
Indicator Lamp will flash.
17
ꢀ The fan may operate at very low speed during Dry operation or
when the unit is monitoring the room’s temperature.
5
5
ꢀ During SUPER QUIET operation, the fan will operate at very low
speed.
ꢀ In the monitor AUTO operation, the fan will operate at very low
speed.
5
ꢀ During Heating operation, water may be produced from the out-
door unit due to Automatic Defrosting operation.
Water is produced from
the outdoor unit:
17
ꢀ After approximately 400 hours of Air Cleaning Mode use, the AIR
CLEAN Indicator Lamp will begin to flash slowly (as shown in the
figure). When this occurs, please stop the system, remove the
mains socket and carry out maintenance on the dust collecting
unit's air filter.
The AIR CLEAN Indicator
Lamp (green) will begin
to slowly flash (as shown
in the figure):
13-14
13-14
ꢀ After approximately 500 hours of Air Cleaning Mode use, the AIR
CLEAN Indicator Lamp will begin to flash quickly (as shown in
the figure). At this point, Air Cleaning will stop functioning. Please
stop the system, remove the mains socket and carry out mainte-
nance on the dust collecting unit's air filter.
The AIR CLEAN Indicator
Lamp (green) will begin
to flash quickly (as shown
in the figure):
En-16
TROUBLESHOOTING
Items to check
Symptom
See Page
ꢀ Is the Power Supply Plug disconnected its outlet?
ꢀ Has there been a power failure?
Doesn’t operate at all:
CHECK ONCE
MORE
—
ꢀ Has a fuse blown out, or a circuit breaker been tripped?
ꢀ Is the timer operating?
8 - 9
Poor Cooling performance: ꢀ Is the Air Filter dirty?
ꢀ Air the air conditioner’s intake grille or outlet port blocked?
ꢀ Did you adjust the room temperature settings (thermostat) cor-
rectly?
ꢀ Is there a window or door open?
—
ꢀ In the case of Cooling operation, is a window allowing bright sun-
light to enter? (Close the curtains.)
ꢀ In the case of Cooling operation, are there heating apparatus and
computers inside the room, or are there too many people in the
room?
ꢀ Is the unit set for SUPER QUIET operation?
5
4
The unit operates
differently from the Remote
Control Unit’s setting:
ꢀ Are the Remote Control Unit’s batteries dead?
ꢀ Are the Remote Control Unit’s batteries loaded properly?
If the problem persists after performing these checks, or if you notice burning smells, or the OPERATION Indicator Lamp
(Fig. 3 5) and the TIMER Indicator Lamp (Fig. 3 6) flashes, immediately stop operation, disconnect the Power Supply Plug
(Fig. 1 F), and consult authorized service personnel.
OPERATING TIPS
Operation and Performance
Microcomputer-controlled Automatic Defrosting
Heating Performance
ꢀ When using the Heating mode under conditions of low
outdoor temperature and high humidity, frost may form
on the outdoor unit, resulting in reduced operating per-
formance.
In order to prevent this kind of reduced performance, this
unit is equipped with a Microcomputer-controlled Auto-
matic Defrosting function. If frost forms, the air condi-
tioner will temporarily stop, and the defrosting circuit will
operate briefly (for about 7-15 minutes).
ꢀ This air conditioner operates on the heat-pump princi-
ple, absorbing heat from outdoor air and transferring that
heat indoors. As a result, the operating performance is
reduced as outdoor air temperature drops. If you feel that
insufficient heating performance is being produced, we
recommend you use this air conditioner in conjunction
with another kind of heating appliance.
ꢀ Heat-pump air conditioners heat your entire room by
recirculating air throughout the room, with the result that
some time may be required after first starting the air con-
ditioner until the room is heated.
During Automatic Defrosting operation, the OPERATION
Indicator Lamp (red) will flash.
AUTO Restart
In Event of Power Interruption
ꢀ
If a power failure occurs during TIMER operation, the timer
will be reset and the unit will begin (or stop) operation at the
new time setting. In the event that this kind of timer fault
occurs the TIMER Indicator Lamp will flash (see Page. 3).
ꢀ The air conditioner power has been interrupted by a
power failure. The air conditioner will then restart auto-
matically in its previous mode when the power is restored.
ꢀ Operated by setting before the power failure.
ꢀ Use of other electrical appliances (electric shaver, etc.) or
nearby use of a wireless radio transmitter may cause the
air conditioner to malfunction. In this event, temporarily
disconnect the Power Supply Plug, reconnect it, and then
use the Remote Control Unit to resume operation.
En-17
OPERATING TIPS
Temperature and Humidity Range
Cooling Mode
Dry Mode
Heating Mode
About 5 °F to 75 °F
About 86 °F or less
Outdoor temperature
Indoor temperature
About 14 °F to 115 °F
About 64 °F to 90 °F
About 14 °F to 115 °F
About 64 °F to 90 °F
ꢀ If the air conditioner is used under higher temperature conditioner than those listed, the built-in protection circuit may
operate to prevent internal circuit damage. Also, during Cooling and Dry modes, if the unit is used under conditions of
lower temperature than those listed above, the heat-exchanger may freeze, leading to water leakage and other damage.
ꢀ Do not use this unit for any purposes other than the Cooling, Dehumidifying, and air-circulation of rooms in ordinary
dwellings.
ꢀ If the unit is used for long periods under high-humidity conditions, condensation may form on the surface of the indoor
unit, and drip onto the floor or other objects underneath. (About 80% or more)
Tips for saving energy
ꢀ When the outdoor temperature is low (about 50 °F or less), the unit will consume the power of 20~40W unless the power
plug is disconnected from the outlet even if the air conditioner turns off.
ꢀ Remove the power plug to stop the power supply for energy saving when not using for a long time.
En-18
|