Chromalox Weather Radio 1604 7 User Manual

1604-7  
Temperature Controller with mA Output  
Chromalox  
1604  
Issue date  
May 2000  
r USER'S MANUAL  
1604-7-0-AB.p65  
1
5/16/00, 10:50 AM  
 
Model identification  
Model  
1604 1/16 DIN Temperature Controller  
Code  
Output 1 - Heat or Cool  
7
20 mA Output  
Code  
1
Output 2 - Alarm  
Relay, 2 Amp at 250 VAC (Resistive load)  
Code  
0
1
2
3
4
None  
Out #3, 2 Amps at 250 V AC (Resistive load)  
Heater Break Down input, Out #3  
RS 485 Digital communications, Out #3  
RS 485 Digital comm., Heater Break Down input, Out #3  
Code  
Instrument Power  
100 - 240 Vac  
24 Vac/dc  
3
5
Code  
0
Add to complete model number  
1601  
6
1
0
3
0
Typical Model Number  
III  
1604-7-0-AB.p65  
3
5/16/00, 10:50 AM  
 
MOUNTING REQUIREMENTS  
Select a mounting location where there is  
minimum vibration and the ambient temperature  
range between 0 and 50 °C.  
The instrument can be mounted on a panel up to  
15 mm thick with a square cutout of 45 x 45 mm.  
For outline and cutout dimensions refer to Fig. 2.  
The surface texture of the panel must be better  
than 6,3 mm.  
The instrument is shipped with rubber panel  
gasket (50 to 60 Sh).  
To assure the IP65 and NEMA 4 protection, insert  
the panel gasket between the instrument and the  
panel as shown in fig. 1.  
While holding the instrument against the panel  
proceed as follows:  
Screw  
1) insert the gasket in the instrument case;  
2) insert the instrument in the panel cutout;  
3) pushing the instrument against the panel,  
insert the mounting bracket;  
bracket  
Panel  
4) with a screwdriver, turn the screws with a  
torque between 0.3 and 0.4 Nm.  
Gasket  
Fig. 1  
1
1604-7-1-AB.p65  
1
5/16/00, 10:50 AM  
 
3.0  
(75)  
OUTLINE AND CUT OUT  
DIMENSIONS  
2.4  
(60)  
1.77  
(45)  
1.9  
(48)  
1.77  
(45)  
2.2  
(56)  
4.8  
(122)  
Fig. 2  
OUTLINE AND CUT-OUT DIMENSIONS  
2
1604-7-1-AB.p65  
2
5/16/00, 10:50 AM  
 
A) MEASURING INPUTS  
CONNECTION DIAGRAMS  
NOTE: Any external components (like zener  
barriers etc.) connected between sensor and  
input terminals may cause errors in measurement  
due to excessive and/or not balanced line  
resistance or possible leakage currents.  
Connections are to be made with the instrument  
housing installed in its proper location.  
TC INPUT  
10  
9
+
_
Shield  
Shield  
10  
9
+
_
Fig. 4  
NOTE:  
1) Don’t run input wires together with power  
cables.  
2) For TC wiring use proper compensating cable  
preferable shielded.  
3) when a shielded cable is used, it should be  
connected at one point only.  
Fig. 3 .A  
REAR TERMINAL BLOCK  
3
1604-7-1-AB.p65  
3
5/16/00, 10:50 AM  
 
RTD INPUT  
LINEAR INPUT  
mA,  
mV  
or  
10  
RTD  
RTD  
+
_
V
9
Shield  
+
10  
9
mA  
mV  
or  
8
9
10  
8
9
10  
_
V
Fig. 5 RTD INPUT WIRING  
G
NOTE:  
1) Don’t run input wires together with power  
cables.  
Fig. 6 mA, mV AND V INPUTS WIRING  
2) Pay attention to the line resistance; a high line  
resistance may cause measurement errors.  
3) When shielded cable is used, it should be  
grounded at one side only to avoid ground loop  
currents.  
NOTE:  
1) Don’t run input wires together with power  
cables.  
2) Pay attention to the line resistance; a high line  
resistance may cause measurement errors.  
3) When shielded cable is used, it should be  
grounded at one side only to avoid ground loop  
currents.  
4) The resistance of the 3 wires must be the  
same.  
4) The input impedance is equal to:  
< 5 W for 20 mA input  
> 1 MW for 60 mV input  
> 200 kW for 5 V input  
> 400 kW for 10 V input  
4
1604-7-1-AB.p65  
4
5/16/00, 10:50 AM  
 
B) LOGIC INPUT  
C) RELAY OUTPUTS  
Safety note:  
NO - OUT 2  
NO - OUT 3  
1) Do not run logic input wiring together with  
power cables.  
2) Use an external dry contact capable of  
switching 0.5 mA, 5 V DC.  
3) The instrument needs 100 ms to recognize a  
contact status variation.  
1
OUT 2  
OUT 3  
3
2
C - OUT 2 and 3  
4) The logic inputs are NOT isolated by the  
measuring input  
Fig. 8 RELAY OUTPUTS WIRING  
The contact rating of the OUT 2, 3 is 2A/250V AC  
on resistive load.  
SP / SP2  
14  
The number of operations is 1 x 105 at specified  
rating.  
15  
NOTES 1) To avoid electrical shock, connect  
power line at the end of the wiring  
procedure.  
2) ForpowerconnectionsuseNo16AWG  
or larger wires rated for at last 75 °C.  
3) Use copper conductors only.  
4) Don’t run input wires together with  
power cables.  
Fig. 7 - LOGIC INPUT WIRING  
This logic input allows to select the operative set  
point.  
The relay contacts are protected by varistor against  
inductive load with inductive component up to 0.5 A.  
logic input  
open  
op. set point  
SP  
close  
SP2  
The following recommendations avoid serious  
problems which may occur, when using relay  
output for driving inductive loads.  
5
1604-7-1-AB.p65  
5
5/16/00, 10:50 AM  
 
INDUCTIVE LOADS  
LINEAR OUTPUT  
High voltage transients may occur switching  
This instrument is equipped with one linear output  
inductive loads.  
(OUT 1) programmable as:  
Through the internal contacts these transients  
may introduce disturbances which can affect the  
performance of the instrument.  
For the OUT 2 and OUT 3, the internal protection  
(varistor) assures a correct protection up to 0.5 A  
of inductive component.  
- main output (heating or cooling)  
- secondary output (cooling)  
- analog retransmission of the measured value  
- analog retransmission of the operative set point.  
+
+
_
6
7
The same problem may occur when a switch is  
used in series with the internal contacts as shown  
in Fig. 9.  
OUT 1  
_
C
R
POWER  
LINE  
Fig. 10 mA OUTPUT WIRING  
LOAD  
It is an isolated analog output.  
Fig. 9 EXTERNAL SWITCH IN SERIES WITH  
THE INTERNAL CONTACT  
Maximum load: 500 W.  
In this case it is recommended to install an  
additional RC network across the external contact  
as show in Fig. 9  
The value of capacitor (C) and resistor (R) are  
shown in the following table.  
LOAD  
(mA)  
C
R
P.  
(W)  
OPERATING  
VOLTAGE  
(mF) (W)  
<40 mA 0.047 100  
<150 mA 0.1 22  
<0.5 0.33 47  
1/2  
2
2
260 V AC  
260 V AC  
260 V AC  
A
The cable involved in relay output wiring must be  
as far away as possible from input or communica-  
tion cables.  
6
1604-7-1-AB.p65  
6
5/16/00, 10:50 AM  
 
SERIAL INTERFACE  
D) POWER LINE WIRING  
RS-485 interface allows to connect up to 30  
devices with one remote master unit.  
N
4
POWER LINE 100 V to 240 V A.C  
I
(50/60Hz)  
or 24 V AC/DC  
A'/A  
B'/B  
A/A'  
B/B'  
N
S
T
R
U
M
E
N
T
11  
12  
13  
M
A
S
T
E
R
5
R (S,T)  
Fig. 12 POWER LINE WIRING  
COMMON  
NOTES:  
1) Before connecting the instrument to the power  
line, make sure that line voltage corresponds to  
the description on the identification label.  
2) To avoid electrical shock, connect power line at  
the end of the wiring procedure.  
3) For supply connections use No 16 AWG or larger  
wires rated for at last 75 °C.  
4) Use copper conductors only.  
5) Dont run input wires together with power cables.  
6) For24VDCthepolarityisadonotcarecondition.  
7) The power supply input is NOT fuse protected.  
Please, provide it externally.  
Fig. 11 - RS-485 WIRING  
The cable length must not exceed 1.5 km at 9600  
BAUD.  
NOTE: The following report describes the signal  
sense of the voltage appearing across the  
interconnection cable as defined by EIA for  
RS-485.  
a) The A terminal of the generator shall  
be negative with respect to the B ”  
terminal for a binary 1 (MARK or OFF)  
state.  
b) The A terminal of the generator shall  
be positive with respect to the B ”  
terminal for a binary 0 (SPACE or ON)  
state.  
Power supply  
24 V AC/DC  
100/240 V AC  
Type Current  
T
T
Voltage  
250 V  
250 V  
500 mA  
125 mA  
When fuse is damaged, it is advisable to verify  
the power supply circuit, so that it is necessary to  
send back the instrument to your supplier.  
8) The safety requirements for Permanently Con-  
nected Equipment say:  
- a switch or circuit-breaker shall be included in  
the building installation;  
- It shall be in close proximity to the equipment  
and within easy reach of the operator;  
- it shall be marked as the disconnecting device  
for the equipment.  
7
1604-7-1-AB.p65  
7
5/16/00, 10:50 AM  
 
NOTE:asingleswitchorcircuit-breakercandrive  
more than one instrument.  
9) When the NEUTRAL line is present, connect it  
to terminal 4.  
8
1604-7-1-AB.p65  
8
5/16/00, 10:50 AM  
 
OPEN INPUT CIRCUIT  
This instrument is able to identify the open circuit  
for TC and RTD inputs.  
The open input circuit condition for RTD input is  
shown by an "overrange" indication.  
For TC input, it is possible to select overrange  
indication (standard) or underrange indication set-  
ting the CH101 and SH101 according to the follow-  
ing table:  
PRELIMINARY HARDWARE  
SETTINGS  
1) Remove the instrument from its case.  
2) It is necessary to set J106 according to the  
desired input type as shown in the following figure.  
INPUT  
TYPE  
J106  
5-6  
1-2  
3-4  
7-8  
9-10  
open  
open  
open  
open  
close  
Overrange (STD) CH101 = close SH101 = open  
TC-RTD open close open open  
Underrange  
CH101 = open SH101 = close  
60 mV  
5 V  
open close open open  
close open close open  
open open close open  
open open open close  
Both pads are located on the soldering side of the  
CPU card  
10 V  
20 mA  
NOTE : the not used jumper can be positioned on  
pin 7-9  
CH101  
SH101  
Fig. 14  
2
1
4
3
6
5
8
7
10  
9
V101  
J106  
Fig. 13  
9
1604-7-1-AB.p65  
9
5/16/00, 10:50 AM  
 
SEr3 = Baude rate for serial link  
Not available when SEr1 = OFF  
From 600 to 19200 baud.  
GENERAL NOTES for configuration.  
FUNC = This will memorize the new value of  
the selected parameter and go to the  
next parameter (increasing order).  
NOTE: 19200 baud is shown on display as 19.2.  
MAN  
=
This will scroll back the parameters  
without memorization of the new value.  
This will increase the value of the  
selected parameter  
s
=
SEr4 = Byte format for serial link  
Not available when SEr1 = OFF  
7E = 7 bits + even parity (For ERO protocol only)  
7O = 7 bits + odd parity (For ERO protocol only)  
8E = 8 bits + even parity  
t
=
This will decrease the value of the  
selected parameter.  
8O = 8 bits + odd parity  
CONFIGURATION PROCEDURE  
1) Remove the instrument from its case.  
2) Set the dip switch V101to the open condition  
(see fig. 13).  
3) Re-insert the instrument.  
4) Switch on the instrument.  
8
= 8 bits no parity  
P1 - Input type and standard range  
0
1
2
3
4
5
6
7
8
9
= TC type  
= TC type  
= TC type  
= TC type  
= TC type  
= TC type  
= TC Type  
= TC type  
= TC type  
= TC type  
L
L
J
J
K
K
T
N
R
S
range  
range  
0 / +400.0 °C  
0 / +900 °C  
The display will show COnF.  
range-100.0 / +400.0 °C  
range -100 / +1000 °C  
range-100.0 / +400.0 °C  
range -100 / +1370 °C  
range-199.9 / +400.0 °C  
range -100 / +1400 °C  
NOTE : If "CAL" indication is displayed, press  
immediately the s pushbutton and return to  
the configuration procedure.  
5) Push the FUNC pushbutton.  
range  
range  
0 / +1760 °C  
0 / +1760 °C  
SEr1 = Serial interface protocol  
OFF = No serial interface  
10 = RTD type Pt 100 range-199.9 / +400.0 °C  
11 = RTD type Pt 100 range -200 / +800 °C  
Ero  
= Polling/selecting ERO  
nbUS = Modbus  
jbUS = Jbus  
12 = mV  
13 = mV  
14 = mA  
15 = mA  
16 = V  
17 = V  
18 = V  
19 = V  
Linear range  
Linear range  
Linear range  
Linear range  
Linear range  
Linear range  
Linear range  
Linear range  
0 /  
12 /  
0 /  
4 /  
0 /  
1 /  
0 /  
2 /  
60 mV  
60 mV  
20 mA  
20 mA  
5 V  
5 V  
10 V  
10 V  
SEr2 = Serial link device address  
Not available when SEr1 = OFF  
From 1 to 95 for ERO protocol.  
From 1 to 255 for all the other protocols.  
NOTE: the electrical characteristic of the RS 485  
serial interface allows you the connection of 31  
devices maximum.  
20 = TC type  
L
range  
0 / +1650 °F  
10  
1604-7-1-AB.p65  
10  
5/16/00, 10:50 AM  
 
21 = TC type  
22 = TC type  
23 = TC type  
24 = TC type  
25 = TC type  
26 = TC type  
J
range -150 / +1830 °F  
range -150 / +2500 °F  
range -330 / +750 °F  
range -150 / +2550 °F  
the input range.  
When this parameter is modified, rH parameter  
will be re-aligned to it.  
The initial and full scale values determine the  
input span which is used by the PID algorithm,  
the SMART and the alarm functions.  
K
T
N
R
S
range  
range  
0 / +3200 °F  
0 / +3200 °F  
27 = RTD type Pt 100 range-199.9 / +400.0 °F  
28 = RTD type Pt 100 range -330 / +1470 °F  
NOTE: selecting P1 = 0, 2, 4, 6, 10 or 27, the  
instrument set automatically P39 = P40 = FLtr.  
For all the remaining ranges it will set P39 = P40  
= nOFL.  
NOTE: the minimum input span (S = P4 - P3), in  
absolute value, should be set as follows:  
For linear inputs, S > 100 units.  
For TC input with °C readout, S > 300 °C.  
For TC input with °F readout, S > 550 °F.  
For RTD input with °C readout, S > 100 °C.  
For RTD input with °F readout, S > 200 °F.  
If a different selection is desired, P39 and P40  
may be modified, after executed P1 configuration.  
P2 = Decimal point position  
This parameter is available only when a linear  
input is selected (P1 = 12, 13, 14, 15, 16, 17, 18  
or 19).  
P5 = Output 1 function  
rEv = Out 1 is used as control output with  
reverse action  
dir = Out 1 is used as control output with direct  
action  
Pv.rt = Out 1 is used as analog retransmission of  
the measured value (process variable)  
SP.rt = Out 1 is used as analog retransmission of  
the operative set point.  
----.  
---.-= No decimal figure.  
--.--= One decimal figure.  
-.---= Two decimal figures.  
= Three decimal figures.  
P3 = Initial scale value  
For linear inputs it is programmable from -1999 to  
4000.  
REVERSE ACTION  
Input  
DIRECT ACTION  
Input  
For TC and RTD input, it is programmable within  
the input range.  
When this parameter is modified, rL parameter  
will be re-aligned to it.  
t
t
t
Output  
Output  
t
P4 = Full scale value  
For linear inputs it is programmable from -1999 to  
4000.  
P6 = Output 1 type.  
0-20 = output type 0 - 20 mA.  
4-20 = output type 4 - 20 mA.  
For TC and RTD input it is programmable within  
11  
1604-7-1-AB.p65  
11  
5/16/00, 10:50 AM  
 
P7 = analog retransmission - initial scale  
value.  
L.A. = Low alarm (inside for band alarm) with  
automatic reset (latched).  
Available only when P5 = Pv.rt or SP.rt.  
It is programmable from -1999 to 4000.  
The decimal point will be positioned as selected  
with P2 parameter.  
H.L. = High alarm (outside band) with manual re-  
set (latched).  
L.L. = Low alarm (inside band) with manual reset  
(latched).  
P8 = analog retransmission - full scale value.  
Available only when P5 = Pv.rt or SP.rt.  
It is programmable from -1999 to 4000.  
The decimal point will be positioned as selected  
with P2 parameter.  
P11 = Output 3 function  
nonE = output not used.  
rEv = Out 3 is used as control output with  
reverse action.  
dir  
= Out 3 is used as control output with direct  
action.  
P9 = Output 2 function.  
nonE = output not used.  
rEv = Out 2 is used as control output with  
reverse action.  
AL2.P =it is used as Alarm 2 output and the alarm  
2 is programmed as process alarm.  
AL2.b =it is used as Alarm 2 output and the alarm  
2 is programmed as band alarm.  
AL2.d =it is used as Alarm 2 output and the alarm  
2 is programmed as deviation alarm.  
NOTES: 1) If P11 has been changed to "rEv", the  
cycle time (Cy3) will be forced to 15  
seconds.  
dir  
= Out 2 is used as control output with direct  
action.  
AL1.P =it is used as Alarm 1 output and the  
alarm 1 is programmed as process alarm.  
AL1.b =it is used as Alarm 1 output and the  
alarm 1 is programmed as band alarm.  
AL1.d =it is used as Alarm 1 output and the  
alarm1 is programmed as deviation alarm.  
NOTE: If P9 has been changed to "rEv", the  
cycle time (Cy2) will be forced to 15  
seconds.  
If P11 has been changed to "dir", the  
cycle time (Cy3) will be forced to:  
10 s when P22 is equal to "AIr"  
4 s when P22 is equal to "OIL"  
2 s when P22 is equal to "H2O".  
If P9 has been changed to "dir", the cycle  
time (Cy2) will be forced to:  
2) The relations among P5, P9 and P11  
are shown by the following notes:  
10 s when P22 is equal to "AIr"  
4 s when P22 is equal to "OIL"  
2 s when P22 is equal to "H2O".  
-
-
-
one Out only can be configured as  
"rEv" output.  
one Out only can be configured as  
"dir" output.  
if no Output is configured as control  
output the instrument will operate as  
an indicator.  
P10 = Alarm 1 operating mode  
Available only when P9 is equal to "AL1.P",  
"AL1.b" or "AL1.d".  
H.A. = High alarm (outside for band alarm) with  
automatic reset (latched).  
12  
1604-7-1-AB.p65  
12  
5/16/00, 10:50 AM  
 
P12 = Alarm 2 operating mode  
Available only when P11 is equal to "AL2.P",  
"AL2.b" or "AL2.d".  
H.A. = High alarm (outside for band alarm) with  
automatic reset (latched).  
P16 = Threshold of the “Soft Start” function.  
Threshold value in eng. units to initiate the "Soft  
start" function (output power limiting) at start up.  
Range : within the readout span.  
NOTE: This threshold value will not be taken into  
account when tOL = InF.  
L.A. = Low alarm (inside for band alarm) with  
automatic reset (latched).  
H.L. = High alarm (outside band) with manual reset  
(latched).  
P17 = Safety lock  
L.L. = low alarm (inside band) with manual reset  
(latched).  
0 = No parameter protection. The device is  
always in unlock condition and all parameters  
can be modified.  
1 = The device is always in lock condition and no  
one of the parameters (exception made for  
set points [SP, SP2] and manual reset of the  
alarms) can be modified (for SMART status  
see P30 parameter).  
P13 = Programmability of the alarm 2  
threshold and hysteresis values  
Available only when P11 is equal to "AL2.P",  
"AL2.b" or "AL2.d".  
OPrt = Alarm 2 threshold and hysteresis are  
programmable in the operating mode.  
COnF = Alarm 2 threshold and hysteresis are  
programmable in configuration mode.  
From 2 to 4999 = This combination number is a  
secret value to be used, in run time (see nnn  
parameter) to put the device in lock/unlock  
condition.  
For SP, SP2 and manual reset of the alarms,  
the lock/unlock condition has no effect (for  
SMART status see P30).  
P14 = Alarm 2 threshold value  
Available only when P11 is equal to "AL2.P",  
"AL2.b" or "AL2.d" and P13 is equal to "COnF".  
Range: For process alarm - within the range  
limits.  
From 5000 to 9999 = This combination number is  
a secret value to be used, in run time (see  
nnn parameter) to put the device in lock/  
unlock condition.  
For SP, SP2, manual reset of the alarm, AL1,  
AL2, the lock/unlock condition has no effect  
(for SMART status see P30).  
For band alarm - from 0 to 500 units.  
For deviation alarm - from -500 to 500  
units.  
NOTE:when safety lock is selected, the secret  
value can not be displayed again and the  
display will show 0, 1, SFt.A (when P17 is  
encompassed between 2 and 4999) or SFt.b  
(when P17 is encompassed between 5000  
and 9999)  
P15 = Alarm 2 hysteresis value  
Available only when P11 is equal to "AL2.P",  
"AL2.b" or "AL2.d" and P13 is equal to "COnF".  
Range: from 0.1% to 10.0 % of the range selected  
with P3 and P4 parameters, or 1 LSD.  
13  
1604-7-1-AB.p65  
13  
5/16/00, 10:50 AM  
 
The configuration procedure is completed and the  
P21 = Displayed value of the power output  
for the secondary control output  
This parameter is available only when two control  
outputs are configured.  
nOrL = the displayed value is equal to the result  
of PID calculation.  
CnPL = the displayed value is complemented  
(100 - PID calculation).  
NOTE: when two control outputs are configured, the  
P18 and P19 selections are applied to the "rEv"  
control output while P20 and P21 selections are  
applied to the "dir" control output.  
instrument shows "  
displays.  
-.-.-.-.  
" on both  
If no other setting is necessary, push the FUNC  
pushbutton, the display returns to show "COnF".  
Otherwise access to the advanced configuration  
parameter proceeding as follows:  
1) using s and t pushbuttons to set the 262  
code on the display.  
2) push the FUNC pushbutton.  
P18 = Main control output action  
This parameter is skipped if none of the outputs is  
configured as control output.  
P22 = Cooling media.  
Available only when the device is configured with  
two control outputs.  
nOrL = the power output is equal to the result of  
PID calculation.  
AIr = Air is used as cooling media.  
CnPL = the power output is complemented (100 -  
PID calculation).  
OIL = Oil is used as cooling media.  
H2O = Direct water is used as cooling media.  
Changing P22 parameter, the instrument forces  
the cycle time and relative cooling gain param-  
eters to the default value related with the chosen  
cooling media  
P19 = Displayed value of the main power  
output  
This parameter is skipped if none of the outputs is  
When P22 = AIr - Cyx = 10 s and rC = 1.00  
P22 = OIL - Cyx = 4 s and rC = 0.80  
P22 = H2O - Cyx = 2 and rC = 0.40  
Where Cyx is the cycle time(Cy2 or Cy3) of the  
out programmed as "dir" control output.  
configured as control output.  
nOrL = the displayed value is equal to the result  
of PID calculation.  
CnPL = the displayed value is complemented  
(100 - PID calculation).  
P20 = Secondary control output action  
This parameter is available only when two control  
outputs are configured.  
nOrL = the power output is equal to the result of  
PID calculation.  
P23 = Relative cooling gain calculated by  
SMART function.  
Available only when device is configured with two  
control outputs.  
OFF = SMART algorithm does not calculate the  
rC parameter value  
On = SMART algorithm calculates the rC  
parameter value.  
CnPL = the power output is complemented (100 -  
PID calculation).  
14  
1604-7-1-AB.p65  
14  
5/16/00, 10:50 AM  
 
P24 = Alarm 1 action  
NOTE: for more details to stand-by (mask) function,  
Available only when P9 = "AL1.P", "AL1.d" or  
see P25 parameter.  
"AL1.b".  
dir = direct action (relay energized in alarm condi-  
tion)  
P28 = OFFSET adjustment added to the  
measured value  
This parameter allows to set a constant OFFSET  
throughout the readout range.  
rEV = reverse action (relay de-energized in alarm  
condition)  
P25 = alarm 1 stand-by (mask) function  
Available only when P9 = "AL1.P", "AL1.d" or  
"AL1.b".  
It is skipped for linear inputs  
-
For readout ranges with decimal figure, P28 is  
programmable from -19.9 to 19.9.  
OFF = stand-by (mask) function disabled  
On = stand-by (mask) function enabled  
NOTE: If the alarm is programmed as band or  
deviation alarm, this function masks the alarm  
condition after a set point change or at the  
instrument start-up until the process variable  
reaches the alarm threshold plus or minus  
hysteresis. If the alarm is programmed as a  
process alarm, this function masks the alarm  
condition at instrument start-up until the process  
variable reaches the alarm threshold plus or  
minus hysteresis.  
-
For readout ranges without decimal figure, P28  
is programmable from -199 to 199.  
Readout  
Real curve  
P28  
Adjusted  
curve  
Input  
P29 = Displayable protected parameters  
This parameter is skipped when P17 = 0.  
OFF = Protected parameters cannot be displayed.  
On = Protected parameter can be displayed.  
P26 = Alarm 2 action  
Available only when P11 = "AL2.P", "AL2.d" or  
"AL2.b".  
dir = direct action (relay energized in alarm  
condition)  
rEV = reverse action (relay de-energized in alarm  
condition)  
P30 = SMART function  
This parameter is skipped when none of the  
outputs is programmed as control output.  
0 = SMART function disabled.  
1 = SMART function is NOT protected by safety  
lock.  
P27 = Alarm 2 stand-by (mask) function  
Available only when P11 ="AL2.P", "AL2.d" or  
"AL2.b".  
OFF = Stand-by (mask) function disabled  
On = Stand-by (mask)function enabled  
2 = SMART function is under safety lock protection.  
15  
1604-7-1-AB.p65  
15  
5/16/00, 10:50 AM  
 
P31 = Maximum value of the proportional band  
calculated by the SMART algorithm.  
This parameter is skipped when none of the  
outputs is programmed as control output or  
P30=0.  
2 = the instrument starts in the same way it was  
left prior to power shut down but if the  
instrument was in manual mode, it will restart  
with a power output equal to 0.  
3 = the instrument starts in the same way it was  
left prior to power shut down but if the  
instrument was in manual mode, it will restart  
with the same power output it had prior to  
power shut down.  
This parameter is programmable from P32 value  
to 200.0 %.  
P32 = Minimum value of the proportional band  
calculated by the SMART algorithm.  
This parameter is skipped when none of the outputs  
is programmed as control output or P30=0.  
It is programmable from 1.0% to P31 value.  
P36 = Timeout selection  
This parameter allows to set the time duration of  
the timeout for parameter setting used by the  
instrument during the operating mode.  
tn. 10 = 10 seconds  
tn. 30 = 30 seconds  
P33 = Minimum value of the integral time  
calculated by the SMART algorithm.  
This parameter is skipped when none of the  
outputs is programmed as control output or  
P30=0.  
P37 = Conditions for output safety value  
This parameter is skipped when none of the  
outputs is programmed as control output.  
0 = No safety value (see "Error Messages")  
1 = Safety value is applied when overrange or  
underrange condition is detected.  
It is programmable from 00.01[mm.ss] to 02.00  
[mm.ss].  
2 = Safety value is applied when overrange  
condition is detected.  
P34 = MANUAL function  
3 = Safety value is applied when underrange  
condition is detected.  
This parameter is skipped when none of the  
outputs is programmed as control output.  
OFF = manual function is disabled  
On = manual function can be enabled/  
disabled by MAN pushbutton.  
P38 = Output safety value  
This parameter is skipped when none of the  
outputs is programmed as control output or  
P37 = 0.  
P35 = Device status at instrument start up.  
This parameter is skipped when none of the outputs  
is programmed as control output or P34=OFF.  
0 = the instrument starts in AUTO mode.  
1 = the instrument starts in MANUAL mode with  
power output set to 0.  
This value can be set  
-
from 0.0 to 100.0 % when the device is  
configured with one control output only.  
from -100.0 % to 100.0 % when the device is  
configured with two control outputs.  
-
16  
1604-7-1-AB.p65  
16  
5/16/00, 10:50 AM  
 
NOTE: when the instrument detects an out of  
range condition, it assignes the P38 value to  
the PID output but P18 and P20 parameter are  
still active.  
negative value decreases the low limit of the anti-  
reset-wind up (under set point).  
P43 = Set point indication  
Fn.SP = during operative mode, when the  
instrument performs a ramp, it will show  
the final set point value.  
OP.SP =during operative mode, when the  
instrument performs a ramp, it will show  
the operative set point.  
P39 = Digital filter on the displayed value  
It is possible to apply to the displayed value a  
digital filter of the first order with a time constant  
equal to :  
- 4 s for TC and RTD inputs  
- 2 s for linear inputs  
nOFL. = no filter  
FLtr = filter enabled  
P44 = Operative set point alignment at  
instrument start up  
0 = At start up, the operative set point will be  
aligned to SP or SP2 according to the digital  
input status.  
1 = At start up, the operative set point will be  
aligned to the measured value, the selected  
set point value will be reached by the  
programmed ramp (see Grd1 and Grd2  
operative parameters).  
P40 = Digital filter on the retransmitted value  
This parameter is available only if P5 = PV.rt.  
It is possible to apply to the retransmitted value a  
digital filter of the first order with a time constant  
equal to :  
- 4 s for TC and RTD inputs  
- 2 s for linear inputs  
NOTE: if the instrument detects an out of range  
or an error condition on the measured value it will  
ever operate as described for P44 = 0.  
nOFL. = no filter  
FLtr = filter enabled  
P41 = Control action type  
This parameter is skipped when none of the  
outputs is programmed as control output.  
Pid. = The process is controlled by PID action.  
Pi. = The process is controlled by PI action.  
The configuration procedure is terminated and the  
display returns to show "COnF".  
P42 = Extension of the anti-reset-wind up  
Range: from -30 to +30 % of the proportional  
band.  
NOTE: a positive value increases the high limit of  
the anti-reset-wind up (over set point) while a  
17  
1604-7-1-AB.p65  
17  
5/16/00, 10:50 AM  
 
When return in "Normal Display Mode" is desired,  
push FUNC push-button again.  
OPERATIVE MODE  
1) Remove the instrument from its case.  
2) Set the internal dip switch V101 in closed condi-  
tion  
INDICATORS  
3) Re-insert the instrument.  
4) Switch on the instrument.  
°C  
Lit when the process variable is shown in  
Celsius degrees.  
°F  
Lit when the process variable is shown in  
Fahrenheit degrees.  
DISPLAY FUNCTION  
The upper display shows the measured value  
while the lower display shows the programmed  
set point value (we define the above condition as  
normal display mode).  
NOTE : When the rate of change (Grd1, Grd2) is  
utilized, the displayed set point value may  
be different from the operating set point.  
It is possible to change the information on the  
lower display as follows:  
SMRT Flashing when the first part of the SMART  
algorithm is active.  
Lit when the second part of the SMART  
algorithm is active.  
OUT1 It will flash with a duty cycle proportional  
to the linear output value.  
OUT2 Lit when OUT 2 is ON or alarm 1 is in the  
alarm state.  
OUT3 Lit when OUT 3 is ON or alarm 2 is in the  
alarm state  
- Push FUNC pushbutton for more than 3  
seconds but less than 10 seconds.  
The lower display will show " r. " followed by  
the power value of the OUT programmed as  
"rEV" control output (from 0.0 to 100.0%*).  
- Push FUNC pushbutton again. The lower display  
will show "d." followed by the power value of the  
OUT programmed as "dir" control output (from  
0.0 to 100.0%*).  
Other functions are shown by decimal points:  
REM  
* The graphic symbol "  
.
" means 100%.  
- Push FUNC pushbutton again. The display will  
return in "Normal Display Mode".  
NOTE : The two power outputs are displayed only if  
therelativefunctionhasbeenpreviouslyconfigured.  
SP2  
MAN  
REM = Flashing, when the instrument is  
controlled via serial link.  
SP2 = Flashing at slow rate when SP2 is used.  
Flashing at fast rate when a set point from  
serial link is used.  
When no pushbutton is pressed during the time  
out (see P36), the display will automatically return  
in "Normal Display Mode".  
In order to keep the desired information  
continuously on the lower display, depress s or  
t push-button to remove the timeout.  
MAN= Flashing at slow rate, when the instrument  
is in MANUAL mode.  
18  
1604-7-1-AB.p65  
18  
5/16/00, 10:50 AM  
 
Pushbuttonfunctionalityduringoperatingmode.  
FUNC = o when the instrument is in "normal  
display mode"  
NOTE: a 10 or 30 seconds time out (see P 36)  
can be selected for parameter modification during  
run time mode.  
1)with a brief pressure (<3s) it starts  
the parameter modification  
procedure.  
If, during operative parameter modification, no  
pushbutton is pressed for more than 10 (30)  
seconds, the instrument goes automatically to the  
normal display modeand the eventual  
modification of the last parameter will be lost.  
2)with a pressure within 3s to 10s it  
changes the indication on the lower  
display (see "display function").  
3)with a pressure longer than 10s it  
enables the lamp test (see "Lamp  
Test" paragraph).  
o During parameter modification, it  
allows to memorize the new value of  
the selected parameter and go to the  
next parameter (increasing order).  
pressed for more than 1 s, it allows to  
enable or disable the manual function  
and, during parameter modification,  
to scroll back the parameters without  
memorizing the new setting.  
ENABLE/DISABLE THE CONTROL OUTPUT  
When the instrument is in "normal display mode",  
by keeping depressed for more than 5 s s and  
FUNC pushbuttons, it is possible to disable the  
control outputs. In this open loop mode the device  
will function as an indicator, the lower display will  
show the word OFF and all control outputs will  
also be in the OFF state (the output is also  
conditioned by P18 and P20 parameters).  
When the control outputs are disabled the alarms  
are also in non alarm condition.  
MAN  
s
=
The alarms output conditions depend on the  
alarm action type (see P24-P26).  
Depress for more than 5 s s and FUNC  
pushbuttons to restore the control status.  
The alarm stand-by function, if configured, will be  
activated as if it was at power up.  
If a power down occures when the control output  
is disabled, at instrument power up the control  
output will be automatically disabled.  
=
o During parameter modification, it  
allows to increase the value of the  
selected parameter.  
o During MANUAL mode, it allows to  
increase the output value.  
o During parameter modification, it  
allows to decrease the value of the  
selected parameter.  
o During MANUAL mode, it allows to  
decrease the output value.  
t
=
s+MAN = During parameter modification they  
allow to jump to the maximum  
programmable value.  
t+MAN = During parameter modification they  
allow to jump to the minimum  
SP - SP2 SELECTION  
It is possible to select the operating set point (SP  
or SP2) only by an external contact (terminals 14  
and 15).  
By setting P43, it is possible to display the final or  
the operative set point during a ramp execution.  
programmable value.  
19  
1604-7-1-AB.p65  
19  
5/16/00, 10:50 AM  
 
DIRECT ACCESS TO SET POINT  
The transfer from AUTO to MANUAL and  
viceversa is bumpless (this function is not  
provided if integral action is excluded).  
If transfer from AUTO to MANUAL is performed  
during the first part of SMART algorithm (TUNE)  
when returning in AUTO the device will be forced  
automatically in the second part of the SMART  
algorithm (ADAPTIVE).  
At power up the device will be in the AUTO mode  
or as it was left prior to power shut down  
depending on P35 configuration selection.  
NOTE:When start up occurs in Manual mode with  
power output set to 0, the control outputs will be  
in accordance with the following formula: "rEV"  
output - "dir" output = 0  
When the device is in AUTO mode and in Normal  
Display Mode, it is possible to access directly to  
set point modification (SP or SP2).  
Pushing s or t for more than 2 s, the set point  
will begin changing.  
The new set point value becomes operative since  
no pushbutton has been depressed at the end of  
2 s timeout.  
MANUAL FUNCTION  
The MANUAL function can be accessed (only if  
enabled by P34=On) by depressing the MAN  
pushbutton for more than 1 sec.  
The command is accepted and executed only if  
the display is in "Normal Display Mode".  
When in MANUAL mode the LED's MAN  
annunciator will light up while the lower display  
shows the power output values.  
The value of "rEV" is shown in the two most signifi-  
cant digit field while the value of "dir" (if present) is  
shown in the two less significant digit field.  
The decimal point between the two values will be  
flashing to indicate instrument in manual mode.  
NOTE :  
LAMP TEST  
When it is desired to verify the display efficiency,  
push FUNC pushbutton for more than 10 s. The  
instrument will turn ON, with a 50 % duty cycle,  
all the LEDs of the display (we define this function  
"LAMP TEST").  
No time out is applied to the LAMP TEST.  
When it is desired to come back to the normal  
display mode, push FUNC pushbutton again.  
During the LAMP TEST the instrument continues  
to control the process but no keyboard functions  
are available (exception made for the FUNC  
pushbutton).  
- A graphic symbol "  
- A graphic symbol "  
" is used for "rEV"= 100  
" is used for "dir"= 100  
The power output can be modified by using s  
and t pushbuttons.  
Inmanualmodetheoutputresolutionisequalto1%.  
By depressing, for more than 1 second, MAN  
pushbutton the device returns in AUTO mode.  
20  
1604-7-1-AB.p65  
20  
5/16/00, 10:50 AM  
 
SERIAL LINK  
The device can be connected to a host computer  
by a serial link.  
SMART function  
It is used to optimize automatically the control  
action.  
The host can put the device in LOCAL (functions  
and parameters are controlled via keyboard) or in  
REMOTE (functions and parameters are  
controlled via serial link).  
To enable the SMART function, push the FUNC  
pushbutton until "Snrt" parameter is shown.  
Pushing s or t set the display "On" and push  
the FUNC pushbutton.  
The REMOTE status is signalled by the decimal  
point (labelled REM) at the right hand of the LSD  
of the upper display.  
This instrument allows to modify the operative  
and configuration parameters, via serial link.  
The necessary conditions to implement this  
function are the following:  
1) Serial parameters from SEr1 to SEr4 should be  
properly configured using the standard front  
keyboard procedure  
The SMRT LED will turn on or flashing according  
to the algorithm selected.  
When the smart function is enabled, it is possible to  
display but not to modify the control parameters.  
To disable the SMART function, push the FUNC  
pushbutton again until "Snrt" parameter is shown.  
Pushing s or t set the display "OFF" and  
push the FUNC pushbutton.  
The SMRT LED will turn off.  
2) Device must be in the OPERATING mode  
The instrument maintains the actual set of control  
parameters and it enables parameter modifica-  
tion.  
NOTES : 1) When ON/OFF control is pro-  
grammed (Pb=0), the SMART  
During the downloading of configuration the  
device goes in open loop with all output in OFF  
state.  
At the end of configuration procedure, the device  
performs an automatic reset and then returns to  
close loop control.  
function is disabled.  
2) The SMART enabling/disabling can  
be protected by safety key (see  
P30).  
21  
1604-7-1-AB.p65  
21  
5/16/00, 10:50 AM  
 
When it is desired to switch from LOCK  
to UNLOCK condition, set a value equal  
to P17 parameter.  
When it is desired to switch from  
UNLOCK to LOCK condition, set a value  
different from P17 parameter.  
Alarm 1 threshold  
OPERATIVE PARAMETERS  
Push the FUNC pushbutton, the lower display will  
show the code while the upper display will show  
the value or the status (On or OFF) of the  
selected parameter.  
By s or t pushbutton it is possible to set the  
desired value or the desired status.  
AL1  
This parameter is available only if P 9 is  
equal to AL1.P, AL1.b or AL1.d.  
Ranges:  
Pushing the FUNC pushbutton, the instrument  
memorizes the new value (or the new status) and  
goes to the next parameter.  
- Span limits for process alarm.  
- From 0 to 500 units for band alarm.  
- From -500 to 500 units for deviation  
alarm.  
Some of the following parameter may be skipped  
according to the instrument configuration.  
Param. DESCRIPTION  
HSA1 Alarm 1 hysteresis  
This parameter is available only if P 9 is  
SP  
Set point (in eng. units).  
equal to AL1.P, AL1.b or AL1.d.  
Range:From 0.1% to 10.0% of the input  
span or 1 LSD.  
Range: from rL to rH.  
SP is operative when the logic input is  
open.  
Note: If the hysteresis of a band alarm is  
larger than the alarm band, the instrument  
will use an hysteresis value equal to the  
programmed band minus 1 digit.  
Alarm 2 threshold  
This parameter is available only if P 11  
is equal to AL2.P, AL2.b or AL2.d and  
P13 = OPrt.  
Snrt  
SMART status.  
The On or OFF indication shows the  
actual status of the SMART function  
(enabled or disabled respectively).  
Set On to enable the SMART function.  
Set OFF to disable the SMART function.  
Manual reset of the alarms.  
This parameter is skipped if none of the  
alarms has the manual reset function.  
SetOnandpushFUNCtoresetthealarms.  
Set point 2 (in eng. units).  
Range: from rL to rH.  
SP2 is operative when the logic input is  
closed.  
Software key for parameter  
protection.  
This parameter is skipped if P17 = 0 or 1  
On = the instrument is in LOCK condition  
OFF = the instrument is in UNLOCK  
condition  
AL2  
n.rSt  
SP2  
nnn  
For other details see AL1parameter.  
HSA2 Alarm 2 hysteresis  
This parameter is available only if P 11  
is equal to AL2.P, AL2.b or AL2.d and  
P13 = OPrt.  
For other details see HSA1parameter.  
Proportional band  
Range: from 1.0% to 200.0% of the input  
span.  
Pb  
When Pb parameter is set to 0, the  
control action becomes ON-OFF.  
22  
1604-7-1-AB.p65  
22  
5/16/00, 10:50 AM  
 
Note:When device is working with  
SMART algorithm the Pb value will be  
limited by P31 and P32 parameters.  
Hysteresis for ON/OFF control action  
This parameter is available only when  
Pb=0.  
Range: from 0.1% to 10.0% of the input  
span.  
Integral time  
Cy3  
rC  
Output 3 cycle time  
This parameter is available only if P11 is  
equal to rEv or dir.  
Range:From 1 to 200 s.  
HyS  
ti  
Relative Cooling gain.  
This parameter is available only when  
device is configured with two control  
outputs and Pb is different from zero or  
device is in manual mode.  
This parameter is skipped if Pb=0 (ON/  
Range: from 0.20 to 1.00  
OFF action).  
Note: When the device is working with  
SMART algorithm and P23 is set to On  
the RCG value is limited in accordance  
with the selected type of cooling media:  
- from 0.85 to 1.00 when P22 = AIr  
- from 0.80 to 0.90 when P22 = OIL  
- from 0.30 to 0.60 when P22 = H2O  
Range: from 00.01 to 20.00 [mm.ss].  
Above this value the display blanks and  
integral action is excluded.  
Note: When the device is working with  
SMART algorithm, the minimum value of  
the integral time will be limited by P33  
parameter.  
OLAP Dead band/Overlap between H/C  
outputs.  
td  
Derivative time  
This parameter is skipped if Pb=0 (ON/  
OFF action) or P41 = Pi.  
This parameter is available only when  
device id configured with two control  
outputs and Pb is different from zero or  
device is in manual mode.  
Range: from -20 to 50 % of the  
proportional band.  
A negative OLAP value shows a dead  
band while a positive value shows an  
overlap.  
Range:From 00.00 to 10.00 mm.ss.  
Notes: When device is working with  
SMART algorithm the td value will be  
equal to a quarter of ti value.  
Integral pre-load  
IP  
Ranges:  
- from 0.0 to 100.0 % of the output span  
if device is configured for one control  
output.  
rL  
Set point low limit  
Range: from initial scale value (P3) to  
- from -100.0 to 100.0 % of the output  
span if device is configured for two  
control outputs.  
rH.  
Note: When P3 has been modified, rL  
will be realigned to it.  
Cy2  
Output 2 cycle time  
rH  
Set point high limit  
This parameter is available only if P9 is  
equal to rEv or dir.  
Range:From 1 to 200 s.  
Range:from rL to full scale value (P4).  
Note: When P4 has been modified, rH  
will be realigned to it.  
23  
1604-7-1-AB.p65  
23  
5/16/00, 10:50 AM  
 
Grd1  
Ramp applied to an increasing set  
point change  
Range: from 1 to 100 digits per minute.  
Above this value the display shows InF”  
meaning that the transfer will be done as  
a step change.  
Grd2  
OLH  
Ramp applied to a decreasing set  
point changes  
For other details see Grd1 parameter.  
Output high limit  
Range:  
- From 0.0 to 100.0 % of the output span  
when device is configured with one  
control output.  
- From -100.0 to 100.0% of the output  
span when device is configured with two  
control outputs.  
tOL  
rnP  
Time duration of the output power  
limiter (soft start)  
Range: from 1 to 540 min. Above this  
value the display shows InFmeaning  
that the limiting action is always on.  
Note: The tOL can be modified but the  
new value will become operative only at  
the next instrument start up.  
Control output max. rate of rise  
This parameter is available only when  
Pb is different from zero or one control  
output is a linear output type.  
Range: From 0.1 % to 25.0 % of the  
output span/second. Above this value  
the display shows InFmeaning that no  
limit is imposed.  
Note:the rnP parameter is active on a  
linear control output even if the device is  
in ON/OFF control mode.  
24  
1604-7-1-AB.p65  
24  
5/16/00, 10:50 AM  
 
When P37 is different from zero and an out of  
range condition is detected, the instrument  
operates in accordance with P37 and P38  
parameters.  
ERROR MESSAGES  
OVERRANGE, UNDERRANGE AND  
SENSOR LEADS BREAK INDICATIONS  
The device is capable to detect a fault on the  
process variable (OVERRANGE or  
UNDERRANGE or SENSOR LEADS BREAK).  
When the process variable exceeds the span  
limits established by configuration parameter P 1  
an OVERRANGE condition will be shown on  
display as show in the following figure:  
NOTE: in every cases, the P18 and P20  
parameters will conditioned the real outputs of the  
instrument.  
The sensor leads break can be signalled as:  
- for TC/mV input : OVERRANGE or  
UNDERRANGE selected by  
a solder jumper  
- for RTD input  
- for mA/V input  
:
:
OVERRANGE  
UNDERRANGE  
NOTE : For mA/V input the leads break can be  
detected only when the range selected has a zero  
elevation (4/20 mA or 1/5 V or 2/10 V)  
For RTD input a special test is provided to signal  
OVERRANGE when input resistance is less than  
15 ohm (Short circuit sensor detection).  
An UNDERRANGE condition will be shown on  
display as show in the following figure:  
ERROR MESSAGES  
The instrument performs same self-diagnostic  
algorithm.  
When an error is detected, the instrument shows  
on the lower display the Errindication while the  
upper display shows the code of the detected  
error.  
When P37 is equal to 0, the following conditions  
may occur:  
- The instrument is set for one output only and if  
an OVERRANGE is detected, the output turns  
OFF (if reverse action) or ON (if direct action).  
- The instrument is set for heating/cooling action  
and an OVERRANGE is detected, "rEV" output  
turns OFF and "dir" output turns ON.  
- The instrument is set for one output only and if  
an UNDERRANGE is detected, the output turns  
ON (if reverse action) or OFF (if direct action).  
- The instrument is set for heating/cooling action  
and an UNDERRANGE is detected, "rEV"  
output turns ON and "dir" output turns OFF.  
25  
1604-7-1-AB.p65  
25  
5/16/00, 10:50 AM  
 
ERROR LIST  
SEr  
100  
150  
200  
Serial interface parameter error.  
Write EEPROM error.  
CPU error.  
Tentative to write on protected  
memory.  
201 - 2xx  
Configuration parameter error. The  
two less significant digits shown the  
number of the wrong parameter (ex.  
209 Err shows an Error on P9  
parameter)  
299  
301  
307  
320  
Error on control output selection.  
Selected input calibration error  
RJ input calibration error  
Analog retransmission calibration  
error.  
400  
500  
502  
510  
Control parameters error  
Auto-zero error  
RJ error  
Error during calibration procedure.  
NOTES  
1) When a configuration parameter error is  
detected, it is sufficient to repeat the configura-  
tion procedure of the specified parameter.  
2) If error 400 is detected, push contemporarily  
the t and s pushbuttons for loading the  
default parameters then repeat control  
parameter setting.  
3) For all the other errors, contact your supplier.  
26  
1604-7-1-AB.p65  
26  
5/16/00, 10:50 AM  
 
EN 50081-2 and EN 50082-2) and to council  
directives 73/23/EEC and 93/68/EEC (reference  
harmonized standard EN 61010-1).  
Installation category: II  
Temperature drift: (CJ excluded)  
< 200 ppm/°C of span for mV and TC ranges 1, 3, 5,  
7, 20, 21, 22, 24.  
< 300 ppm/°C of span for mA/V  
< 400 ppm/°C of span for RTD range 11, 28 and  
TC range 0, 2, 4, 6, 23.  
GENERAL INFORMATIONS  
GENERAL SPECIFICATIONS  
Case: Polycarbonate grey dark color; self-extin-  
guishing degree: V-0 according to UL 94.  
Front protection - designed and tested for IP 65 (*)  
and NEMA 4X (*) for indoor locations (when panel  
gasket is installed).  
(*) Test were performed in accordance with CEI 70-  
1 and NEMA 250-1991 STD.  
Installation: panel mounting.  
Rear terminal block: 15 screw terminals ( screw  
M3, for cables from f 0.25 to f 2.5 mm2 or from  
AWG 22 to AWG 14 ) with connection diagrams  
and safety rear cover.  
Dimensions: DIN 43700 48 x 48 mm,  
depth 122 mm.  
< 500 ppm/°C of span for RTD range 10 and TC  
ranges 8, 9, 25, 26.  
< 800 ppm/°C of span for RTD range 27.  
Operative temperature: from 0 to 50 °C.  
Storage temperature : -20 to +70 °C  
Humidity: from 20 % to 85% RH, non condensing.  
Protections:  
1) WATCH DOG circuit for automatic restart.  
2) DIP SWITCH for protection against tampering  
of configuration and calibration parameters.  
Weight: 250 g.  
Power supply:  
- 100V to 240V AC 50/60Hz (-15% to + 10% of the  
nominal value).  
- 24 V AC/DC (+ 10 % of the nominal value).  
Power consumption: 6 VA max.  
Insulation resistance: > 100 MW according to  
IEC 1010-1.  
Dielectric strength: 1500 V rms according to IEC  
1010-1.  
Display updating time: 500 ms.  
Sampling time: 250 ms for linear inputs  
500 ms for TC and RTD inputs.  
Resolution: 30000 counts.  
Accuracy: + 0,2% f.s.v.. + 1 digit @ 25 °C  
ambient temperature.  
Common mode rejection: 120 dB @ 50/60 Hz.  
Normal mode rejection: 60 dB @ 50/60 Hz.  
Electromagnetic compatibility and safety  
requirements: This instrument is marked CE.  
Therefore, it is conforming to council directives  
89/336/EEC (reference harmonized standard  
INPUTS  
A) THERMOCOUPLE  
Type : L -J -K -N -R -S -T. °C/°F selectable.  
External resistance: 100 W max, maximum error  
0,1% of span.  
Burn out: It is shown as an overrange condition  
(standard). It is possible to obtain an underrange  
indication by cut and short.  
Cold junction: automatic compensation from 0 to  
50 °C.  
Cold junction accuracy : 0.1 °C/°C  
Input impedance: > 1 MW  
Calibration : according to IEC 584-1 and DIN  
43710 - 1977.  
27  
1604-7-1-AB.p65  
27  
5/16/00, 10:50 AM  
 
STANDARD RANGES TABLE  
C) LINEAR INPUTS  
Read-out: keyboard programmable between  
-1999 and +4000.  
Decimal point: programmable in any position.  
Burn out: the instrument shows the burn out condi-  
tion as an underrange condition for 4-20 mA, 1-5 V  
and 2-10 V input types.  
It shows the burn out condition as an underrange or  
an overrange condition (selectable by soldering  
jumper) for 0-60 mV and 12-60 mV input types. No  
indication are available for 0-20 mA, 0-5 V and 0-10  
V input types.  
T/C  
type  
Ranges  
L
L
J
0
1
0 /+ 400.0°C  
0 /+ 900 °C 20  
2 -100.0/ + 400.0°C  
-100 / + 1000 °C 21 -150 / + 1830 °F  
4 -100.0/ + 400.0°C ---  
-100 /+ 1370 °C 22 -150 / + 2500 °F  
6 -199.9/ + 400.0°C 23 -330 / + 750 °F  
---  
0 / + 1650 °F  
---  
J
3
K
K
T
N
R
S
5
7
8
9
-100 /+ 1400 °C 24 -150 / + 2550 °F  
Input type  
impedance  
0 /+ 1760 °C 25  
0 /+ 1760 °C 26  
0 / + 3200 °F  
0 / + 3200 °F  
Accuracy  
12  
13  
14  
15  
16  
17  
18  
19  
0 - 60 mV  
> 1 MW  
< 5 W  
12 - 60 mV  
0 - 20 mA  
4 - 20 mA  
0 - 5 V  
1 - 5 V  
0 - 10 V  
2 - 10 V  
B) RTD (Resistance Temperature Detector)  
Input: for RTD Pt 100 W, 3-wire connection.  
Input circuit: current injection.  
°C/°F selection: via front pushbuttons or serial link.  
Line resistance: automatic compensation up to  
20 W/wire with no measurable error.  
0.2 % + 1 digit  
@ 25°C  
> 200 kW  
> 400 kW  
Calibration: according to DIN 43760  
Burnout: up scale. NOTE: a special test is  
provided to signal OVERRANGE when input  
resistance is less than 15 W.  
D) LOGIC INPUT  
The instrument is equipped with one input from  
contact (voltage free) for setpoint selection.  
Contact open = Main setpoint.  
STANDARD RANGES TABLE  
Input  
Contact closed = Auxiliary setpoint.  
NOTES  
Ranges  
type  
1) Use an external contact with a contact rating  
better than 0.5 mA, 5 V DC.  
2) The instrument needs 100 ms to recognize a  
contact status variation.  
3) The logic inputs are NOT isolated by the  
measuring input.  
- 199,9 / + 400,0 °C  
- 200 / + 800 °C  
-199,9 / +400,0 °F  
-330 / + 1470 °F  
10  
11  
27  
28  
RTD Pt 100 W  
DIN 43760  
28  
1604-7-1-AB.p65  
28  
5/16/00, 10:50 AM  
 
SET POINTS  
This instrument allows to use 2 set points: SP and  
SP2.  
The set point selection is possible only by logic  
input.  
SMART: keyboard enabling/disabling  
Auto/Manual: selectable by front pushbutton.  
Auto/Manual transfer: bumpless method type  
Indicator "MAN" : OFF in auto mode and lit in  
manual mode.  
Set point transfer:  
The transfer between one set point to another (or  
between two different set point values) may be  
realized by a step transfer or by a ramp with two  
different programmable rate of change (ramp up  
and ramp down).  
OUTPUTS  
Type: This instrument is equipped with 3  
independent outputs programmable as follows:  
Slope value: 1 - 100 eng. unit/min or step.  
Set points limiter: RLO and RHI parameters, pro-  
grammable.  
Out 1  
linear (mA)  
Heating  
Out 2  
relay  
AL1  
Out 3  
relay  
AL2  
Heating  
Heating  
Cooling  
Cooling  
AL1  
AL1  
AL2  
Cooling  
AL2  
CONTROL ACTIONS  
Cooling  
Cooling  
Heating  
AL1  
Heating  
AL1  
Cooling  
AL1  
Heating  
Cooling  
AL1  
AL2  
Heating  
AL2  
Heating  
AL2  
Cooling  
Cooling  
Heating  
AL2  
Control action: PID + SMART  
Type: One (heating or cooling) or two (heating and  
cooling) control outputs.  
Proportional Band (Pb):  
Range: - from 1.0 to 100.0 % of the input span for  
process with one control output.  
Retransm.  
Retransm.  
Retransm.  
Retransm.  
Retransm.  
Retransm.  
Retransm.  
- from 1.5 to 100.0 % of the input span for  
process with two control outputs.  
When Pb=0, the control action becomes ON/OFF.  
Hysteresis (for ON/OFF control action):  
from 0.1% to 10.0% of the input span.  
Integral time (Ti): from 1s to 20 min. or excluded.  
Derivative time (Td): from 1 s to 10 min.  
If zero value is selected, the derivative action is  
excluded.  
Control output updating time :  
- 250 ms when a linear input is selected  
- 500 ms when a TC or RTD input is selected.  
Action: direct/reverse programmable by front  
keyboard.  
Output level indication:  
The instrument displays separately the output 1  
level (heating) and the output 2 level (cooling).  
Output status indication: the OUT 1 LED will  
flash with a duty cycle proportional to the output 1  
power. Two indicators (OUT 2 and/or OUT 3) are  
lit when the respective output is in ON condition.  
Integral pre-load:  
- from 0.0 to 100.0 % for one control output  
- from -100.0 (cooling) to +100.0 % (heating) for  
two control outputs.  
29  
1604-7-1-AB.p65  
29  
5/16/00, 10:50 AM  
 
Output level limiter:  
OUTPUT 3  
-
-
For one control medium: from 0 to 100 % .  
For two control mediums: from -100 to +100 %.  
Type: relay with SPST contact with rated current 2  
A at 250 V AC on resistive load.  
Function: programmable as:  
- control output (heating or cooling)  
- Alarm 2 output.  
This function may be operative at instrument start  
up for a programmable time (To avoid thermal  
shock and/or preheating the plant) otherwise it can  
be enabled by an external contact.  
Output cycle time (when used as control output)  
programmable from 1 s to 200 s.  
OUTPUT 1  
Type: optoisolated 0-20 mA or 4-20 mA  
programmable.  
Function: programmable as:  
- control output (heating or cooling)  
- retransm. of the measured value  
- retransm. of the operative set point.  
Scaling: programmable from -1999 to 9999.  
Maximum load: 500 W.  
ALARMS  
Actions: Direct or reverse acting.  
Alarm functions: each alarm can be configured  
as process alarm, band alarm or deviation alarm.  
Alarm reset: automatic or manual reset  
programmable on each alarm.  
Resolution:  
Stand by (mask) alarm: each alarm can be  
configured with or without stand by (mask)  
function.  
-
-
0.1 % when used as control output.  
0.05 % when used as analog retransmission.  
Digital filter: it is possible to enable a digital filter,  
on the output retransmission, with the same time  
constant chosen for the read-out.  
This function allows to delete false indication at  
instrument start up and/or after a set point change.  
Output level indication (as control output only):  
from 00.0 to 100.0 %.  
Output status indication: the indicator OUT 1  
flashes with a duty cycle proportional to the output  
level.  
Process alarm:  
Operative mode : High or low programmable.  
Threshold : programmable in engineering unit  
within the input span.  
Hysteresis: programmable from 0.1 % to 10.0 % of  
the input span (P4 - P3), or 1 LDS.  
OUTPUT 2  
Type: relay SPST contact (NO or NC selectable  
by jumper).  
Contact rated: 2 A at 250 V AC on resistive load.  
Function: programmable as:  
- control output (heating or cooling)  
- Alarm 1 output  
Band alarm:  
Operative mode: Inside or outside programmable.  
Threshold : programmable from 0 to 500 units.  
Hysteresis : programmable from 0.1 % to 10.0 % of  
the input span or 1 LDS.  
Output cycle time (when used as control output)  
programmable from 1 s to 99 s.  
Deviation alarm  
30  
1604-7-1-AB.p65  
30  
5/16/00, 10:50 AM  
 
Operative mode : High or low programmable.  
Threshold : programmable from - 500 to +500  
units.  
Hysteresis : programmable from 0.1 % to 10.0 % of  
the input span or 1 LDS.  
SUPPLY TERMINALS AND FROM RELAY  
OUTPUT TERMINALS  
2) Remove the instrument from case.  
3) Using a vacuum cleaner or a compressed air jet  
(max. 3 kg/cm2) remove all deposit of dust and  
dirt which may be present on the louvers and  
on the internal circuits trying to be careful for  
not damage the electronic components.  
4) To clean external plastic or rubber parts use  
only a cloth moistened with:  
SERIAL COMMUNICATION INTERFACE  
Type: RS-485  
Protocol type: MODBUS, JBUS, ERO polling/  
selecting.  
Baud rate: programmable from 600 to 19200  
BAUD.  
- Ethyl Alcohol (pure or denatured) [C2H5OH] or  
- Isopropil Alcohol (pure or denatured)  
[(CH3)2CHOH] or  
- Water (H2O)  
Byte format: 7 or 8 bit programmable.  
Parity: even, odd or none programmable.  
Stop bit : one.  
5) Verify that there are no loose terminals.  
6) Before re-inserting the instrument in its case, be  
sure that it is perfectly dry.  
Address :  
7) re-insert the instrument and turn it ON.  
-
from 1 to 95 for ERO protocol  
-
from 1 to 255 for all the other protocols  
Output voltage levels: according to EIA standard.  
MAINTENANCE  
1) REMOVE POWER FROM THE POWER  
31  
1604-7-1-AB.p65  
31  
5/16/00, 10:50 AM  
 
PARAMETER  
SP  
SnrT  
DEFAULT VALUE  
= Minimum range-value  
= Disabled  
APPENDIX A  
DEFAULT PARAMETERS  
n.Srt  
SP2  
nnn  
A1, A2  
= OFF  
= Minimum range value  
= OFF  
= Minimum range-value for  
process alarms  
0 for deviation or band alarms  
DEFAULT OPERATIVE PARAMETERS  
The control parameters can be loaded with  
predetermined default values. These data are the  
typical values loaded in the instrument prior to  
shipment from factory. To load the default values  
proceed as follows:  
HSA1, HSA2 = 0.1 %  
Pb  
HyS  
ti  
td  
IP  
= 4.0 %  
= 0.5 %  
a) The internal switch should be closed.  
b) The SMART function should be disabled.  
c) The upper display will show the process  
variable while the lower display will show the  
set point value.  
= 4.00 (4 minutes)  
= 1.00 (1 minute)  
= 30.0 for one control output  
0.0 for two control outputs  
= 15 seconds  
d) the device must be in "UNLOCK"  
and"LOCAL" conditions  
Cy2 - Cy3  
If two control outputs are  
configured and OUT2 (OUT 3) is  
configured as "dir", the default  
value will be equal to:  
10 seconds when P22 = AIr  
4 seconds when P22 = OIL  
2 seconds when P22 = H2O  
= 1.00 for P22 = AIr  
0.80 for P22 = OIL  
0.40 for P22 = H2O  
= 0  
e) Held down t pushbutton and press s  
pushbutton; the display will show:  
O F F  
d F L t  
e) Press s or t pushbutton; the display will show:  
rC  
O N  
OLAP  
rL  
rH  
d F L t  
= Initial scale value  
= Full scale value  
g) Press FUNC pushbutton; the display will show:  
Grd 1  
Grd 2  
OLH  
tOL  
= Infinite (step transfer)  
= Infinite (step transfer)  
= 100 %  
= Infinite  
= 25.0 % /s.  
L O A d  
This means that the loading procedure has been  
initiated. After about 3 seconds the loading  
procedure is terminated and the instrument  
reverts to NORMAL DISPLAY mode.  
rnP  
The following is a list of the default operative  
parame-ters loaded during the above procedure:  
Appendix A.1  
1604-7-A-AB.p65  
1
5/16/00, 10:50 AM  
 
This means that the loading procedure has been  
initiated. After about 3 seconds the loading  
procedure is terminated and the instrument  
reverts to visualization as in point b).  
DEFAULT CONFIGURATION PARAM-  
ETERS  
The configuration parameters can be loaded with  
predetermined default values. These data are the  
typical values loaded in the instrument prior to  
shipment from factory. To load the default values  
proceed as follows:  
a) The internal switch (V101, see fig. 13) should  
be open.  
b) The upper display will show:  
PARA.  
TABLE 1  
TABLE 2  
SEr 1  
SEr 2  
SEr 3  
SEr 4  
P1  
ErO  
1
19200  
7E  
ER0  
1
19200  
7E  
3
21  
C O n F  
c) Push the t pushbutton; the display will show  
P2  
P3  
----.  
0
----.  
0
P4  
P5  
P6  
P7  
400  
rEV  
0-20  
0
1000  
rEV  
0-20  
0
the firmware version.  
C O n F  
A. 0 0  
P8  
P9  
400  
nonE  
H.A.  
nonE  
H.A.  
OPrt.  
0
0.1  
0
0
norL  
norL  
norL  
norL  
Air  
OFF  
rEV  
OFF  
rEV  
OFF  
0
1000  
nonE  
H.A.  
nonE  
H.A.  
OPrt  
0
0.1  
0
0
norL  
norL  
norL  
norL  
Air  
OFF  
rEV  
OFF  
rEV  
OFF  
0
d) Maintaining the pressure on the t pushbutton  
push the s pushbutton also.  
P10  
P11  
P12  
P13  
P14  
P15  
P16  
P17  
P18  
P19  
P20  
P21  
P22  
P23  
P24  
P25  
P26  
P27  
P28  
The instrument will show:  
O F F  
d F L t  
e) Press s pushbutton to select between table 1  
(European) or table 2 (American) default set  
of parameters; the display will show:  
t b. 1  
d F L t  
f) Press FUNC pushbutton; the display will show:  
L O A d  
Appendix A.2  
1604-7-A-AB.p65  
2
5/16/00, 10:50 AM  
 
P29  
P30  
P31  
P32  
P33  
P34  
P35  
P36  
P37  
P38  
P39  
P40  
P41  
P42  
P43  
P44  
On  
2
30.0  
1.0  
00.20  
On  
0
10  
0
0.0  
nO.FL  
nO.FL  
Pid  
10.0  
Fn.Sp  
0
On  
2
30.0  
1.0  
00.20  
On  
0
30  
0
0.0  
nO.FL  
nO.FL  
Pid  
10.0  
Fn.Sp  
0
Appendix A.3  
1604-7-A-AB.p65  
3
5/16/00, 10:50 AM  
 
Appendix A.4  
1604-7-A-AB.p65  
4
5/16/00, 10:50 AM  
 
170.IU0.160.400  
Chromalox®  
INSTRUMENTS AND CONTROLS  
1382 HEIL QUAKER BOULEVARD  
LAVERGNE, TN 37086-3536  
PHONE (615) 793-3900  
FAX (615) 793-3563  
WIEGAND INDUSTRIAL DIVISION  
EMERSON ELECTRIC CO.  
1604-7-A-AB.p65  
5
5/16/00, 10:50 AM  
 

Black Box Pager FX800A User Manual
Blanco Indoor Furnishings 157 131 User Manual
Bosch Power Tools Drill SG45M User Manual
Braun Thermometer 6023 User Manual
Braun Toaster HT 600 User Manual
Broan Range 463002 User Manual
Brookstone Pedicure Spa Pedicure Spa User Manual
Brookstone Wheelchair OSIM USTYLE2 User Manual
Bushnell Hunting Equipment 743333 User Manual
Char Broil Charcoal Grill 463620410 User Manual