313AAV/JAV Plus 80x
4-WAY MULTIPOISE
INDUCED--COMBUSTION GAS FURNACE
INPUT CAPACITIES: 45,000 THRU 135,000 Btuh
Product Data
STANDARD FEATURES
S ECM blower motor included
S Noise elimination combustion system
S SmartEvapt can lower the humidity level in the home by
nearly 10%
S Four--position furnace: Upflow, Horizontal Right,
Horizontal Left, Downflow
Thirteen different vent options
S Compact design only 33--1/3 in. (847 mm) tall
S High--Efficiency Media Filtration Cabinet included
S Washable filter included
S Microprocessor based “smart” control center
“Fan on Plust “--Continuous Fan speed adjustable from
thermostat
Adjustable heating air temperature rise
Dehumidify mode
LED diagnostics, non--volatile fault code memory, and self--test
feature
A08288
On--board fuse for transformer protection
THE BRYANT Plus 80x GAS FURNACE
The Plus 80x Deluxe 4--Way Multipoise Gas Furnace offers
outstanding features in an 80% AFUE furnace.
S Patented blocked vent safeguard to ensure proper furnace
venting
Deluxe features include: an ECM motor which enhances SEER
performance up to 1.5 points*, a third fan relay for discrete
continuous fan speed, the ability to change continuous fan speeds
from the thermostat (Fan on Plust), dehumidify mode, standard
Media Filter Cabinet, fault code storage, and more. The Plus 80x
is very quiet thanks to a new combustion design that eliminates
noise, rather than just muffle or box it in. Applications are easy
with 4--way multipoise design, through--the--furnace downflow
venting, 13 different venting options, and a door designed for easy
service access. An inner blower door is provided for tighter sealing
in sensitive applications. The 313JAV is approved for use in Low
NOx Air Quality Management Districts.
S Insulated blower compartment
S HYBRID HEAT® Dual Fuel System compatible
S All models are chimney friendly when used with accessory
vent kit
S Perfect Lightt Igniter
S Residential installations eligible for consumer financing
through the Comfort Credit Program
*as compared to the Air Conditioning Heating and Refrigeration
Institute’s standard coil--only ratings when paired with selected
Bryant evaporator coils.
1
BRYANT ACCESSORIES
A97432
CONTROLS:
THERMOSTATS
AND ZONING
C04009
A01484
Available in programmable and
non-programmable models,
Bryant thermostats maintain a
constant, comfortable tempera-
ture level in the home.
MECHANICAL
MODEL HUMCCLFP
OR ELECTRONIC
HUMIDIFIER
By adding moisture to winter-dry
air, a Bryanthumidifier can often
improve comfort and keep
furniture, rugs, and draperies in
better condition. Moisturizing
household air also helps to retain
normal body heat and provides
comfort at lower temperatures.
AIR CLEANER
Cleans the air of smoke, dirt, and
many pollens commonly found.
Saves decorating and cleaning
expenses by keeping carpets,
furniture, and drapes cleaner.
For the ultimate in home comfort,
Bryant’s 2, 4, and 8-zone systems
allow temperature control of indi-
vidual “zones” of the home. This is
accomplished through a series of
electronic dampers and
Electronic air cleaner is shown.
remote room sensors.
The
4-zone system is shown.
A08153
ACCESSORIES
ELECTRONIC AIR CLEANER
(EAC)
Model EACB
AIR PURIFIER
MECHANICAL AIR CLEANER
HUMIDIFIER
Models GAPAAXBB1625, GAPAAXBB2025
Models EZXCAB, FILCAB
Model HUM
HEAT RECOVERY
VENTILATOR
ENERGY RECOVERY
VENTILATOR
Model HRV
Model ERV
UV LIGHTS
Model UVL
F o r u s e w i t h 1 --- s p e e d A i r C o n d i t i o n e r --- d e g . F / C , A u t o C h a n g e o v e r --- T 6 --- N A C , T 2 --- N A C
F o r u s e w i t h 1 --- s p e e d H e a t P u m p --- d e g . F / C , A u t o C h a n g e o v e r --- T 6 --- N H P, T 2 --- N H P *
F o r u s e w i t h 2 --- s p e e d A i r C o n d i t i o n e r --- d e g . F / C , A u t o C h a n g e o v e r --- T 6 --- N R H *
For use with multi---use / stage configurations --- deg. F/C, Auto Changeover/Temperature and
H u m i d i t y C o n t r o l --- T 6 --- P R H {
T H E R M O S T A T ---
N O N --- P R O G R A M M A B L E
F o r u s e w i t h 1 --- s p e e d A i r C o n d i t i o n e r --- d e g . F / C , A u t o C h a n g e o v e r, 7 --- D a y P r o g r a m m a b l e ---
T 6 --- PA C
F o r u s e w i t h 1 --- s p e e d H e a t P u m p --- d e g . F / C , A u t o C h a n g e o v e r, 7 --- D a y P r o g r a m m a b l e ---
T6---PHP*
F o r u s e w i t h 2 --- s p e e d A i r C o n d i t i o n e r --- d e g . F / C , A u t o C h a n g e o v e r, 7 --- D a y P r o g r a m m a b l e ---
T 6 --- P R H *
F o r u s e w i t h 1 --- s p e e d A i r C o n d i t i o n e r --- d e g . F / C , 5 --- 2 D a y P r o g r a m m a b l e --- T 6 --- PA C
T H E R M O S T A T ---
PROGRAMMABLE
F o r u s e w i t h m u l t i --- s t a g e a p p l i c a t i o n s --- d e g . F / C , A u t o C h a n g e o v e r, 7 --- D a y P r o g r a m m a b l e ---
T 2 --- P H P }
F o r m u l t i --- u s e / s t a g e c o n f i g u r a t i o n s --- d e g . F / C , A u t o C h a n g e o v e r, 7 --- D a y P r o g r a m m a b l e /
Temperature and Humidity Control ---T6---PRH{
Zone Perfect 3---Zone kit --- ZONEBB3ZAC01, ZONEBB3ZHP01
2 --- Z o n e P e r f e c t P l u s k i t / Te m p e r a t u r e a n d H u m i d i t y C o n t r o l --- Z O N E B B 2 K I T 0 1 --- B
4 --- Z o n e P e r f e c t P l u s k i t / Te m p e r a t u r e a n d H u m i d i t y C o n t r o l --- Z O N E B B 4 K I T 0 1 --- B
8 --- Z o n e P e r f e c t P l u s k i t / Te m p e r a t u r e a n d H u m i d i t y C o n t r o l --- Z O N E B B 8 K I T 0 1 --- B
ZONING CONTROL
*Model HP and 2S thermostat must be field converted to air conditioner operation.
{Thermidistatt Control can be configured for multiple use and staging. It must be configured for each specific application.
}Dual Fuel thermostat is used with furnace and heat pump application.
3
BRYANT ACCESSORIES
DESCRIPTION 313AAV/JAV
PART NO.
024045
X
048070
X
048090
X
060110
X
060135
FILBBCAR0016
FILBBCAR0020
FILBBCAR0024
EXPXXUNV0016
EXPXXUNV0020
EXPXXUNV0024
EXPXXFIL0016
EXPXXFIL0020
EXPXXFIL0024
KGAFR0401B14
KGAFR0501B17
KGAFR0601B21
KGAFR0701B24
KGAFR0801SRE
KGAWF1301UFR {
KGAWF1401UFR
KGAWF1501UFR
KGAWF1306UFR {
KGAWF1406UFR
KGAWF1506UFR
KGAFE0112UPH
KGASB0201ALL
KGAVG0101DFG
KGAVE0101DNH
KGACA02014FC
KGACA02015FC
KGANP4601ALL
KGAPN3901ALL
KGALB0101KIT
KGBAC0110DGK
KGBAC0110DGK
KGAHA0150N42
Cartridge Media Filter
X
X
X
X
X
X
X
X
X
X
X
X
EZ Flex Media Filter with End Caps
Replacement EZ Flex Filter Media
External Bottom Return
X
X
X
S
X
X
S
Filter Rack
X
X
External Side Return Filter Rack
X
S
X
S
S
Unframed Filter 3/4---in. (19 mm)
X
X
X
X
X
X
X
X
X
Flue Extension
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
Combustible Floor Base
Downflow Vent Guard
Vent Extension Kit
Chimney Adapter Kit
Chimney Adapter Kit
N a t u r a l --- t o --- P r o p a n e C o n v e r s i o n K i t *
P r o p a n e --- t o --- N a t u r a l C o n v e r s i o n K i t *
Label Kit
Air Leakage Kit (Qty 10)
Air Leakage Kit (Qty 10)
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
KGAHA0250N43
(factory supplied)
KGAHA0350N44
KGAHA0450N45
KGAHA0550N46
KGAHA1550N47
KGAHA1650N48
KGAHA0650P54
KGAHA0750P55
KGAHA0850P56
KGAHA5750125
KGAHA5750130
Gas Orifice Kit (Qty 50)
See Installation Instructions for model, altitude, and heat value usages.
*Factory---authorized and field---installed. Gas conversion kits are CSA (AGA/CGA) recognized.
{Suitable for Side Return Filter Rack (KGAFR0801SRE)
X
--- Accessor y
S --- Stan dar d
4
PHYSICAL DATA
UNIT SIZE
024045
048070
048090
060110
060135
OUTPUT CAPACITY
BTUH
( N o n --- w e a t h e r i z e d I C S )
313JAV Upflow; all 313AAV
313JAV Downflow/Horizontal
36,000
53,000
72,000
90,000
107,000
34,000
51,000
69,000
86,000
102,000
313JAV Upflow; all 313AAV
313JAV Downflow/Horizontal
N o n --- w e a t h e r i z e d IC S
44,000
42,000
80.0
66,000
63,000
80.0
88,000
84,000
80.0
110,000
105,000
80.0
132,000
126,000
80.0
INPUT BTUH
AFUE%
SHIPPING WEIGHT LB. (KG)
104 (47)
126 (57)
140 (64)
152 (69)
163 (74)
30---60
( 1 7 --- 3 3 )
25---55
( 1 4 --- 3 1 )
35---65
( 1 9 --- 3 6 )
30---60
( 1 7 --- 3 3 )
40---70
( 2 2 --- 3 9 )
CERTIFIED TEMP RISE RANGE ˚_F (_C)
Heating
Cooling
Heating
Cooling
0.10
0.50
735
0.12
0.50
1230
1460
0.15
0.50
1345
1665
SPST
0.20
0.50
1890
2040
0.20
0.50
1865
2070
CERTIFIED EXT STATIC
PRESSURE (IN. WC)
AIRFLOW CFM
1035
LIMIT CONTROL
HEATING BLOWER CONTROL
BURNERS (Monoport)
Solid---State Time Operation
4
2
3
5
6
GAS CONNECTION SIZE
1 / 2 --- in . N P T
GAS VALVE(Redundant) Manufacturer
Minimum Inlet Pressure (in. wc)
Maximum Inlet Pressure (in. wc)
IGNITION DEVICE
W h it e --- R o d g e r s
4.5 (Natural Gas)
13.6 (Natural Gas)
Hot Surface
*Gas input ratings are certified for elevations to 2000 ft. (610 M)*. In USA, For elevations above 2000 ft. (610 M), reduce ratings 4 percent for each 1000 ft. (305
M) above sea level. In Canada, derate the unit 10 percent for elevations 2000 to 4500 ft. (610 --- 1372 M) above sea level. Refer to National Fuel Gas Code
NFPA 54/ANSI Z223.1---2006 Table F.1 (d) or furnace Installation Instructions.
{Capacity in accordance with U.S. Government DOE test procedures.
}Airflow shown is for bottom only return---air supply. For air delivery above 1800 CFM, see Air Delivery Table for other options. A filter is required for each
return---air supply. An airflow reduction of up to 7 percent may occur when using a Bryant 4---5/16 in. (110 mm) high efficiency media filter.
ICS --- Isolated Combustion System
BLOWER PERFORMANCE DATA
UNIT SIZE
024045
1/2
6.8
048070
3/4
8.4
048090
3/4
8.4
060110
1
10.9
060135
1
10.9
DIRECT---DRIVE MOTOR Hp (ECM --- 5 Speed)
MOTOR FULL LOAD AMPS
R P M ( N o m i n a l ) --- S P E E D S
1050---5
1050---5
1050---5
1050---5
1050---5
10 x 6
(254 x 152)
11 x 8
(279 x 203)
10X10
(254 x 254)
11 x 11
(279 x 279)
11 x 11
(279 x 279)
BLOWER WHEEL DIAMETER x WIDTHS --- IN (MM)
5
SEE NOTES: 1,2,3,4,7,8,9
SEE NOTES: 1,2,4,5,7,8,9
SEE NOTES: 1,2,4,7,8,9
UPFLOW
DOWNFLOW
UPFLOW
A02061
A02058
A02059
SEE NOTES:1,2,3,4,5,7,8,9
DOWNFLOW
SEE NOTES: 1,2,3,4,7,8,9
DOWNFLOW
SEE NOTES: 1,2,4,5,6,7,8,9
DOWNFLOW
A02062
A02060
A02063
Venting Notes
1. For common vent, vent connector sizing and vent material: United States, latest edition of the National Fuel Gas Code (NFGC),
NFPA54/ANSI Z223.1. In Canada, latest edition of the National Standards of Canada, Natural Gas and Propane Installation Code
(NSCNGPIC), CSA B149.1.
2. Immediately increase to 5--in. (127 mm) vent connector outside furnace casing when 5--in. (127 mm) vent connector required, refer to
Note 1.
3. Side outlet vent for upflow and downflow installations must use Type B vent immediately after exiting the furnace, except when
KGAVG0101DFG is used in downflow position.
4. Type B vent where required, refer to Note 1.
5. 4--in. (102 mm) single wall vent must be used inside furnace casing and the KGAVG0101DFG Downflow Vent Guard Kit.
6. Accessory Downflow Vent Guard Kit, KGAVG0101DFG required in downflow installations with bottom vent configuration.
7. Chimney Adapter Kit required for exterior masonry chimney applications. Refer to Chimney Adapter Kit, KGACA02014FC and
KGACA02015FC for sizing and complete application details.
8. Secure vent connector to furnace elbow with (2) corrosion--resistant sheet metal screws, space approximately 180_ apart.
9. Secure all other single wall vent connector joints with (3) corrosion--resistant screws spaced approximately 120_ apart. Secure Type B
vent connectors per vent connector manufacturer’s recommendations.
6
SEE NOTES: 1,2,4,5,7,8,9
HORIZONTAL RIGHT
SEE NOTES: 1,2,4,5,7,8,9
HORIZONTAL RIGHT
A02068
A02070
SEE NOTES: 1,2,4,7,8,9
HORIZONTAL RIGHT
A02069
SEE NOTES: 1,2,4,7,8,9
HORIZONTAL LEFT
SEE NOTES: 1,2,4,5,7,8,9
HORIZONTAL LEFT
A02064
A02065
SEE NOTES: 1,2,4,5,7,8,9
HORIZONTAL LEFT
SEE NOTES: 1,2,4,5,7,8,9
HORIZONTAL LEFT
A02067
A02066
7
AIR DELIVERY -- CFM (WITH FILTER)*
EXTERNAL STATIC PRESSURE (in. wc)
RETURN---AIR
UNIT SIZE
SPEED
SUPPLY
0.1
1185
920
735
820
0.2
1145
880
685
765
0.3
1115
835
625
725
0.4
1075
800
0.5
1035
755
0.6
980
720
0.7
905
680
0.8
820
0.9
720
1
580
5
4
3
2
1
5
4
3
2
1
5
4
3
2
1
5
4
3
2
1
5
4
3
2
1
645
605
540
Bottom or
Side(s)
024045
585
530
490
435
395
345
295
670
630
580
545
490
455
405
650
595
535
490
430
390
330
280
235
--- ---
1625
1405
1240
1190
1035
1845
1590
1365
1225
1100
2255
1600
1945
1420
1280
2295
1725
1910
1630
1430
1585
1360
1200
1140
985
1535
1320
1155
1095
930
1755
1500
1270
1110
960
2150
1465
1830
1280
1140
2185
1605
1800
1510
1285
1495
1280
1110
1050
885
1460
1240
1065
1000
835
1415
1195
1020
955
1365
1155
975
915
745
1295
1115
935
1220
1070
895
1125
1030
850
Bottom or
Side(s)
048070
048090
060110
060135
870
830
790
785
695
650
600
1800
1545
1320
1160
1030
2205
1525
1890
1340
1205
2240
1660
1865
1575
1355
1710
1455
1215
1060
875
1665
1410
1170
1010
805
1595
1365
1125
950
1500
1315
1070
895
1400
1270
1025
830
1275
1180
955
1105
1000
900
Bottom or
Side(s)
770
710
730
645
570
505
425
2100
1400
1770
1200
1055
2125
1545
1745
1435
1200
2040
1335
1715
1140
990
2070
1460
1685
1365
1125
1985
1275
1655
1065
910
2005
1395
1610
1300
1075
1920
1210
1600
1005
840
1925
1340
1545
1245
1015
1835
1150
1545
925
1735
1080
1480
865
1615
1015
1430
790
Bottom or
Side(s)
760
695
630
1805
1285
1485
1185
945
1670
1230
1435
1130
855
1545
1170
1380
1065
800
Bottom or
Side(s)
*A filter is required for each return---air inlet. Airflow performance included 3/4---in. (19 mm) washable filter media such as contained in factory ---authorized ac-
cessory filter rack. To determine airflow performance without this filter, assume an additional 0.1 in. wc available external static pressure.
--- --- Indicates unstable operating conditions.
ELECTRICAL DATA
OPERATING VOLTAGE
313AAV/
JAV UNIT
SIZE
V O LT S ---
H E R T Z ---
PHASE
MAXIMUM FUSE
OR CKT BKR
AMPS{
MAXIMUM
MAXIMUM WIRE
MINIMUM
WIRE GAGE
RANGE*
UNIT AMPS
LENGTH FT (M)}
Maximum
127
Minimum
104
024045
048070
048090
060110
060135
1 1 5 --- 6 0 --- 1
1 1 5 --- 6 0 --- 1
1 1 5 --- 6 0 --- 1
1 1 5 --- 6 0 --- 1
1 1 5 --- 6 0 --- 1
8.1
9.5
10.3
13.1
13.1
34 (10)
29 (9)
27 (8)
34 (10)
34 (10)
15
15
15
20
20
14
14
14
12
12
127
104
127
104
127
104
127
104
* Permissible limits of the voltage range at which the unit operates satisfactorily.
{ Time---delay type is recommended.
}Length shown is as measured 1 way along wire path between unit and service panel for maximum 2 percent voltage drop.
8
DIMENSIONS
(733mm)
28-7/8"
(664mm)
26-1/8"
(FLUE COLLAR)
(641mm)
25-1/4"
2-7/16"
(62mm)
1-5/16"
(33mm)
22-9/16"
(573mm)
A
D
AIRFLOW
13/16"
(21mm)
19"
(483mm)
JUNCTION BOX
LOCATION
13/16"
(21mm)
1-1/8"
(29mm)
5-15/16"
(135mm)
OUTLET
4-13/16"
(122mm)
F
1/2" DIA. K.O.THERMOSTAT
(22mm)
7/8" DIA
ACCESSORY
9-5/8"
(244mm)
WIRE ENTRY
(13mm)
11/16" 7-3/4"
(17mm)(197mm)
8-9/16"
(217mm)
1-3/4" DIA.RIGHT HAND
GAS ENTRY (44mm)
1/2" (13 mm) DIA.
THERMOSTAT WIRE ENTRY
11-1/2"
(292mm)
3-15/16" (84mm)
LEFT HAND GAS
ENTRY
7/8" DIA. K.O. WIRE ENTRY
(22mm)
ALTERNATE
33-5/16"
(846mm)
JUNCTION BOX
24-7/8"
(632mm)
LOCATIONS (TYP)
VENT OUTLET
5 PLACES (TYP)
14-7/8"
(378mm)
7/8" (22mm) DIA.
ACCESSORY
7/8" DIA. ACCESSORY
(22mm)
5-1/2" (140mm)
5-1/2"
(140mm)
11/16"
(17mm)
(549mm)
1-1/2"
(38mm)
11/16"
(17mm)
1-1/4"
3-3/4"
(95mm)
E
21-5/8"
1-11/16"
(43mm)
(32mm)
(560mm)
22-1/16"
SIDE INLET
BOTTOM INLET
1"
(25mm)
24"
CASING
(610mm)
A04037
1. Two additional 7/8--in. (22 mm) dia. knockouts are located in the top plate.
2. Minimum return--air openings at furnace, based on metal duct. If flex duct is used, see flex duct manufacturer’s recommendations for equivalent diameters.
3. Minimum return--air opening at furnace.
a. For 800 CFM--16--in. (406 mm) round or 14--1/2 x 12--in. (368 x 305 mm) rectangle.
b. For 1200 CFM--20--in. (508 mm) round or 14--1/2 x 19--1/3 in. (368 x 491 mm)rectangle.
c. For 1600 CFM--22--in. (559 mm) round or 14--1/2 x 22--1/16--in. (368 x 560 mm) rectangle.
d. For airflow requirements above 1800 CFM, see Air Delivery table in Product Data literature for specific use of single side inlets. The use of both side inlets, a
combination of 1 side and the bottom, or the bottom of single side inlets. The use of both side inlets, a combination of one side and the bottom, or the bottom only
will ensure adequate return air openings for airflow requirements above 1800 CFM.
A
E
F
VENT
CONNECTION
SIZE
D
MEDIA CABINET
SIZE
313AAV/JAV
UNIT SIZE
CABINET
WIDTH
IN (MM)
BOTTOM
TOP VENT
OUTLET
IN (MM)
SUPPLY WIDTH
IN (MM)
RETURN WIDTH
IN (MM)
IN (MM)
(see Notes 1 & 2)
024045
048070
048090
060110
060135
14---3/16 (360)
17---1/2 (445)
21 (533)
21 (533)
24---1/2 (622)
12---9/16 (319)
15---7/8 (403)
19---3/8 (492)
19---3/8 (492)
22---7/8 (581)
12---11/16 (322)
16---1/8 (410)
19---1/2 (495)
19---1/2 (495)
23 (584)
9---5/16 (237)
11---9/16 (294)
13---5/16 (338)
13---5/16 (338)
15---1/16 (383)
4
4
4
4
16 (406)
16 (406)
20 (508)
20 (508)
24 (610)
4 (Note 1)
1. 135 size furnaces require 5---in. (127 mm) vents. Use a 4---5 in. (102---127 mm) vent adaptor between furnace and vent stack.
2. See installation instructions for complete installation requirements.
9
A08471
ISO 9001:2000
D
MEETS DOE RESIDENTIAL CONSERVATION
EFFICIENCY
RATING
SERVICES PROGRAM STANDARDS.
CERTIFIED
Before purchasing this appliance, read important
energy cost and efficiency information available
from your retailer.
REGISTERED
CERTIFIED
®
5
/
25 8" (651mm)
5
/
8
23
"
1
(600mm)
(651mm)
/
24
2
"
With Flanges Bent Out
3
/
8
1
23
"
(587mm)
/
23
8
"
(600mm)
Opening
A
B
Furnace Side
Duct Side
3
/
4"
23
Centerline Screw Slots
3
/
4
5
"
(603mm)
Media/
(146mm)
Filter Cabinet
A
B
C
1
/
15"/
(41327m"/m) 16 4"/
(406mm)
16"/
20"/(508mm)
(610mm)
(413mm)
(31819m"/m)
1
/
(52331m"/m)
(62355m"/m)
20 4"/
(514mm)
(483mm)
1
/
23"/
24 4"/
24"/
(616mm)
(584mm)
A00444
10
TYPICAL WIRING SCHEMATIC
FIELD 24-V WIRING
FIELD 115-, 208/230-, 460-V WIRING
FACTORY 24-V WIRING
FACTORY 115-V WIRING
NOTE 2
THERMOSTAT
TERMINALS
W
C
R
G
Y
FIVE WIRE
FIELD-SUPPLIED
DISCONNECT
THREE-WIRE
HEATING-ONLY
208/230- OR
460-V
BLOWER DOOR SWITCH
THREE
PHASE
W
R
BLK
BLK
C
O
N
T
R
O
L
WHT
WHT
208/230-V
SINGLE
PHASE
GND
GND
G
AUXILIARY
J-BOX
115-V FIELD-
SUPPLIED
DISCONNECT
COM
Y/Y2
GND
NOTE 1
CONDENSING
UNIT
TWO
WIRE
24-V
TERMINAL
BLOCK
NOTES: 1. Connect Y-terminal in furnace as shown for proper blower operation.
2. Some thermostats require a "C" terminal connection as shown.
3. If any of the original wire, as supplied, must be replaced, use
same type or equivalent wire.
FURNACE
A99440
TYPICAL INSTALLATION
CONDENSING
UNIT
HUMIDIFIER
GAS-FIRED
WATER HEATER
ELECTRONIC
AIR CLEANER
AIRFLOW
A08177
11
Casing
GUIDE SPECIFICATIONS
Casing shall be of .030 in. (.76 mm) thickness minimum,
pre--painted galvanized steel.
Gas Furnace
313AAV/JAV
Inducer Motor
Inducer motor shall be soft mounted to reduce vibration
transmission.
GENERAL
System Description
Furnish a _________________ fixed capacity gas--fired furnace
for use with natural gas or propane (factory authorized conversion
kit required for propane); furnish cold air return plenum; furnish
external medial cabinet for use with accessory media filter or
standard filter.
Draft Safeguard Switch
Draft Safeguard Switch (blocked vent safeguard) shall be factory
installed to reduce the possibility of vent gas infiltration due to a
blocked or restricted vent pipe.
Heat Exchangers
Quality Assurance
Unit will be designed, tested and constructed to the current ANSI Z
21.47/CSA 2.3 design standard for gas--fired central furnaces.
Heat exchangers shall be a 4--Pass 20 gage aluminized steel of
fold--and--crimp sectional design when applied operating under
negative pressure.
Unit will be 3rd party certified by CSA to the current ANSI Z
21.47/CSA 2.3 design standard for gas--fired central furnaces.
Controls
Control shall include a micro--processor based integrated electronic
control board with at least 11 service troubleshooting codes
displayed via diagnostic flashing LED light on the control, a
self--test feature that checks all major functions of the furnace
within one minute, and a replaceable automotive--type circuit
protection fuse. Multiple operational settings available including,
separate blower speeds for heating, cooling and continuous fan.
Continuous fan speed may be adjusted from the thermostat.
Features will also include temporary reduced airflow in the cooling
mode for improved dehumidification when a Thermidistatt
Control is selected as the thermostat.
Unit will carry the CSA Blue Star® and Blue Flame® labels.
Unit efficiency testing will be performed per the current DOE test
procedure as listed in the Federal Register.
Unit will be certified for capacity and efficiency and listed in the
latest GAMA Consumer’s Directory of Certified Efficiency
Ratings.
Unit will carry the current Federal Trade Commission Energy
Guide efficiency label.
Delivery, Storage and Handling
Unit shall be shipped as single package only and is stored and
handled per unit manufacturer’s recommendations.
Operating Characteristics
Heating Capacity shall be ________ Btuh input; ________ Btuh
output capacity.
Warranty (for inclusion by specifying engineer)
U.S. and Canada only. Warranty certificate available upon request.
Fuel Gas Efficiency shall be 80% AFUE.
Air delivery shall be ___________ CFM minimum at 0.50 in. wc
external static pressure.
PRODUCTS
Equipment
Dimensions shall be: depth __________ in.; width _________ in;
height_________in. (mm) (casing only). Height shall
be_________in. (mm) with A/C coil and _____________in. (mm)
overall with plenum.
Components shall include: slow--opening gas valve to reduce
ignition noise, regulate gas flow, with electric switch gas shut--off;
flame proving sensor, hot surface igniter, pressure switch assembly;
flame rollout switch, blower and inducer assembly, 40va
transformer; low--voltage (heating) (heating/ cooling) thermostat.
Electrical Requirements
Blower Wheel and Blower Motor
Electrical supply shall be 115 volts, 60 Hz, single--phase (nominal).
Minimum wire size shall be_________AWG; maximum fuse size
or circuit breaker shall be __________Amps.
Galvanized blower wheel shall be centrifugal type, statically and
dynamically balanced. Blower motor of ECM type shall be
permanently lubricated with sealed bearings, of _______hp, and
shall be multiple--speed direct drive. Blower motor shall be soft
mounted to the blower scroll to reduce vibration transmission.
Special Features
Refer to section of the product data sheet identifying accessories
and descriptions for specific features and available enhancements.
Filters
Furnace may have reusable--type filters. Filter shall be _______ in
(x) _______in. (mm).An accessory high efficiency Media Filter is
available as an option. _______________ Media Filter.
8 Bryant Heating & Cooling Systems D 7310 W. Morris St. D Indianapolis, IN 46231
Printed in U.S.A.
Edition Date: 3/09
Catalog No. PDS313AAV--- 0 4
Replaces: PDS313AAV---03
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
12
|