Black Box Network Card LMC200A 2PS DC User Manual

Hot Attachment of Power Supplies:  
1. Unpack the power supply carefully. Inspect for any damages. If any damage is  
observed, do not use the power supply and call (949) 250-6510 to report the  
damage immediately and request a replacement unit.  
2. Attach the power supply to the chassis and reconnect the 48VDC power source  
to the FlexPoint power supply.  
JULY 2001  
LMC200A-2PS-DC  
LMC200A-DC  
PSFP20-DC  
3. Locate the 48VDC circuit breaker and switch the circuit breaker to the ON  
position.  
4. Turn the FlexPoint Chassis power supply ON.  
5. Observe the LED in the front of the chassis indicating that the power has been  
restored.  
SPECIFICATION  
Indicators:  
Power ON:  
LED (2), Yellow, power applied  
FlexPointTM Powered Chassis  
Dimensions / Weight: W:19.0"xD:7.0"xH:3.5" / 9 lb.  
Power:  
48VDC / 3.0 Amps (for model 4386)  
2ea. 48VDC / 3.0 Amps (for model 4385)  
Environmental:  
Temperature:  
Humidity:  
48V Power Redundant  
14 Module Chassis  
0 to 40 degrees C  
0-90% (non-condensing)  
User’s Manual  
Order toll-free in the U.S.: Call 877-877-BBOX (outside U.S. call 724-746-5500)  
CUSTOMER  
SUPPORT  
INFORMATION  
FREE technical support 24 hours a day, 7 days a week; Call 724-746-5500 or fax 724-746-0746  
Mailing address: Black Box Corporation, 1000 Park Drive, Lawrence, PA 15055-1018  
©Copyright 1999-2001.Black Box Corporation. All rights reserved.  
1000 Park Drive  
z
Lawrence, PA 15055-1018  
z
724-746-5500  
z
Fax 724-746-0746  
 
6
Cabling and Power-Up:  
FlexPointTM Powered Chassis  
User’s Manual  
1. Insure that both FlexPoint Chassis power supply switches are in the OFF position.  
2. Assure that the 48VDC circuit breaker can supply 3Aof current per power supply.  
3. Locate the 48VDC circuit breaker, and switch the 48VDC circuit breaker to the  
OFF position.  
4. Cut the power cable to the length required.  
GENERAL DESCRIPTION  
5. Strip approximately 3/8 of an inch of insulation from the power cable wires.  
6. Connect the power cables to the FlexPoint Chassis by fastening the stripped  
ends to the 48VDC connector.  
The FlexPointTM Powered Chassis is a chassis capable of holding up to 14  
FlexPointTM media converter modules. It is equipped with two power supplies in a  
power-redundant configuration.  
WARNING: Note the wire colors used for making the positive, negative and  
ground connections. Use the same color assignment for the connection at the  
circuit breaker.  
7. Connect the power cable to the circuit breaker and switch the circuit breaker  
ON.  
8. Turn both FlexPoint Chassis power supply switches on and check the power  
LED’s on the front panel of the powered chassis. The two LED’s should be ON.  
9. Attach the L shaped tabs to the FlexPoint media converter units to be inserted  
into the chassis, Secure the FlexPoint module using the enclosed screws.  
10. Save the unused tabs in a safe place or secure them to the chassis’ unused  
Slots.  
POWER SUPPLY REPLACEMENT  
WARNING!  
This User’s Manual describes the following models:  
NEVER ATTEMPT TO OPEN OR SERVICE THE POWER  
SUPPLY UNIT. OPENING THE POWER SUPPLY UNIT  
MAY CAUSE SERIOUS INJURY OR DEATH.  
Model  
Description  
LMC200A-2PS-DC  
Powered Chassis, rack-mountable chassis, 2 power  
supplies  
LMC200A-DC  
PSFP20-DC  
Powered Chassis, rack-mountable chassis, 1 power  
supply  
Power supply unit for models LMC200A-2PS-DC and  
LMC200A-DC  
The Powered Chassis is intended to be used with two power supplies in a power-  
redundant operation. A failure of a single supply should not disturb the operation  
of the chassis unit. However, certain power supply failures may cause a  
secondary failure to the associated fan and cause undesired overheating of  
the chassis unit.  
 
4
5
8. Wiring methods used for the connection of the equipment to the primary  
power supply shall be in accordance with the National Electrical Code, ANSI/  
NFPA 70, and the Canadian Electrical Code, Part I, C22.1.  
CONTROLS AND INDICATORS  
LEDs Display:  
The Powered Chassis features two LEDs on the left front of the chassis, these  
LEDs display the status of the two power supplies.  
UNPACKING  
a. Visual Inspection: Inspect equipment in order to detect any physical damage.  
Any evidence of damage should be noted and reported immediately.  
Function  
Top LED  
Bottom LED Yellow / ON  
Color/State  
Yellow / ON  
Description  
Power OK in right power supply  
Power OK in left power supply  
INVENTORY  
Review contents, the following items should be included:  
Note: Left/right direction as viewed from the front of the chassis.  
(1) FlexPoint Powered Chassis unit.  
(2) Power supplies (2 for model LMC200A-2PS-DC, 1 for model LMC200A-DC).  
(14) L shape tabs.  
(14) Screws  
(1) User’s manual (this document).  
Please note any missing items or discrepancies and report them immediately.  
INSTALLATION  
WARNING: Only a DC power source that complies with safety extra low  
voltage (SLEV) requirements can be connected to the DC-input power supply.  
Tools and Equipment Required:  
Flat-head screwdriver (not supplied)  
Wire cutter/stripper (not supplied)  
Three-conductor 14 AWG copper power cable (recommended; not supplied)  
SITE PREPARATION REQUIREMENTS  
Preparation:  
1. Power: Assure the 48VDC power can supply 3A of current.  
Assure that the FlexPoint Chassis is physically installed in accordance with  
the Site Preparation Requirements outlined earlier in this document.  
2. The operating temperature of this equipment is 0-40 degrees C. If installed  
in a closed or multiunit rack assembly, the operating ambient temperature  
of the rack must not exceed the maximum rated 40 degrees C temperature.  
3. Installation of the equipment should be such that the air flow in the front and  
back of the unit is not compromised or restricted.  
4. Never use this equipment to carry any weight except its own, never use it as  
a shelf to support weight of other equipment.  
5. Installing this equipment into a rack in such a way as to make it unstable  
may cause injury or death. Always make sure that the rack you are installing  
this equipment into is properly secure, stable, balanced and designed to  
carry the weight and weight distribution of this equipment.  
WARNING REGARDING EARTHING GROUND:  
a) This equipment shall be connected to the DC supply system earthing  
electrode conductor or to a bonding jumper from an earthing terminal bar  
or bus to which the DC supply system earthing electrode is connected.  
b) This equipment shall be located in the same immediate area (such as,  
adjacent cabinets) as any other equipment that has a connection  
between the earthed conductor of the same DC supply circuit and the  
earthing conductor, and also the point of earthing of the DC system. The  
DC system shall not be earthed elswere.  
6. When rack-mounting this equipment, the rack should be appropriately  
earth-grounded.  
c) The DC supply source is to be located within the same premises as this  
equipment.  
7. This equipment requires 48 VDC / 3.0 Amps per power supply. Appropriate  
overloading protection should be provided on all DC power source outlets  
utilized.  
d) There shall be no switching or disconnecting devices in the earthed circuit  
conductor between the DC source and the earthing electrode conductor.  
 

Belkin Vacuum Cleaner F8E426 User Manual
Bifinett Kitchen Utensil KH 109 User Manual
Bolzano Villetri Speaker DB 5004 BP AB User Manual
Brother Printer FAX 8250P User Manual
Brother Sewing Machine XE3725 1011 User Manual
Canon Digital Camera 115 HS User Manual
Canon Photo Scanner FS 2720 U User Manual
Cecilware Fryer EL 6 User Manual
CFM Corporation Smoker 3405BG User Manual
Cisco Systems IP Phone 7915 User Manual