Air King Ventilation Hood AK110LS User Manual

SPECIFICATIONS  
AK110LS  
EXHAUST FANS  
110 CFM/1.5 SONES @ 0.10" wg. • 90 CFM/1.5 SONES @ 0.25 wg.  
HVI CERTIFIED 120 Volts, 0.30 amps, 60 hz.  
938"  
/
1078"  
/
Grill  
4"  
White, polymeric grill secured in place with torsion springs;  
3
/
easily removed if necessary, dimensions - 11" x 13 4".  
778"  
/
• Blower Wheel  
Balanced polymeric dual inlet blower wheel 513 " dia. x 4"  
/32  
depth, 30 paddles, secured in place using 8M hex nut.  
1334"  
11"  
/
• Motor  
Enclosed 4 pole electronically balanced permanently split  
capacitor motor (PSC); life time lubrication, suitable for  
continuous operation. Motor bearings - ball. Rated 115/120 volts,  
60 Hz, 0.30 amps.  
CUL/HVI  
Acceptable for use over tub or shower when  
installed in a GFCI protected branch circuit.  
• Fan Housing  
23 gauge galvanized steel housing, fully sealed.  
3
7
/
Overall dimensions 107 8" x 9 8" x 7 8".  
/
/
• Unit Mounting  
The housing will mount in ceilings with at least 8" of clearance  
• Duct Collar  
and through drywall thickness up to 3 4", with a rough-in opening  
/
4" round, zinc plated metal collar adapter. 4" spring loaded  
aluminum backdraft damper.  
1
/
5
/
of 11 8" x 9 8". Rated for ceilings insulated to R-40. The housing  
will mount either between 16" or 24" on center joists, using the  
4 supplied housing mounting rails. The housing mounting rails  
can be adapted for overhead mounting (hardware not provided).  
• Ventilating Area  
For bathrooms up to 110 sq. ft. For other rooms up to 135 sq. ft.  
• Single Pack Shipping Info  
1
5
5
/
• Electrical Connections  
/
/
Box Dim: 14 8" x 11 8" x 9 8"  
UPC: 0-8316221121-7  
1
/
2" electrical knockouts provided. Easy wiring access via either  
Shipping Weight: 11.5 lbs.  
internal or external wiring compartment cover.  
PERFORMANCE  
HVI Sones Fan Speed Power  
Static Pressure (inches of w.g.)  
@ .1 SP  
RPM  
Watts  
0
119  
0.05  
115  
0.1  
110  
0.2  
99  
0.25  
90  
0.3  
75  
0.35  
65  
0.4  
48  
Air Flow - CFM  
PROJECT  
1.5  
1125  
28  
ARCHITECT  
ENGINEER  
LOCATION  
CONTRACTOR  
SUBMITTED BY  
DATE  
FAN  
MODEL  
IN  
W.G.  
OPTIONAL EQUIPMENT  
& REMARKS  
CFM  
RPM  
WATTS AMPS  
SONES  
QTY  
NUMBER NUMBER  
U.S.: 820 Lincoln Drive  
West Chester, Pennsylvania 19380-4466  
Tel: (877)-304-3785  
Canada: 110 Glidden Road  
Brampton, Ontario L6T 2J3  
Tel: (905) 456-2033  
C
US  
Fax: (610) 696-8048  
Fax: (905) 456-1015  
Specifications subject to change without notice.  
Updated 6-06  
 

3M Computer Monitor UMUV10 045V2 User Manual
AdobeAir Humidifier CC2000B User Manual
ADTRAN Server MP 114 User Manual
AEG Oven B3101 5 M User Manual
Airlink101 Network Card AWLH4130 User Manual
Alloy Computer Products Network Card WDS2454AP User Manual
Alto Shaam Oven Cook and Hold Ovens User Manual
Aluratek Portable Stereo System AWS01F User Manual
Asus Cell Phone M530w User Manual
Beckett Water Gardening Plumbing Product G325AG20 User Manual