Protect
3.M 2.0
Modular uPs systeM
Uninterruptible Power Supply
3-Phase Input; 3-Phase Output
20–120 kVA power supply
Networks, workstations, intranet and internet servers,
Key features
telecommunications applications and other company
applications must be permanently available. AEG
Protect 3.M 2.0 is the modular UPS solution for IT and
telecommunications. Modern data centers require the
highest levels of efficiency, reliability and flexibility.
»Modular design allows for flexible adaption
to the current power demand
»Up to 95% efficiency in “online double conversion”
mode, up to 98% in ECO mode
»IGBT technology, input power factor >0.99
»Low phase effect <3%
Protect 3.M 2.0 provides a technically convincing
and reliable solution to this requirement that can be
modularly adapted to any increasing power demand.
»Redundant control and n+x parallel
redundancy for high availability
An extension can be made at any time during
operation. The flexible redundancy concept ensures a
steady power supply to any connected devices.
»Parallel operation of up to 4 UPS units (max. 480kVA)
»Module installation and removal during operation
(”hot swappable”)
Lower operating costs for energy and cooling with high
efficiency and fast module replacement in the event of power
failure, reduce operational costs and ensure an optimal price
vs. performance ratio for the Protect 3.M 2.0 UPS solution.
»Graphical LCD screen
»Built-in manual bypass, separate input for bypass power
»Load dependent fan speed
»Small footprint
3
Classification VFI SS 111 acc. to IEC 62040-3
Power type rating
Protect 3.M 2.0
20 kVA
16 kW
40 kVA
32 kW
60 kVA
80 kVA
64 kW
100 kVA
80 kW
120 kVA
96 kW
48 kW
88 A
SyStEM
Nominal input current
Efficiency (typical)
29 A
59 A
117 A
145 A
172 A
95 %
98 %
Efficiency in ECO mode
Waste heat from power (typical)
1.3 kW
4436 BTU/h
309
2.6 kW
8872 BTU/h
617
3.9 kW
13308 BTU/h
926
5.2 kW
17744 BTU/h
1234
6.5 kW
22180 BTU/h
1543
7.8 kW
26616 BTU/h
1852
Airflow (max.) m³/h
INPut
Nominal voltage
Input voltage range
Frequency
3 x 400 V (380 V, 415 V adjustable), 3 phase + neutral
305 – 477 V
50 Hz/ 60 Hz (adjustable)
≤3 % 1)
total harmonic distortion (tHDv)
Power factor
>0.99
INVErtEr
Nominal voltage
Frequency
3 x 400 V (380 V, 415 V adjustable), 3 phase + neutral
50 / 60 Hz (adjustable)
Precision static/dynamic
total harmonic distortion (tHDv)
Max. phase displacement
Admissible overload
Crest factor
1 % / 7 %
<3 % ( linear load), <5 % (non-linear load)
1.5 % (balanced load), 2 % (100 % unbalanced load)
125 % for 10 min., 150 % for 60 s
2.7 : 1
Max. short circuit current
Admissible power factor
BAttEry
>270 % of the rated current
0.1 inductive to 0.1 capacitive
rated voltage
240 V DC
Max. charging power
Charging principle
Autonomy time
5 A
10 A
15 A
20 A
25 A
30 A
Load switching per power module
Selectable over external battery cabinet
StAtIC ByPASS
Nominal voltage
Frequency
3 x 400 V (380, 415 V adjustable), 3 phase + neutral
50 Hz / 60 Hz (adjustable)
Synchronization range
transfer time at mains outage
Admissible overload
GENErAl DAtA
Parallel mode
0.1 – 5 % (adjustable)
0 ms (without interruption)
175 % for 10 ms
Up to 4 UPS (central battery possible)
Audible noise
62 – 69 dB(A) dependent on equipment installed and load state
Operating temperature range/humidity
Protection
0 – 40°C / <95 % (without condensation)
IP20
RAL 7035
Color
Cable entry
Underside
Environmental conditions
COMMuNICAtION
Display
Free from corrosive air and conductive dust
320 x 240 graphical LCD display
Acoustic and visual
Alarm signals
Interfaces
Remote signal contact, RS232, 2 x communication slots for SNMP / Modbus / additional relay cards
DIMENSIONS
Dimensions approx. D x W x H (mm)
Footprint (m²)
910 x 520 x 1165
0.47
975 x 520 x 1655
0.51
Weight approx.
139 kg
204 kg
Weight approx. (incl. module)
1) by THDv ≤2 %
169 kg
199 kg
229 kg
259 kg
354 kg
384 kg
Protect
3.M 2.0
Intelligent
communication
Protect 3.M 2.0
Customer Benefits
Interfaces
Protect 3.M 2.0 contains a
powerful communications
module that readily supplies
all relevant information
(measurements, alarms
and error messages). All
information is supplied via
an easy to use LCD screen
»6 integrated remote signal
Modular concept
contacts
»The UPS output can be easily
»RS232 interface
adapted to any required
performance parameters.
»Two expansion slots for
additional remote signal
contacts, MODBUS
extension card and SNMP
adapter
»Rapid expansion by insertion
of new modules at any time
and without additional costs.
»N+1 redundancy module
large multi-language
lCD screen
increases reliability
Battery Management
low maintenance costs
Languages supported:
Each UPS power module
contains its own battery
charger with intelligent
charging electronics. These
can be adapted to the battery
in use and facilitate the use
of vendor independent
standard batteries.
»Module replacement in
case of failure within the
shortest possible time.
»German
»English
»French
»Spanish
»Portuguese
»Italian
»For multiple UPS devices,
module exchange between
units is possible.
»Turkish
High efficiency
»Russian
»Chinese
»Efficiency of 94% at 35% load
»Better efficiency means less
heat and thus lower running
costs for air conditioning
A temperature compensated
charging curve ensures
an optimum charging
regime. Automatic testing
informs you of the charging
state of charge and when
charging will be complete.
»Significant reduction
of CO2 emissions
AEG Power Solutions
Approach your local AEG Power Solutions
representative for further support.
Contact details can be found on:
|