BARD MANUFACTURING COMPANY, INC.
QW2S-QW5S Water-to-Air H/P
Engineering Specification Guide
1.0 GENERAL
Furnish and install a self-contained, vertical, floor standing, heat pump to
be manufactured by Bard Manufacturing Company, Inc. The unit shall be
approved and Listed by Intertek ETL Listed (ETL US/C). Unit shall be
factory assembled, pre-charged, pre-wired, tested and ready to operate.
Unit performance shall be AHRI Certified in accordance with ISO Standard
13256-1:1998 “Water to Air and Brine to Air Heat Pumps”, which includes
watt allowance for water pumping. Unit shall include 5 year parts warranty
covering compressor, parts, and heat exchange coils, subject to terms and
conditions of Bard Limited Warranty Agreement.
Unit efficiency shall be specified in terms of EER and COP.
Manufacturers: Capacities shall be as indicated on drawings and units
shall be manufactured by Bard Manufacturing Company, Inc. or prior
approved equal.
2.0 CONSTRUCTION FEATURES
2.1 CABINET
Constructed of 20 gauge pre-painted or vinyl laminated galvanized
steel. Choices available are either two-tone (vinyl) finish with “slate”
front panels and “platinum” cabinet for designer appearance, (gray)
or (beige) painted steel (select one). Vinyl finish is very resistant to
scratching and marring and is easy to clean. Tamper resistant
fasteners are provided for access panels. Unit includes built-in
rollers for each installation into wall sleeve and removal for service,
if necessary. Front panel is hinged and lockable for filter service and
access to primary functional electrical controls.
2.2 INSULATION
Cabinet is fully insulated with foil covered, high-density fiberglass
insulation with sealed edge treatment and special sound deadening
insulation material in the compressor section. All insulation is
designed to resist mold and mildew growth and facilitate ease of
cleaning.
F1915 (2012 04)
Page 1 of 6
standard. One shall be used for fresh water applications, the other
for protected (antifreeze) closed systems. The factory wired switch is
for fresh water.
Phase rotation protection and phase failure protection shall be
standard factory installed features on all equipment with three-phase
power. If unit is wired incorrectly phase monitor will lock out
compressor operation and red warning light shall energize. Once
power wiring is corrected at field power wiring location, a green light
will energize on phase monitor. If a phase of power is lost, the phase
monitor will also lock out.
2.9 SERVICE FEATURES
The unit shall include a diagnostic light to indicate when service is
required. System Service shall detect high or low-pressure control
operation.
3.0 LOOP MODULE PUMPING SYSTEM
All models shall be designed with mounting and wiring provisions
for field installed pump module option, when unit is applied with
ground loop system.
4.0 VENTILATION OPTIONS (Select One)
Q-Tec models are designed to provide optional ventilation packages to
meet all of your ventilation and indoor air quality requirements. All
ventilation packages are factory installed.
4.1 BAROMETRIC FRESH AIR DAMPER
STANDARD
The barometric fresh air damper is a standard feature on all models.
It allows outside ventilation air, up to 25% of the total airflow rating
of the unit, to be introduced through the air inlet openings and to be
mixed with the conditioned air. The damper opens during blower
operation and closes when the blower is off. Adjustable blade stops
allow different amounts of outside air to be introduced into the
building and can be easily locked closed if required.
4.2 BLANK OFF PLATE
OPTIONAL
A blank off plate covers the air inlet openings, which restrict any
outside air from entering the unit. The blank off plate should be
utilized in applications where outside air is not required to be mixed
with the conditioned air.
4.3 COMMERCIAL ROOM VENTILATOR
OPTIONAL
F1915 (2012 04)
Page 3 of 6
The built-in commercial room ventilator (CRV) is internally mounted
and allows outside ventilation air, up to 50% of the total air flow
rating of the unit, to be introduced through the air inlet openings. The
CRV shall be modular and easily added or removed from the unit
cabinet. It includes a built-in exhaust air damper. The damper can
be easily adjusted to control the amount of fresh air supplied into the
building. The CRV can be controlled by indoor blower operation or
field controlled based on room occupancy. Unit complies with
ANSI/ASHRAE Standard 62.1 Ventilation for Acceptable Air Quality.
Two Models Available: Spring Return on Power Loss or
Deactivation - Vent Option V
Power Return (will not close on power loss)
– Vent Option P
4.4 ENERGY RECOVERY VENTILATOR
OPTIONAL
The Energy Recovery Ventilator (ERV) shall consist of 1 or 2 rotary
wheels in an insulated cassette frame with seals, drive motor and
belt. The ERV assembly shall also include intake and exhaust
blowers. The entire assembly shall easily slide in or out of the unit
cabinet, allowing for maintenance or replacement. The total energy
wheel shall be coated with silica gel desiccant, permanently bonded
without the use of binders or adhesives. The coated segments shall
be washable with detergent or alkaline coil cleaner and water.
Desiccant shall not dissolve or deliquesce in the presence of water
or high humidity. All diameter and perimeter seals shall be provided
as part of the cassette assembly and shall be factory set. Drive belts
shall not require external tensioners or adjustment. Cassette wheels
shall include rims to prevent belts from slipping off wheels. Intake
and exhaust blowers shall have selections of high, medium or low
speed and selected independently, to allow for positive
pressurization if desired. The ERV cassette including parts and
media shall include 5year warranty subject to terms and conditions
of Bard’s warranty.
The ERV thermal performance shall be certified by the manufacturer
in accordance with ASHRAE Standard 84, Method of Testing Air-to
Air Heat Exchangers and ARI Standard 1060, Rating for Air-to-Air
Energy Recovery Ventilation Equipment Cassettes, and shall be
listed in the ARI Certified Products. Unit complies with
ANSI/ASHRAE Standard 62.1 Ventilation for Acceptable Air Quality.
.
5.0 FILTER OPTIONS - (Select One)
F1915 (2012 04)
Page 4 of 6
5.1 2” Fiberglass – Pleated – MERV 8
6.0 HOT GAS REHEAT- (Factory installed option)
6.1 The dehumidification circuit incorporates an independent heat
exchanger coil in the supply air stream in addition to the standard
evaporator coil. This coil reheats the supply air after it passes over
the cooling coil, and is sized to nominally match the sensible cooling
capacity of the evaporator coil.
Extended run times in
dehumidification mode can be achieved using waste heat from the
refrigeration cycle to achieve the reheat process, while at the same
time large amounts of moisture can be extracted from the passing air
stream.
7.0 CABINET COLOR – (Select One)
7.1 Washable Vinyl- Two-Tone Finish with Slate front and platinum sides
7.2 Slate Gray
7.3 Beige
9.0 CONTROLS – (Select one of the following factory mounted
control options)
9.1 None
9.2 Electronic non-programmable, manual changeover
9.3 Electronic programmable, auto changeover
9.4 Electronic programmable, auto changeover, with dehumidistat
9.5 Electronic non-programmable, auto changeover, with humidistat
10.0 ACCESSORIES
10.1 WALL SLEEVE
Wall sleeve shall be factory supplied and must be constructed of 16
gauge-galvanized steel, coated with an epoxy primer and baked-on
polyester enamel paint. It shall be designed to withstand a minimum
of 1000 hours of salt spray protection when tested per ASTM B117-03
standard. One sleeve size fits all models. Sleeve only required when
a ventilation option is selected.
10.2 Exterior Louver
Furnish factory louver designed for condenser air and outside air
F1915 (2012 04)
Page 5 of 6
intake and exhaust. Louver shall have a powder coat finish.
See our color chart for color selections. Louver required with sleeve
with the use of any ventilation option.
10.4 AIR DISTRIBUTION – (Select 1)
10.3.1
10.3.2
The Q-Tec shall have a discharge air plenum with
double deflection register mounted on front.
The Q-Tec shall have a discharge air plenum with
double deflection supply register on the front and both
sides.
10.3.3
The Q-Tec shall be ducted with a cabinet extension to
cover ductwork
11.0 WARRANTY
11.1 The Bard product specified shall be free from defects in materials
and workmanship for a period of 5 years for compressor, and for a
period of 5 years for all parts. Warranty period shall start from date
of installation as stated on warranty card; or from date of shipment if
no warranty card is returned to Bard Manufacturing. Equipment
must be used under normal conditions and warranty is subject to
Bard Manufacturing’s standard limited warranty statement.
12.0 INSTALLATION
12.1 Installation shall be done in strict adherence to Bard’s Installation
Instructions.
F1915 (2012 04)
Page 6 of 6
|