321 Studios Gas Grill FSAF24 User Manual

FSAF24(-S) US, FSAF120(-S) US  
On/Off, Spring Return, Meets 250°F [121°C] for Half Hour, 75 Seconds  
Torque min. 133 in-lb, for control of air dampers  
Application  
For two position control of UL555S rated dampers in HVAC. Actuator sizing should be  
done in accordance with the damper manufacturer’s specifications.  
The actuator is mounted directly to a damper shaft or jackshaft 3/8” to 1.05” in  
diameter by means of its universal clamp. A crank arm and mounting brackets are  
available if the actuator cannot be direct coupled to the jackshaft or damper shaft.  
Square footage of damper operated will depend on make and model of damper.  
Typically 12 sq.ft. minimum up to 24 sq.ft maximum will be operated for UL555S  
applications.  
Operation  
The FSAF series actuators provide true spring return operation for reliable fail-safe  
application and positive close-off on UL555S dampers. The spring return system  
provides constant torque to the damper with, and without, power applied to the  
actuator.  
The FSAF series provides 95° of rotation and is provided with a graduated position  
indicator showing 0 to 95°. The FSAF has a manual positioning mechanism which  
allows the setting of any damper position within its 95° of rotation.  
Technical Data  
Power supply  
FSAF24(-S) US, FSAF120(-S) US  
FSAF24(-S) US  
FSAF120(-S) US  
Power consumption  
FSAF24(-S) US  
24 VAC 20%, 24 VDC -10% +20%  
120 VAC 10%, 50/60 Hz  
The actuator is shipped in the zero fail-safe position to provide automatic compression  
against damper gaskets for tight shut-off. When power is applied, the manual  
mechanism is released and the actuator drives toward the  
running 7.5 W, 10 VA, .4 A  
open position where it stops rotating.  
holding 2 W, 4 VA, .15 A  
running 50/60Hz: 9.5 W, 11 VA, .1 A  
holding 3.5 W, 6 VA, .05 A  
The manual override can also be released physically by the use of a crank supplied  
with the actuator.  
FSAF120(-S) US  
Transformer sizing  
Electrical connection  
10 VA (Class 2 power source 24V only)  
motor 3 ft, 18 ga, 2 color coded leads  
1/2” conduit connectors  
SAFETY NOTE  
Screw a conduit fitting into the actuator’s bushing. Jacket the actuator’s input and  
output wiring with suitable flexible conduit. Properly terminate the conduit in a  
suitable junction box.  
-S models 3 ft, 18 ga, 4 leads appliance cable  
1/2” conduit connectors  
Overload protection  
Angle of rotation  
Torque  
Direction of rotation  
Position indication  
electronic throughout 0 to 95° rotation  
mechanically limited to 95°  
133 in-lb [15 Nm] constant  
Dimensions (Inches [mm])  
0.65" [16.5]  
spring reversible with cw/ccw mounting  
Standard:  
visual indicator, 0° to 95°  
(0° is spring return position)  
1/2" to 1.05"  
Manual override  
Running time  
3mm hex crank (shipped w/actuator)  
<75 sec. constant, independent of load  
spring <20 seconds nominal  
Optional*  
0.19" [5]  
3/8" to 3/4"  
Humidity  
5 to 95% RH non-condensing  
Ambient temperature  
3/8" to 5/8"  
10.59" [269]  
0.39" [10]  
0.35" [9]  
2.64"  
[67]  
normal duty -22°F to 122°F [-30°C to 50°C]  
safety duty 3 on/off cycles after 30 minutes at ambient  
temperature of 250°F [121°C]  
-40°F to 176°F [-40°C to 80°C]  
NEMA type 1 / IP40  
5.85" [148.5]  
0.26" [6.5]  
Storage temperature  
Housing  
Housing material  
Gears  
*with K4 US  
clamp  
zinc coated metal  
permanently lubricated  
cULus listed to UL873 and  
CAN/CSA C22.2 No.24  
1.97"  
[50]  
Agency listings  
Noise level (max)  
45 dB (A)  
spring return 62 dB  
Servicing  
Maintenance free  
Quality standard  
Weight  
ISO 9001, 5 year Belimo warranty  
(standard / -S model)  
FSAF24(-S) US  
FSAF120(-S) US  
5.7 / 6.2 lbs (2.6 / 2.8 kg)  
6.1 / 6.6 lbs (2.8 / 3 kg)  
FSAF24-S US, FSAF120-S US  
Auxiliary Switch  
2xSPST 7A resistive, 2.5A inductive at 120V or  
250V, UL Approved, double-insulated, one switch  
at 10°, one adjustable from 30° to 90°  
800-543-9038 USA  
866-805-7089 CANADA  
203-791-8396 LATIN AMERICA  
171  
 
FSAF230(-S) US  
On/Off, Spring Return, 250°F [121°C] for Half Hour, 75 Seconds  
Torque min. 133 in-lb, for control of air dampers  
Application  
For two position control of UL555S rated dampers in HVAC. Actuator sizing should be  
done in accordance with the damper manufacturer’s specifications.  
The actuator is mounted directly to a damper shaft or jackshaft 3/8” to 1.05” in  
diameter by means of its universal clamp. A crank arm and mounting brackets are  
available if the actuator cannot be direct coupled to the jackshaft or damper shaft.  
Square footage of damper operated will depend on make and model of damper.  
Typically 12 sq.ft. minimum up to 24 sq.ft maximum will be operated for UL555S  
applications.  
Operation  
The FSAF series actuators provide true spring return operation for reliable fail-safe  
application and positive close-off on UL555S dampers. The spring return system  
provides constant torque to the damper with, and without, power applied to the  
actuator.  
The FSAF series provides 95° of rotation and is provided with a graduated position  
indicator showing 0 to 95°. The FSAF has a manual positioning mechanism which  
allows the setting of any damper position within its 95° of rotation.  
Technical Data  
Power supply  
FSAF230(-S) US  
230 VAC 14%, 50/60 Hz  
The actuator is shipped in the zero fail-safe position to provide automatic compression  
against damper gaskets for tight shut-off. When power is applied, the manual  
mechanism is released and the actuator drives toward the  
Power consumption  
running 50/60Hz: 11 W, 12 VA, .07 A  
holding 3.5 W, 6 VA, .03 A  
open position where it stops rotating.  
Transformer sizing  
Electrical connection  
10 VA (Class 2 power source 24V only)  
motor 3 ft, 18 ga, 2 color coded leads  
1/2” conduit connectors  
The manual override can also be released physically by the use of a crank supplied  
with the actuator.  
-S models 3 ft, 18 ga, 4 leads appliance cable  
1/2” conduit connectors  
SAFETY NOTE  
Screw a conduit fitting into the actuator’s bushing. Jacket the actuator’s input and  
output wiring with suitable flexible conduit. Properly terminate the conduit in a  
suitable junction box.  
Overload protection  
Angle of rotation  
Torque  
electronic throughout 0 to 95° rotation  
mechanically limited to 95°  
133 in-lb [15 Nm] constant  
Direction of rotation  
Position indication  
spring reversible with cw/ccw mounting  
Dimensions (Inches [mm])  
visual indicator, 0° to 95°  
(0° is spring return position)  
0.65" [16.5]  
Manual override  
Running time  
3mm hex crank (shipped w/actuator)  
<75 sec. constant, independent of load  
spring <20 seconds nominal  
Standard:  
1/2" to 1.05"  
Humidity  
5 to 95% RH non-condensing  
Ambient temperature  
Optional*  
normal duty -22°F to 122°F [-30°C to 50°C]  
safety duty 3 on/off cycles after 30 minutes at ambient  
temperature of 250°F [121°C]  
-40°F to 176°F [-40°C to 80°C]  
NEMA type 1 / IP40 with flexible conduit  
zinc coated metal  
0.19" [5]  
3/8" to 3/4"  
3/8" to 5/8"  
10.59" [269]  
0.39" [10]  
0.35" [9]  
2.64"  
[67]  
Storage temperature  
Housing  
Housing material  
Gears  
5.85" [148.5]  
0.26" [6.5]  
permanently lubricated  
Agency listings  
cULus listed to UL873 and  
CAN/CSA C22.2 No.24  
*with K4 US  
clamp  
Noise level (max)  
45 dB (A)  
spring return 62 dB  
1.97"  
[50]  
Servicing  
Maintenance free  
Quality standard  
Weight  
ISO 9001, 5 year Belimo warranty  
6.9 lbs (3.1 kg)  
FSAF230-S US  
Auxiliary Switch  
2xSPST 7A resistive, 2.5A inductive at 120V or  
250V, UL Approved, double-insulated, one switch  
at <10°, one adjustable from >30° to 90°  
800-543-9038 USA  
866-805-7089 CANADA  
203-791-8396 LATIN AMERICA  
173  
 
FSAF230(-S) US  
On/Off, Spring Return, 250°F [121°C] for Half Hour, 75 Seconds  
Wiring Diagrams  
Accessories (AF series accessories may be employed)  
IND-AF2  
Damper position indicator  
K4 US  
K4-1 US  
K4-H  
Universal clamp for 3/8” to 3/4” shafts  
Universal clamp for up to 1.05” dia. jackshafts  
Universal clamp for hexshafts 3/8” to 5/8”  
Crank arm for up to 3/4” round shaft (Series 2)  
Crank arm for up to 1.05” jackshaft (Series 2)  
V-bolt kit for KH-AF and KH-AF-1  
10 mm wrench  
Angle of rotation limiter  
Universal mounting bracket  
Universal mounting bracket  
Multiple actuator mounting bracket  
Universal mounting bracket  
Provide overload protection and disconnect as required.  
1
KH-AF  
CAUTION Equipment Damage!  
Actuators may be connected in parallel.  
2
KH-AF-1  
KH-AFV  
Tool-01  
ZDB-AF2 US  
ZG-100  
ZG-101  
ZG-102  
ZG-103  
ZG-104  
ZG-106  
Power consumption and input impedance must be observed.  
Actuator may also be powered by 24 VDC.  
3
No ground connection required. Double insulated.  
4
For end position indication, interlock control, fan startup, etc., the  
FSAF230-S US incorporates two built-in auxiliary switches: 2 x SPST, 7A  
5
resistive, 2.5 inductive @120/250 VAC, UL Approved, one switch is fixed at  
10°, one is adjustable from 30° to 90°.  
Universal mounting bracket  
Mounting bracket for Honeywell Mod IV replacement or new  
®
crank arm type installations  
Mounting bracket for Honeywell Mod III or Johnson Series  
100 replacement or new crank arm type installations  
®
®
ZG-107  
ZG-108  
Meets UL requirements without the need of an electrical ground  
connection.  
®
®
Mounting bracket for Barber Colman MA 3../4.., Honeywell  
®
Meets cULus or UL and CSA Standard requirements without the  
need of an electrical ground connection.  
Mod III or IV or Johnson Series 100 replacement or new  
crank arm type installations  
Crank arm adaptor kit for AF/NF  
Crank arm adaptor kit for AF/NF  
Weather shield (metal)  
Weather shield (polycarbonate)  
NEMA 4X housing  
ZG-AF  
ZG-AF108  
ZS-100  
ZS-150  
ZS-300  
WARNING Live Electrical Components!  
During installation, testing, servicing and troubleshooting of this product, it may be  
necessary to work with live electrical components. Have a qualified licensed electrician or other  
individual who has been properly trained in handling live electrical components perform these  
tasks. Failure to follow all electrical safety precautions when exposed to live electrical compo-  
nents could result in death or serious injury.  
22965-00001  
12mm form fit square shaft adaptor  
For an overview of how to apply the accessories, see Belimo Mechanical Accessories and refer to the Belimo  
Mounting Methods Guide.  
NOTE: When using FSAFxx (-S) US actuators, only use accessories listed on this page.  
Typical Specification  
Large combination fire and smoke dampers are to be operated by Belimo FSAF  
series actuators. Manufacturer shall provide 5 year warranty.  
Actuators shall draw no more than 12VA at 230V or 10 VA at 24V.  
Where auxiliary switches are required for signaling, starting fans, or position indica-  
tion, -S model actuators, damper blade, or proximity switches shall be provided.  
Smaller dampers shall employ Belimo FSLF or FSNF actuators per damper manufac-  
turer recommendations.  
FSAF24 US and FSAF230 US  
Auxiliary switch  
800-543-9038 USA  
866-805-7089 CANADA  
 
203-791-8396 LATIN AMERICA  
174  
FSAF24-SR(-S) US  
Proportional, Spring Return, 24 V, 2 to 10 VDC or 4 to 20 mA control signal  
Operation at 250°F for limited time per UL555S testing  
Torque min. 133 in-lb, for control of air dampers  
Application  
For proportional modulation of UL555S rated dampers in HVAC. Actuator sizing should  
be done in accordance with the damper manufacturer’s specifications.  
The actuator is mounted directly to a damper shaft or jackshaft up to 1.05” in diameter  
by means of its universal clamp. A crank arm and mounting brackets are available if  
the actuator cannot be direct coupled to the jackshaft or damper shaft.  
The actuator operates in response to a 2 to 10 VDC, or with the addition of a  
500 Ω resistor, a 4 to 20 mA control input from an electronic controller or positioner.  
A 2 to 10 VDC feedback signal is provided for position indication or master-slave  
applications. See Application Bulletin for details.  
Operation  
The FSAF series actuators provide spring return operation. There is no reversing  
switch on the FSAF24-SR. It is direct acting only. A reverse acting signal is required if  
it must spring open while 2V signal drives it closed. The torque is asymmetrical giving  
180 in-lb drive and 133 in-lb spring.  
The FSAF resets after being driven or springing closed to the 0 position. There is a  
possible hysteresis of 1° every 1000 changes in signal. This can cause a position shift.  
It is recommended that power or signal be reset once a week.  
Technical Data  
Power supply  
FSAF24-SR(-S) US  
24 VAC 20% 50/60 Hz  
24 VDC 10%  
Power consumption  
running 7 W, 11 VA  
holding 3 W, 5 VA  
15 VA (class 2 power source)  
A manual override winder and locking mechanism is provided. If the manual winder is  
used when the actuator is powered, the actuator will release and drive closed to reset  
the 0 degree position.  
Transformer sizing  
Electrical connection  
The actuator may not be mechanically parallelled or “piggybacked.” Each damper  
section should be controlled by a separate actuator.  
FSAF24-SR  
FSAF24-SR-S  
Overload protection  
Operating range  
Input impedance  
Feedback output U  
Angle of rotation  
Torque  
3 ft, 18 GA, 4 color coded leads (24V)  
1/2” conduit connector  
3 ft, 18 GA appliance cable  
1/2” conduit connector  
electronic throughout 0 to 95° rotation  
2 to 10 VDC, 4 to 20mA  
100 kΩ (0.1 mA), 500 Ω  
2 to 10 VDC (max. 0.5 mA) for 95°  
mechanically limited to 95°  
133 in-lb [15 Nm] constant  
The wire 5 feedback can be used to parallel up to five additional actuators. If less than  
2.1 V or greater than 9.9V is given wire 3, actuator drives all the way to the respective  
end stop.  
The FSAF uses a DC motor which is controlled by a microchip The actuator may be  
stalled anywhere during its rotation without damage. If power is removed, the damper  
will spring closed. Interlocks must be provided as necessary for life safety functions  
and to shut down fan if required.  
SAFETY NOTE  
Direction of rotation  
spring reversible with cw/ccw mounting  
The control direction switch is not present. Direct  
acting only. 2 VDC=Fail-safe position.  
visual indicator, 0° to 95°  
Screw a conduit fitting into the actuator’s bushing. Jacket the actuator’s input and  
output wiring with suitable flexible conduit. Properly terminate the conduit in a  
suitable junction box.  
Position indication  
(0° spring return position)  
Manual override  
Running time  
3mm hex crank (shipped w/actuator)  
motor <75 sec. constant, independent of load  
spring < 20 seconds  
Dimensions (Inches [mm])  
0.65" [16.5]  
Standard:  
Humidity  
Ambient temperature  
5 to 95% RH non-condensing  
1/2" to 1.05"  
normal duty -22°F to 122°F [-30°C to 50°C]  
safety duty 3 on/off cycles after 30 minutes at ambient  
temperature of 250°F [121°C]  
-40°F to 176°F [-40°C to 80°C]  
NEMA type 2 / IP40  
Optional*  
3/8" to 3/4"  
0.19" [5]  
Storage temperature  
Housing  
Housing material  
Agency listings†  
Noise level (max)  
Servicing  
10.59" [269]  
5.85" [148.5]  
0.26" [6.5]  
zinc coated metal  
cULus to UL873 and CSA C22.2 No. 24-93  
running 45 db (A)  
0.39" [10]  
0.35" [9]  
2.64"  
[67]  
maintenance free  
Quality standard  
Weight  
ISO 9001, 5 year Belimo warranty  
6.0 lbs (2.7 kg.)  
*with K4 US  
clamp  
1.97"  
[50]  
FSAF24-SR-S US  
Auxiliary switch  
2 x SPDT 7A resistive, 2.5A inductive at  
120/250VAC. UL Approved, double-insulated,  
one set at =+10°, one adjustable 30° to 90°  
800-543-9038 USA  
866-805-7089 CANADA  
203-791-8396 LATIN AMERICA  
175  
 
FSAF24-SR(-S) US  
Proportional, Spring Return, 24 V, 2 to 10 VDC or 4 to 20 mA control signal  
Operation at 250°F for limited time per UL555S testing  
Accessories (AF series accessories may be employed)  
No ground connection required. Double insulated.  
4
5
6
IND-AF2  
Damper position indicator  
K4 US  
K4-1 US  
K4-H  
Universal clamp for 3/8” to 3/4” shafts  
Universal clamp for up to 1.05” dia. jackshafts  
Universal clamp for hexshafts 3/8” to 5/8”  
Crank arm for up to 3/4” round shaft (Series 2)  
Crank arm for up to 1.05” jackshaft (Series 2)  
V-bolt kit for KH-AF and KH-AF-1  
10 mm wrench  
Min. and/or max. positioner in NEMA 4 housing  
Min. and/or max. positioner for flush panel mounting  
500 Ω resistor for 0 to 20 mA control signal  
Angle of rotation limiter  
Only connect common to neg. (–) leg of control circuits.  
For end position indication, interlock control, fan startup, etc.,  
FSAF24-SR-S US incorporates two built-in auxiliary switches:  
2 x SPDT, 7A resistive, 2.5A inductive 120/250 VAC, UL Approved, one  
switch is fixed at 10°, one is adjustable 30° to 90°.  
KH-AF  
KH-AF-1  
KH-AFV  
Tool-01  
SGA24  
Meets UL requirements without the need of an electrical ground  
connection.  
SGF24  
ZG-R01  
ZDB-AF2 US  
ZG-100  
ZG-101  
ZG-102  
ZG-103  
ZG-104  
ZG-106  
The ZG-R01 500 Ω resistor converts the 4 to 20 mA control signal to  
2 to 10 VDC.  
Universal mounting bracket  
Universal mounting bracket  
Multiple actuator mounting bracket  
Universal mounting bracket  
WARNING Live Electrical Components!  
During installation, testing, servicing and troubleshooting of this product, it may be  
necessary to work with live electrical components. Have a qualified licensed electrician or other  
individual who has been properly trained in handling live electrical components perform these  
tasks. Failure to follow all electrical safety precautions when exposed to live electrical compo-  
nents could result in death or serious injury.  
Universal mounting bracket  
Mounting bracket for Honeywell Mod IV replacement or new  
®
crank arm type installations  
Mounting bracket for Honeywell Mod III or Johnson Series  
100 replacement or new crank arm type installations  
®
®
ZG-107  
ZG-108  
®
®
Mounting bracket for Barber Colman MA 3../4.., Honeywell  
®
Mod III or IV or Johnson Series 100 replacement or new  
crank arm type installations  
Crank arm adaptor kit for AF/NF  
Crank arm adaptor kit for AF/NF  
Weather shield (metal)  
Weather shield (polycarbonate)  
Explosion-proof housing  
ZG-AF  
ZG-AF108  
ZS-100  
ZS-150  
ZS-260  
ZS-300  
NEMA 4X housing  
For an overview of how to apply the accessories, see Belimo Mechanical Accessories and refer to the Belimo  
Mounting Methods Guide.  
NOTE: When using FSAF24-SR(-S) US actuators, only use accessories listed on this page.  
Typical Specification  
Proportional smoke, and combination fire and smoke dampers, shall be controlled by  
Belimo FSAF24-SR actuators. The control signal shall provide proportional damper  
control in response to a 2 to 10 VDC or, with the addition of a 500 Ω resistor, a 4 to  
20 mA control input from an electronic controller or positioner. The actuators must be  
designed so that they may be used for either clockwise or counter clockwise fail-safe  
operation. Actuator shall open damper in <75 seconds per UL555S and shall spring  
closed in under 20 seconds. Actuators shall be UL Approved, have a 5-year warranty,  
and be manufactured under ISO 9001 International Quality Control Standards.  
Actuators shall be as manufactured by Belimo. Actuators with auxiliary switches  
must be constructed to meet the requirement for double insulation so an electrical  
ground connection is not required to meet agency listings.  
Proportional control  
Replacement Application  
The number one “equal or better” requirement for use as a replacement for obsolete  
defective motors is the UL555S listing of the Belimo actuator with the damper for the  
application. The local authority having jurisdiction sets the requirements since UL  
has stated that they do not regulate replacements.  
Wiring Diagrams  
Provide overload protection and disconnect as required.  
1
CAUTION Equipment Damage!  
Actuators may be connected in parallel.  
2
Auxiliary switch  
Power consumption and input impedance must be observed.  
Actuator may also be powered by 24 VDC.  
3
800-543-9038 USA  
866-805-7089 CANADA  
 
203-791-8396 LATIN AMERICA  
176  
FSAF24-BAL(-S) US  
Spring Return, 24 V, 3-Position, 100% Open Override  
Operation at 250°F for limited time per UL555S testing  
Application  
For 3-position control of UL555S rated dampers in HVAC. Actuator sizing should be  
done in accordance with the damper manufacturer’s tests. In the absence of other  
information, use 10 in-lb of torque per square foot of area for opposed blade and 14  
in-lb for parallel blade fire and smoke dampers at 1000 fpm air velocity.  
The FSAF24-BAL is specifically designed to balance the air flow in ducts and  
simultaneously provide control of fire and smoke dampers. 0V = spring closed. 24V on  
wire 2, not 3 = drive to the potentiometer position (balanced flow). 24V on wire 3,  
regardless of the status of wire 2 = drive full open (smoke control extraction or  
pressurization). See Application Bulletin for details.  
Operation  
For 3-position control of UL555S rated dampers in HVAC. Actuator sizing should be  
done in accordance with the damper manufacturer’s tests. In the absence of other  
information, use 10 in-lb of torque per square foot of area for opposed blade and 14  
in-lb for parallel blade fire and smoke dampers at 1000 fpm air velocity.  
The FSAF24-BAL is specifically designed to balance the air flow in ducts and  
simultaneously provide control of fire and smoke dampers. 0V = spring closed. 24V on  
wire 2, not 3 = drive to the potentiometer position (balanced flow). 24V on wire 3,  
regardless of the status of wire 2 = drive full open (smoke control extraction or  
pressurization).  
Technical Data  
Power supply  
FSAF24-BAL(-S) US  
24 VAC 20% 50/60 Hz  
24 VDC 10%  
Power consumption  
running AC 9.5 VA 6.5W  
DC 6W  
holding AC 5 VA 3W  
DC 3W  
SAFETY NOTE  
The actuator contains no components which the user can replace or repair.  
Transformer sizing  
Electrical connection  
Overload protection  
Control signal  
10 VA (class 2 power source 24V only)  
Dimensions (Inches [mm])  
3 ft, 18 GA, 1/2” conduit connector  
electronic throughout 0 to 95° rotation  
24 VAC/DC 3-position  
0.65" [16.5]  
Angle of rotation  
Torque  
20° to 95°, pot adjustable  
133 in-lb [15 Nm]  
Direction of rotation  
Position indication  
spring reversible with cw/ccw mounting  
visual indicator, 0° to 95°  
0.19" [5]  
(0° spring return position)  
Manual override  
Running time  
3mm hex crank (shipped w/actuator)  
motor <75 seconds @ 250°F [121°C]  
spring < 20 seconds  
10.59" [269]  
5.85" [148.5]  
0.26" [6.5]  
0.39" [10]  
0.35" [9]  
2.64"  
[67]  
Humidity  
5 to 95% RH non-condensing  
-22°F to 122°F [-30°C to 50°C]  
-40°F to 176°F [-40°C to 80°C]  
NEMA type 1/IP40 (with flex conduit)  
zinc coated metal  
Standard  
½” to 1.05”  
Ambient temperature  
Storage temperature  
Housing  
Housing material  
Agency listings†  
Noise level (max)  
Optional  
1.97"  
[50]  
½”  
cULus to UL873 and CSA C22.2 No. 24-93  
running <45 dB(A)  
spring <62dB(A)  
Servicing  
maintenance free  
Quality standard  
Weight  
ISO 9001, 5 year Belimo warranty  
5.3 lbs (2.4 kg)  
5.7 lbs (2.6 kg) for -S model  
FSAF24-BAL-S US  
Auxiliary switch  
2 x SPDT 7A resistive, 2.5A inductive at  
120/250VAC. UL listed, double-insulated,  
one switch is set at 10°, one is adjustable  
30° to 90°  
800-543-9038 USA  
866-805-7089 CANADA  
203-791-8396 LATIN AMERICA  
177  
 
FSAF24-BAL(-S) US  
Spring Return, 24 V, 3-Position, 100% Open Override  
Operation at 250°F for limited time per UL555S testing  
Wiring Diagrams  
Accessories (AF series accessories may be employed)  
IND-AF2  
K4-1 US  
KH-AF  
Damper position indicator  
Universal clamp for up to 1.05” dia. jackshafts  
Crank arm for up to 3/4” round shaft (Series 2)  
Crank arm for up to 1.05” jackshaft (Series 2)  
V-bolt kit for KH-AF and KH-AF-1  
10 mm wrench  
Angle of rotation limiter  
Universal mounting bracket  
Universal mounting bracket  
Universal mounting bracket  
Universal mounting bracket  
Mounting bracket for Honeywell Mod IV replacement or new  
crank arm type installations  
Mounting bracket for Honeywell Mod III or Johnson Series  
100 replacement or new crank arm type installations  
Provide overload protection and disconnect as required.  
1
2
KH-AF-1  
KH-AFV  
Tool-01  
ZDB-AF2  
ZG-100  
ZG-101  
ZG-103  
ZG-104  
ZG-106  
CAUTION Equipment Damage!  
Actuators may be connected in parallel.  
Power consumption and input impedance must be observed.  
Actuator may also be powered by 24 VDC.  
3
4
Only connect Hot, Wire 2 to Wire 3 override control  
For end position, interlock control, fan start-up, etc., FSAF24-BAL-S  
incorporates two built-in auxiliary switches: 2 x SPDT, 7A resistive, 2.5A  
inductive 120/250 VAC, UL listed, one switch is fixed at 10°, one adjustable  
30° to 90°  
For end position indication, interlock control, fan startup, etc.,  
FSAF24-SR-S US incorporates two built-in auxiliary switches:  
2 x SPDT, 7A resistive, 2.5A inductive 120/250 VAC, UL Approved, one  
switch is fixed at 10°, one is adjustable 30° to 90°.  
®
5
6
®
®
ZG-107  
ZG-108  
®
®
Mounting bracket for Barber Colman MA 3../4.., Honeywell  
®
Mod III or IV or Johnson Series 100 replacement or new  
crank arm type installations  
Crank arm adaptor kit for AF/NF  
Crank arm adaptor kit for AF/NF  
Weather shield (metal)  
Weather shield (polycarbonate)  
NEMA 4X housing  
ZG-AF  
ZG-AF108  
ZS-100  
ZS-150  
ZS-300  
Meets UL requirements without the need of an electrical ground  
connection.  
6
7
22965-00001  
12 mm form fit square shaft adaptor  
Double insulated  
For an overview of how to apply the accessories, see Belimo Mechanical Accessories and refer to the Belimo  
Mounting Methods Guide.  
WARNING
Live Electrical Components!  
NOTE: When using FSAF24-BAL(-S) US actuators, only use accessories listed on this page.  
During installation, testing, servicing and troubleshooting of this product, it may be  
necessary to work with live electrical components. Have a qualified licensed electrician or other  
individual who has been properly trained in handling live electrical components perform these  
tasks. Failure to follow all electrical safety precautions when exposed to live electrical compo-  
nents could result in death or serious injury.  
Typical Specification  
Where indicated on drawings, combination fire and smoke and balancing dampers  
shall be controlled by Belimo FSAF24-BAL or equal actuators. The actuators must  
be designed so that they may be used for either clockwise or counter clockwise  
failsafe operation. Actuator shall open damper in <75 seconds per UL555S and shall  
spring closed in under 20 seconds. Actuators shall have a 5-year warranty and be  
manufactured under ISO9001 International Quality Control Standards.  
24 VAC Transformer  
1
3
Line  
Volts  
1 Blk Com  
2 Red Hot  
6
2
3 Override Open  
Actuator shall have an adjustable Maximum Opening Potentiometer which shall be  
used by the TAB contractor to adjust flow to that portion of the system fed by the  
damper.  
4
FSAF24-BAL US  
The actuator shall spring closed if either the smoke detector or alarm system  
removes power from it. Actuator shall spring closed if the primary temperature  
thermodisc opens due to high ambient of >165°F or as otherwise indicted on  
drawings.  
Override control  
S1  
5
NC  
The actuator shall drive full open if either the smoke control system 100% open  
override or Fire Fighters Smoke Control Station override is activated. Damper shall  
spring closed again if the thermodisc of a combination fire and smoke damper opens  
due to high temperature (typically 250°F).  
10°  
S2  
S3  
NO  
NC  
S4  
7
S5  
S6  
30° to 90°  
NO  
FSAF24-BAL-S US  
2
Auxiliary switch  
800-543-9038 USA  
866-805-7089 CANADA  
 
203-791-8396 LATIN AMERICA  
178  

Accusys Network Card ACS 61100 User Manual
AeroComm Network Card CL4490 1000 User Manual
AKG Acoustics Music Mixer AS 8 User Manual
Alliance Laundry Systems Washer LTS95AN User Manual
Altec Lansing Portable Speaker ADA880 User Manual
Amerec Stove PKLE 181 User Manual
AOC Flat Panel Television E941S User Manual
Ask Proxima Projector Pro AV 9500 User Manual
Barco Computer Monitor MD 4221 User Manual
Behringer Stereo Amplifier NU4 6000 User Manual