ABB COMMANDER 150 User Manual

User Guide  
COMMANDER 150  
Universal Process Indicator  
150  
COMMANDER  
A1  
A2  
A3  
8 8 8 8 8 8  
GETTING STARTED  
This manual is divided into 5 sections which contain all the information needed to  
install, configure, commission and operate the COMMANDER 150. Each section is  
identified clearly by a symbol as shown below.  
Displays and Controls  
Displays and function keys  
LED Indication  
Error Messages  
Operator Mode (Level 1)  
Operator menus for:  
Standard Indicator  
Totalizer/Batch Controller  
Maximum/Minimum/Average Indicator  
Set Up Mode (Level 2)  
Alarm trip points  
Totalizer functions  
8
Configuration Mode (Levels 3 and 4)  
Accessing the configuration levels  
Level 3  
Hardware assignment and input type  
Alarm types and hysteresis  
Operator functions and totalizer setup  
Digital input and serial communications  
Level 4  
Ranges and passwords  
Installation  
Siting  
Mounting  
Electrical connections  
Symbol Identification and Section Contents  
1
CONTENTS  
GETTING STARTED ...............................................................................................1  
1
DISPLAYS AND FUNCTION KEYS ..................................................................3  
1.1 Introduction ...............................................................................................3  
1.2 Use of Function Keys .................................................................................4  
1.3 LED Alarms and Indicators ........................................................................5  
1.4 Error Messages .........................................................................................6  
2
OPERATOR MODE ...........................................................................................7  
2.1 Introduction ...............................................................................................7  
2.2 Operating Page – Standard (Level 1) .........................................................8  
2.3 Operating Page – Totalizer (Level 1) ..........................................................9  
2.4 Operating Page – Maths Functions (Level 1) ...........................................11  
3
4
SET UP MODE ............................................................................................... 13  
3.1 Introduction .............................................................................................13  
3.2 Setup Level (Level 2) ..............................................................................14  
CONFIGURATION MODE ...............................................................................18  
4.1 Introduction .............................................................................................18  
4.2 Accessing the Configuration Mode..........................................................18  
4.3 Basic Hardware and Configuration (Level 3)............................................20  
4.3.1  
4.3.2  
4.3.3  
4.3.4  
Hardware Assignment and Input Type ........................................20  
Alarms .......................................................................................22  
Operator Functions and Totalizer Set Up ....................................24  
Digital Input and Serial Communications ....................................26  
4.4 Ranges and Passwords (Level 4) ............................................................28  
5
INSTALLATION .............................................................................................. 31  
5.1 Siting ....................................................................................................... 31  
5.2 Mounting..................................................................................................33  
5.3 Electrical Connections ............................................................................ 35  
5.4 Relays, Arc Suppression, Inputs and Outputs .........................................35  
5.4.1  
5.4.2  
5.4.3  
5.4.4  
5.4.5  
Relay Contact Ratings ...............................................................35  
Arc Suppression ........................................................................35  
Logic Output ..............................................................................35  
Retransmission Analog Output ...................................................35  
Digital Input ................................................................................35  
2
1
DISPLAYS AND FUNCTION KEYS  
Information.  
The fold-out page inside on the back cover of this manual  
shows all the frames in the programming levels. Space is  
provided on the page for writing the programmed setting or  
selection for each frame.  
1.1 Introduction – Fig. 1.1  
The COMMANDER 150 front panel display, function keys and LED indicators are  
shown in Fig. 1.1.  
Alarm LEDs  
A1  
(secret-til-lit)  
A2  
Display  
A3  
888888  
Function Keys  
Parameter Advance  
Raise  
Lower  
Multi-function Key  
Fig. 1.1 Front Panel Display, Function Keys and Indicators  
3
…1 DISPLAYS AND FUNCTION KEYS  
1.2 Use of Function Keys – Fig. 1.2  
A – Raise and Lower Keys  
+
1000  
1001  
999  
LEVEL2  
or…  
Use to change/set a parameter value…  
LEVEL1  
…move between levels  
B – Parameter Advance Key  
Frame 1  
(top of level)  
LEVEL1  
LEVELx  
1001  
2002  
3003  
4 004  
or…  
Frame 2  
1001  
Press and  
hold  
Use to advance to the next  
frame within a level…  
…select the top (LEVEL) frame  
from within a level  
Note. This key also stores any changes made in the previous frame  
C – Multi-function Key  
CodE  
or…  
1234 56  
0
Use to view a parameter setting or selection…  
…select individual characters in a frame  
Fig. 1.2 Use of Function Keys  
4
1
DISPLAYS AND FUNCTION KEYS…  
1.3 LED Alarms and Indicators  
COMMANDER  
150  
Alarm LEDs  
A1  
Alarm 1  
A2  
A3  
Alarm 2  
Alarm 3  
LED  
Status  
All Flashing  
• Indicator is in the configuration mode – see Section 4.2.  
A1, A2 and A3  
• Flashes when Alarm is active (off when inactive).  
• Lit constantly when Alarm 1 is an active latched alarm which has  
been acknowledged  
Fig. 1.3 LED Alarms and Indicators  
5
…1 DISPLAYS AND FUNCTION KEYS  
1.4 Error Messages  
To Clear Display  
Display  
Error/Action  
Press the  
key  
Calibration error  
CALErr  
Turn mains power off and on again  
(if the error persists contact the  
Service Organization).  
Press the  
key  
Configuration error  
CFGErr  
Ad Err  
The configuration and/or setup  
data for the instrument is  
corrupted. Turn mains power off  
and on again (if error persists,  
check configuration/setup settings).  
Turn power on and  
off again. If the error  
persists, contact the  
Service Organization  
A to D Converter Fault  
The analog to digital converter is  
not communicating correctly.  
Restore valid  
input  
Process Variable Over/Under  
Range  
9999  
Contact the Service  
Organization  
Option board error  
Communications to the option  
board have failed.  
DPtErr  
6
2
OPERATOR MODE  
2.1 Introduction  
Operator Mode (Level 1) is the normal day-to-day mode of the COMMANDER 150.  
Frames displayed in level 1 are determined by the indicator functions which are  
selected during configuration of the instrument – see Section 4.  
Note. Only the operating frames relevant to the configured functions are  
displayed in Operator Mode.  
The three indicator functions are:  
Standard Indicator  
page 8  
page 9  
page 11  
Indicator with Totalization  
Indicator with Max./Min./Average  
7
…2 OPERATOR MODE  
2.2 Operating Page – Standard (Level 1)  
Process Variable  
214 53  
Normally displayed in engineering  
214 53  
units.  
To view the process variable in  
276  
electrical units, press the  
key.  
UN-ACK•1  
Global Alarm Acknowledge (latch alarms only)  
UN-ACK  
ACK  
.
alarm unacknowledged  
acknowledged  
.
Security Code  
Enter the correct code to access the setup level  
(Level 2).  
CodE  
------  
[0 to 9999]  
Level 1  
LEVEL1  
Note. To select to this frame from anywhere in  
this level, press the  
key for a few seconds.  
•1 Only displayed if there is an active latch alarm.  
8
2
OPERATOR MODE…  
2.3 Operating Page – Totalizer (Level 1)  
These frames are only displayed if the totalizer function is enabled in the configuration  
level – see Section 4.3.3  
214 53•1  
Process Variable  
To view the input value (in electrical units) press the  
key.  
ACK-n  
Global Alarm Acknowledge (latch alarms only)  
UN-ACK  
ACK  
.
alarm unacknowledged  
acknowledged  
.
1234 56•1  
rSt-n  
Totalizer Value  
When this frame is selected the current counter status  
is displayed (t–GOor t-StOP).  
Stop/Start  
t–GO  
t-StOP  
start totalizer  
stop totalizer  
Reset  
rSt-Y – reset totalizer  
rSt-n – do not reset totalizer  
To reset the totalizer, select rSt-Ythen press the  
key.  
Continued on next page.  
•1 Totalizer stop/go and reset from these frames can be disabled  
Section 4.3.3.  
see  
A digital input can also be used to start/stop or reset the totalizer – see Section  
4.3.4  
9
…2 OPERATOR MODE  
…2.3 Operating Page – Totalizer (Level 1)  
Preset Total  
PrESEt  
This is the value the batch total is set to when it is reset  
•1  
000000  
[000000 to 999999 flow units]  
Select Digit  
Predetermined Total  
PrEdEt•2  
When the predetermined total is reached the batch  
total is reset (with wrap on) or stops (wrap off),  
depending on the wrap setting – see Section 3.2.  
•1  
999999  
[000000 to 999999 flow units]  
Select Digit  
Security Code  
Enter the correct code to access the setup level.  
CodE  
------  
[0 to 9999]  
Level 1  
LEVEL  
Note. To select to this frame from anywhere in  
this page, press the  
key for a few seconds.  
•1 The predetermined value should be greater than the preset value when the  
totalizer is counting up and lower than the preset value when the totalizer is  
counting down.  
•2 Only displayed if enabled in the configuration level – see Section 4.3.3.  
10  
2
OPERATOR MODE…  
2.4 Operating Page – Maths Functions (Level 1)  
Note. It is possible to have totalizer and maths functions together.  
Process Variable  
214 53  
To view the input value (in electrical units) press the  
key.  
UN-ACK  
Global Alarm Acknowledge (latch alarms only)  
UN-ACK  
ACK  
.
alarm unacknowledged  
acknowledged  
.
Average Value  
This is the mean average value of the process variable  
input, since the average was reset.  
A 14 05•1  
rSt-n  
rSt-Y – reset  
rSt-n – do not reset  
To reset the average value, select rSt-Ythen press  
the  
key.  
H 1502  
Continued on next page.  
•1 This frame can be disabled – see Section 4.3.3.  
The average value is reset automatically on power-up and can also be reset from  
a digital input – see Section 4.3.4.  
The reset function in this frame can be disabled – see Section 4.3.3.  
11  
…2 OPERATOR MODE  
…2.4 Operating Page – Maths Functions (Level 1)  
•1  
Maximum Value  
This is the maximum value of the process variable since  
the maximum was reset.  
H 1502  
rSt-Y – reset  
rSt-n – do not reset  
rSt-n  
To reset the maximum value, select rSt-Ythen press  
the  
key.  
•1  
Minimum Value  
This is the minimum value of the process variable since  
the minimum was reset.  
L1308  
rSt-Y – reset  
rSt-n – do not reset  
rSt-n  
To reset the minimum value, select rSt-Ythen press  
the  
key.  
Security Code  
Enter the correct code to access the setup level.  
CodE  
------  
LEVEL1  
[0 to 9999]  
Level 1  
Note. To select to this frame from anywhere in  
this page, press the  
key for a few seconds.  
•1 This frame can be disabled – see Section 4.3.3.  
The Max. and Min. values are reset automatically on power-up and can also be  
reset from a digital input – see Section 4.3.4.  
The reset reset function in this frame can be disabled – see Section 4.3.3.  
12  
8
3
SET UP MODE  
3.1 Introduction  
To access the Setup Level (Level 2) the correct password must be entered in the  
security code frame (CodE) in Level 1– see Fig. 3.1.  
Level 2 – Set Up  
LEVEL2  
Alarm 1 Trip Point  
A1xx  
Correct  
Password  
Level 1 –  
Operating Level  
LEVEL1  
CodE x  
Alarm 2 Trip Point  
Alarm 3 Trip Point  
Batch Total  
A2xx  
A3xx  
Security  
Code  
1234 56  
t-GO  
Totalizer Stop/Go  
Secure Total/Reset  
Preset Batch Total  
SECtot  
PrESEt  
PrEdEt  
A xxxx  
H xxxx  
L xxxx  
0AdJ  
Predetermined Batch  
Total  
Average Value  
Maximum Value  
Minimum Value  
Offset Adjustment  
Fig. 3.1 Accessing the Setup Level (Level 2)  
13  
8
…3 SET UP MODE  
3.2 Setup Level (Level 2)  
Level 2  
LEVEL2  
Note. To select to this frame from anywhere in  
this level, press the key for a few seconds.  
•1  
Alarm 1 Trip Point  
Alarm type:  
A1hP  
1001  
A1  
A1  
A1  
A1  
.
.
.
.
hP = High process alarm  
LP = Low process alarm  
H L = Latched high process alarm  
LL = Latched low process alarm  
[In engineering units]  
A1 H YS•2  
125  
Alarm 1 Hysteresis Value  
[In engineering units]  
•1  
Alarm 2 Trip Point  
Alarm type  
A2LP  
[In engineering units]  
2002  
A2 H YS•2  
Alarm 2 Hysteresis Value  
[In engineering units]  
279  
A3hP  
Continued on next page.  
•1 Not displayed if the alarm is disabled (Noneselected) – see Section 4.3.2.  
•2 Only displayed if custom alarm hysteresis is selected – see section 4.3.2  
14  
8
3
SET UP MODE…  
…3.2 Setup Level (Level 2)  
•1  
Alarm 3 Trip Point  
Alarm type  
A3hP  
[In engineering units]  
Alarm 3 Hysteresis Value  
[In engineering units]  
3003  
A3 H YS•2  
34 6  
1234 56•3  
rSt-n  
Totalizer Value  
rSt-Y – reset  
rSt-n – do not reset  
•4  
To reset the maximum value, select rSt-Ythen press  
the key.  
•3  
Totalizer Stop/Go  
t-GO  
t-GO  
t-StOP  
start totalizer  
stop totalizer  
t-StOP  
Setting to t-GOstarts the totalizer counting towards  
the predetermined value. Setting to t-StOPholds the  
totalizer at its present value.  
SECtOt  
Continued on next page  
•1 Not displayed if the alarm is disabled (Noneselected) – see section 4.3.2  
•2 Only displayed if custom alarm hysteresis is selected – see section 4.3.2  
•3 Only displayed if enabled in the Configuration Level – see section 4.3.3  
•4 A digital input can also be used to reset the batch total.  
15  
8
…3 SET UP MODE  
…3.2 Set Up Level (Level 2)  
SECtOt•1  
Secure Total  
The secure total is independent of the batch total value.  
When 999999 or 000000 is reached, the total is reset  
and then continues counting.  
Total  
4 56789  
rSt-n  
Reset  
rSt-Y – reset totalizer  
rSt-n – do not reset totalizer  
To reset, select rSt-Ythen press the  
key.  
PrESEt•2  
Preset Batch Total  
This is the value the batch total is set to when it is reset.  
[000000 to 999999]  
000000  
PrEdEt•2  
Predetermined Batch Total  
When this value is reached the batch total either resets  
(with wrap on) or stops (wrap off) – see Section 4.3.3.  
[000000 to 999999]  
999999  
A14 05  
Continued on next page.  
•1 Only displayed if enabled in the Configuration Level – see Section 4.3.3.  
•2 The preset value must be lower than the predetermined value when counting up,  
and greater than the predetermined value when counting down.  
16  
8
3
SET UP MODE…  
…3.2 Set Up Level (Level 2)  
Average Value  
This is the mean average value of the process variable  
input since the average was reset.  
•1  
A14 05  
rSt-Y – reset  
rSt-n – do not reset  
rSt-n  
To reset, select rSt-Ythen press the  
key.  
Maximum Value  
This is the maximum value of the process variable since  
the maximum was reset.  
•2  
H 1502  
rSt-Y – reset  
rSt-n – do not reset  
rSt-n  
To reset, select rSt-Ythen press the  
key.  
Minimum Value  
This is the minimum value of the process variable since  
the minimum was reset.  
•2  
L1308  
rSt-Y – reset  
rSt-n – do not reset  
rSt-n  
To reset , select rSt-Ythen press the  
key.  
Offset Adjustment  
An offset can be applied to the process variable input to  
enable spot calibration or the removal of system errors.  
OAdJ  
10  
[ 10% of engineering range]  
•1 The average value is reset automatically on power-up and can also be reset from  
a digital input – see Section 4.3.4.  
•2 The maximum and minimum values are reset automatically on power-up and can  
also be reset from a digital input – see Section 4.3.4.  
17  
4
CONFIGURATION MODE  
4.1 Introduction  
The Configuration Mode comprises two levels (3 and 4) as shown in Fig. 4.2.  
Configuration level 3 is divided into four frames. For most simple applications it is only  
necessary to set up the parameters in the first frame.  
Note.  
When in the configuration level:  
All the LED indicators flash.  
All relays and logic outputs are turned off.  
The analog output reverts to 0% (4mA) output level.  
4.2 Accessing the Configuration Mode – Fig. 4.1  
To access the Configuration Mode set the security switch to the 'Configure' position  
(levels 1 and 2 cannot be accessed from this setting). When the configuration  
parameters are programmed, reset the security switch to the 'Normal' position and  
the Operating page is displayed automatically .  
Normal  
Configure  
Fig. 4.1 Accessing the Configuration Mode  
18  
4
CONFIGURATION MODE…  
Level 4  
LEVEL4  
Engineering  
ENG H I  
Level 3  
LEVEL3  
Range High  
Engineering  
ENG LO  
Hardware  
Configuration  
A 1KC0  
Range Low  
b 1KC0  
C 1KC0  
d 1KC0  
Retransmission  
rEt H I  
Range High  
Retransmission  
rEt LO  
Alarms and  
Set Points  
E 0000  
Range Low  
F 0000  
G 0000  
H 0000  
Totalizer Count  
High  
CNt H I  
Custom Operator  
Settings  
Totalizer Count  
CUtOFF  
J 0000  
Cut-off  
K 0000  
L 0000  
N 0000  
Set-up Password  
PASSrd  
Modbus Address  
Digital Input and  
Serial Comms.  
Addr  
P 0000  
r 0000  
S 0000  
t 0000  
Fig. 4.2 Configuration Levels  
19  
…4 CONFIGURATION MODE  
4.3 Basic Hardware and Configuration (Level 3) – Fig. 4.3  
4.3.1 Hardware Assignment and Input Type  
Level 3  
LEVEL3  
Note. To select to this frame from anywhere in  
this level, press the key for a few seconds.  
'ABCD' Settings  
A 1KC0  
b 1KC0  
The first character (A, b, Cor d) identifies the parameter  
to be changed. The current setting is indicated by a  
flashing letter. Parameter options are shown in Fig. 4.3.  
C 1KC0  
A
b
C
d
=
=
=
=
Hardware configuration  
Input type and range  
Temperature units  
d 1KC0  
No. of decimal points  
Note 1. The temperature ranges default to their  
maximum values when the input type is changed.  
Note 2. For custom settings contact the local  
distributor.  
E 1203  
Continued on page 22.  
Information.  
Count High Calculation  
actual engineering flow rate  
flow range time units (in seconds)  
Convert flow rate into units/sec =  
units/sec  
Count High =  
resultant must be >0.001 and <99.999pps.  
counter factor  
Counter factor is the engineering value of the least significant digit shown on the  
totalizer display – see Section 4.3.3.  
Totalizer Count Pulse  
The totalizer count pulse is on for a preset time of 250ms and off for a minimum of  
250ms.  
20  
4
CONFIGURATION MODE…  
A – Hardware Configuration  
A 1KC0  
50Hz/60Hz  
Relay 1  
Source  
Relay 2*  
Source  
Relay 3*  
Source  
Logic O/P  
Source  
Analog O/P  
Source  
1
2
3
4
A
b
C
d
E
Alarm 1  
Alarm 1  
TCP**  
Alarm 2  
Alarm 2  
Alarm 1  
Alarm 1  
Alarm 2  
Custom  
Alarm 3  
Alarm 3  
Alarm 2  
Alarm 2  
Alarm 3  
Custom  
TCP**  
PV  
PV  
PV  
PV  
TWP**  
TWP**  
TCP**  
TCP**  
Custom  
TWP**  
5
Alarm 1  
Custom  
PV Average  
Custom  
U
TCP = Totalizer Count Pulse  
TWP = Totalizer Wrap Pulse  
PV = Process Variable  
*
Only available if the appropriate option board is fitted.  
** Pulse energizes assigned relay  
B – Input Type and Range Configuration  
b 1KC0  
Display  
Display  
b
E
J
K
N
r
S
t
P
THC Type B  
1
2
3
4
6
7
U
0 to 20 mA  
4 to 20 mA  
0 to 5 V  
1 to 5 V  
0 to 50 mV  
4 to 20 mA (square root lineariser)  
Custom Configuration  
THC Type E  
THC Type J  
THC Type K  
THC Type N  
THC Type R  
THC Type S  
THC Type T  
PT100 RTD  
C – Temperature Units  
Temperature Units  
D – Process Variable  
Display Decimal Places  
C 1KC0  
d 1KC0  
Display  
Display  
C
F
0
Degrees C*  
Degrees F*  
No temperature units  
0
1
2
3
4
xxxx  
xxx . x  
xx . xx  
x . xxx  
x . xxxx  
* Temperature inputs only  
Fig. 4.3 Hardware Configuration and Input/Output Ranges  
21  
…4 CONFIGURATION MODE  
4.3.2 Alarms – Figs. 4.4 and 4.5  
Note. Relays assigned to alarms are de-energized in the alarm state.  
'EFGH' Settings  
E 0000  
The first character (E, F, Gor H) identifies the parameter  
to be changed. The current setting is indicated by a  
flashing letter. Parameter options are shown in Fig. 4.5.  
F 0000  
G 0000  
E
F
G
H
=
=
=
=
Alarm 1 type  
Alarm 2 type  
Alarm 3 type  
Alarm hysteresis  
H 0000  
Note. For custom settings contact the local  
distributor.  
J 0000  
Continued on page 24.  
Hysteresis  
Trip point  
Hysteresis  
Process  
Variable  
Alarm on  
Alarm off  
High Process  
Alarm on  
Alarm off  
Low Process  
Information.  
For latch alarms the relay remains de-energized until acknowledged in  
Level 1 (or by a digital input).  
Fig. 4.4 Alarm Action  
22  
4
CONFIGURATION MODE…  
E – Alarm 1 Type  
E 0000  
Display  
0
1
2
3
4
None  
High Process  
Low Process  
High Latch  
Low Latch  
F – Alarm 2 Type  
G – Alarm 3 Type  
F 0000  
G 0000  
Display  
Display  
0
1
2
3
4
None  
High Process  
Low Process  
High Latch  
Low Latch  
0
1
2
3
4
None  
High Process  
Low Process  
High Latch  
Low Latch  
H – Alarm Hysteresis  
h 0000  
Note. When custom alarm  
Display  
hysteresis is selected, the alarm  
hysteresis values are set  
individually in the Set Up Level –  
See section 3.2.  
0
1
2
3
4
5
6
U
None  
0.1%  
0.2%  
0.5%  
1.0%  
2.0%  
5.0%  
Custom  
Value in % of  
engineering range  
Value in engineering units  
Fig. 4.5 Alarm Setup  
23  
…4 CONFIGURATION MODE  
4.3.3 Operator Functions and Totalizer Set Up – Fig. 4.6  
'JKLN' Settings  
The first character (J, K, Lor n) identifies the parameter  
J 0000  
to be changed. The current setting is indicated by a  
flashing letter. Parameter options are shown in Fig. 4.6.  
K 0000  
L 0000  
n 0000  
J
K
L
n
=
=
=
=
Totalizer set-up  
No. of decimal places for totalizer  
Operator level frame enable  
Operator level functions enable/disable  
Note. For custom settings contact the local  
distributor.  
P 0000  
Continued on page 26.  
24  
4
CONFIGURATION MODE…  
J – Totalizer Setup  
K – Totalizer Display  
Decimal Places  
J 0000  
K 0000  
Display  
Display  
0
1
2
3
4
Off  
0
1
2
3
4
xxxxxx  
xxxxx.x  
xxxx.xx  
xxx.xxx  
xx.xxxx  
x.xxxxx  
Count Up, Wrap Off  
Count Up, Wrap On  
Count Down, Wrap Off  
Count Down, Wrap On  
5
L – Operator Level Frame Enable  
L 0000  
Display Max/Min Values  
Displayed  
Average Value  
Displayed  
Preset/Predetermined  
Values Displayed  
0
1
2
3
4
No  
Yes  
Yes  
No  
No  
Yes  
Yes  
No  
No  
Yes  
Yes  
No  
No  
Yes  
No  
No  
No  
Yes  
Yes  
Yes  
Yes  
5
6
This frame determines which frames appear in the operating page (level 1)  
N – Operator Level Math Function & Totaliser Control Enable  
n 0000  
Display Totalizer Stop/Go Totalizer Reset  
Max./Min./Average  
0
1
2
3
4
No  
Yes  
No  
Yes  
No  
No  
No  
Yes  
No  
Yes  
Yes  
No  
No  
No  
Yes  
Yes  
Yes  
5
Yes  
This frame determines which functions the operator can control  
Fig. 4.6 Totalizer Setup and Operator Functions  
25  
…4 CONFIGURATION MODE  
4.3.4 Digital Input and Serial Communications – Figs. 4.7 and 4.8  
'PRST' Settings  
P 0000  
The first character (P, r, Sor t) identifies the parameter  
to be changed and the current setting is indicated by a  
flashing letter. Parameter options are shown in Fig. 4.8.  
r 0000  
S 0000  
P
r
S
t
=
=
=
=
Digital input function  
Analog input filter  
Serial communications configuration  
Serial communications parity  
t 0000  
Note. For custom settings contact the local  
distributor.  
LEVEL4  
Continued on page 28.  
Lock  
Unlock  
Reset  
4
5
Front Panel Lock out  
1
Totalizer Reset  
Stop  
Acknowledge  
Go  
2
Totalizer Stop/Go  
Alarm Acknowledge  
Max  
Min  
3
Average Max/Min Reset  
Information.  
Digital input options 1, 2, 3 and 5 are edge-triggered to enable the front  
panel keys to change the function when the digital input is operational.  
Fig. 4.7 Digital Function Configuration  
26  
4
CONFIGURATION MODE…  
P – Digital Input Function  
R – Analog Input Filter  
P 0000  
r 0000  
Display  
Display  
0
1
2
3
4
None  
Totalizer Reset  
Totalizer Stop/Go  
Average, Max/Min Reset  
Front Panel Lockout  
Alarm Acknowledge  
0
1
2
5
A
b
C
0 seconds  
1 second  
2 seconds  
5 seconds  
10 seconds  
20 seconds  
40 seconds  
60 seconds  
5
d
S – Serial Communication  
Configuration  
T – Serial Communication  
Parity  
S 0000  
t 0000  
Display Baud Rate, 2/4 Wire  
Display  
0
1
2
3
4
Off  
0
1
2
None  
Odd  
Even  
2400, 2 Wire  
2400, 4 Wire  
9600, 2 Wire  
9600, 4 Wire  
Note. Settings for options P, S and T are only available if the  
appropriate option board is fitted.  
Fig. 4.8 Digital Function and Serial Communications Configuration  
27  
…4 CONFIGURATION MODE  
4.4 Ranges and Passwords (Level 4)  
Level 4  
LEVEL4  
Note. To select to this frame from anywhere in  
this level, press the key for a few seconds.  
Engineering (Display) Range  
High Value  
ENG H I  
1000•1  
[–9999 to 99999]  
Low Value  
ENG LO  
00•1  
[–9999 to 99999]  
CNt H I  
Continued on next page…  
•1 The engineering range high and low values are automatically set to the maximum  
allowed value when thermocouple or RTD is selected in the configuration level –  
see Section 4.3.1. This value can be modified if required.  
28  
4
CONFIGURATION MODE…  
…4.4 Ranges and Passwords (Level 4)  
Retransmission Range  
The retransmission range defines the the engineering  
range to be retransmitted.  
High (20mA output)  
rEt H I  
1000•1  
[–9999 to 99999 (in engineering units)]  
Low (4mA output)  
rEt LO  
1000•1  
[–9999 to 99999 (in engineering units)]  
CNt H I  
Continued on next page…  
•1 The retransmission range high and low values are automatically set to the  
maximum allowed value when thermocouple or RTD is selected in the  
configuration level – see Section 4.3.1. This value can be modified if required.  
29  
…4 CONFIGURATION MODE  
…4.4 Ranges and Passwords (Level 4)  
CNt H I•1  
Totalizer Count High  
This frame determines the count corresponding to the  
full-scale input.  
[0.000 and 99.999 pulses/second]  
100  
cutoFF•1  
1000  
Cut-off  
This frame sets the lowest flow value at which the  
totalizer is to stop counting.  
[In engineering units]  
Setup Password  
This password enables access to the setup level (levels  
2).  
PASSrd  
[0 to 9999]  
0
•2  
Modbus Address  
This frame sets the Modbus address.  
Addr  
[1 to 99]  
1
•1 Only displayed if enabled in the configuration level – see Section 4.3.3.  
•2 Only available if the appropriate option board is fitted.  
30  
5
INSTALLATION  
5.1 Siting – Figs. 5.1 and 5.2  
Close to Sensor  
Sensor  
At Eye Level  
Avoid Vibration  
Fig. 5.1 Siting – General Requirements  
31  
…5 INSTALLATION  
…5.1 Siting – Figs. 5.1 and 5.2  
Temperature Limits  
55°C  
Max.  
0°C  
Min.  
Humidity Limits  
0 to 90% RH  
Environmental Limits  
IP65/NEMA3  
(front panel)  
IP20  
(rear)  
Use Screened Cable  
+
Fig. 5.2 Environmental Requirements  
32  
5
INSTALLATION…  
5.2 Mounting – Figs. 5.3 and 5.4  
The instrument is designed for panel mounting (see Fig. 5.4). Overall dimensions are  
shown in Fig. 5.3.  
Dimensions in inches (mm)  
0.28 (7.1)  
4.68 (119)  
1.57 (40  
)
3.11 (79)  
1.76  
(44.6)  
0.11 (2.7)  
3.78 (96)  
1.89  
+ 0.03  
– 0  
3.62  
(92  
+ 0.8  
)
– 0  
+ 0.6  
– 0  
Panel  
(45  
)
cut-out  
+ 0.02  
– 0  
1.77  
0.55 (14)  
0.55  
(14)  
Fig. 5.3 Overall Dimensions  
33  
…5 INSTALLATION  
…5.2 Mounting – Figs. 5.3 and 5.4  
Cut a suitable hole in the panel (see Fig. 5.3)  
1
2
Insert the instrument into the panel cut-  
out  
3
Fit the retaining clamp  
over the instrument  
case  
Push the retaining clamp firmly  
against the panel  
4
Fig. 5.4 Mounting Details  
34  
5
INSTALLATION…  
EC Directive 89/336/EEC  
5.4.3 Logic Output  
18V DC at 20mA  
In order to meet the requirements of  
the EC Directive 89/336/EEC for  
EMC regulations, this product must  
Min load 900  
Isolated from Analog Input  
(not isolated from Retransmission  
O/P).  
not be used in  
environment.  
a
non-industrial  
5.3 Electrical Connections  
Fig. 5.5 (overleaf)  
Dielectric strength: 500V d.c. for 1  
minute.  
Warning. Before making  
any connections, ensure that the  
power supply, any powered control  
circuits and high common mode  
voltages are switched off.  
5.4.4 Retransmission  
Analog Output  
Max. load 15V (750at 20mA)  
Isolated from Analog Input (not  
isolated from Logic O/P).  
Note. If it is not possible to  
avoid strong electrical and magnetic  
fields, screened cables within  
earthed metal conduit must be used.  
Dielectric strength: 500V d.c. for 1  
minute.  
5.4.5 Digital Input  
Type: Volt-free  
5.4 Relays, Arc Suppression,  
Inputs and Outputs  
Minimum Pulse: 250 ms  
5.4.1 Relay Contact Ratings  
Relay contacts are rated at:  
115/230V AC at 5A (non-inductive)  
250V DC 25W max.  
5.4.2 Arc Suppression  
Arc suppression components are fitted  
to relays 2 and 3 only. If relay 1 is  
required to switch inductive loads, fit  
the arc suppression components  
supplied.  
35  
…5 INSTALLATION  
Logic Output  
(18V at 20mA max.)  
85 to 265V a.c.  
1
N
L
2
Analog Input  
(see below)  
+
Relay  
Output 1  
24V d.c.  
Analog  
Output  
+
+
N/O  
C
N/C  
RTD1  
3
+
+
4
1A  
1
2
5
6
7
8
9
10 11 12  
22 23 24  
21  
13 14 15 16  
18 19  
17  
20  
+
N/O  
C
N/C  
C
Relay  
Output 2  
RS485 RS485 RS485  
TX RX  
or  
N/O  
Relay Output 3  
Not  
Used  
Digital  
Input  
C
N/C  
750max. load  
Note 1. The Analog Output and Logic Output use a common positive  
terminal, capable of driving both outputs simultaneously.  
Note 2. Fit arc suppression components if switching inductive loads.  
THC  
millivolts  
and volts  
3-lead  
RTD  
2-lead RTD  
Milliamps * Milliamps  
and resistance  
3rd lead  
1
2
RTD –  
RTD –  
RTD +  
**100Ω  
**100Ω  
+
RTD –  
+
2-wire  
Tx  
3
4
RTD  
+
transmitter  
+
* Using internal transmitter power supply  
** Use 100shunt resistor provided with instrument  
Fig. 5.5 Electrical Connections  
36  
8
CUSTOMER SETUP LOG  
LEVEL2  
A1xx  
LEVEL1  
A2xx  
A3xx  
CodE  
xxxxxx  
t-GO  
SECtot  
PrESEt  
PrEdEt  
A xxxx  
H xxxx  
L xxxx  
0AdJ  
Instrument Serial Number:  
C 1 5 0 /  
/
Product Code:  
CUSTOMER CONFIGURATION LOG  
LEVEL4  
ENG H I  
ENG LO  
rEt H I  
rEt LO  
CNt H I  
CUtOFF  
PASSrd  
Addr  
LEVEL3  
A 1KC0  
A
B
C
G
L
D
H
N
T
E 0000  
E
F
J 0000  
J
K
P 0000  
P
S
R
Customer Support  
We provide a comprehensive after sales  
service via our Worldwide Service  
Organization. Contact one of the following  
offices for details on your nearest Service  
and Repair Centre.  
United Kingdom  
ABB Limited  
Tel: +44 (0)1480 475321  
Fax: +44 (0)1480 217948  
United States of America  
ABB Inc.  
Tel: +1 215-674-6000  
Fax: +1 215-674-7183  
Client Warranty  
Prior to installation, the equipment referred to in this manual must be stored in a clean,  
dry environment, in accordance with the Company's published specification. Periodic  
checks must be made on the equipment's condition.  
In the event of a failure under warranty, the following documentation must be provided  
as substantiation:  
1. A listing evidencing process operation and alarm logs at time of failure.  
2. Copies of operating and maintenance records relating to the alleged faulty unit.  
ABB has Sales & Customer Support expertise  
in over 100 countries worldwide  
The Company’s policy is one of continuous product  
improvement and the right is reserved to modify the  
information contained herein without notice.  
Printed in UK (06.03)  
© ABB 2003  
ABB Limited  
ABB Inc  
Howard Road, St. Neots  
Cambridegshire, PE19 8EU  
UK  
125 E. County Line Road  
Warminster, PA 18974  
USA  
Tel: +44 (0)1480 475321  
Fax:+44 (0)1480 470787  
Tel: +1 215 674 6000  
Fax:+1 215-674 7183  

McCulloch MCS2003 User Manual
Jura Capresso IMPRESSA E65 User Manual
Huawei Technologies Cell Phone M835 User Manual
HP Hewlett Packard Hewlett Packard Computer Accessories Windows CE 50 HP Compaq Thin Client User Manual
DeLonghi EC190 User Manual
DeLonghi cc 100 User Manual
Califone CD102 User Manual
Bunn SRUA User Manual
Black &amp; Decker HCC100C User Manual
Audiovox CMD 9000 User Manual