GE NETWORX NX 548E User Manual

NetworX NX-548E Receiver  
Installation Instructions  
466-2225B July 2006  
Copyright © 2006, GE Security Inc.  
4. Use the mounting screw provided to loosely install the edge  
guide standoff in the lower mounting hole in the appropriate  
Contents  
space to the left of the control panel (Figure 2). Do not  
tighten the mounting screw down at this time.  
Figure 2.  
Installing the edge guide standoff  
Introduction  
The NX-548E Receiver adds wireless capabilities to the  
NetworX line of control panels. Adding a receiver makes these  
control panels compatible with NX wireless transmitters.  
Only three wire connections are required for power and commu-  
nication to the control panel.  
Mounting screw  
Edge guide standoff  
WARNING: To avoid possible equipment damage  
WA  
or personal injury, remove power from  
the control panel before making any  
wiring connections to the receiver.  
You must be free of static electricity before  
CAUTION  
handling circuit boards. Touch a bare metal  
surface or wear a grounding strap to  
discharge yourself.  
Internal mounting  
For internal mounting, mount the receiver inside the control  
panel enclosure. Use the following installation guidelines:  
• Leave at least 10 in. (25 cm) above the control panel for the  
receiver’s antennas.  
5. Slide the printed circuit board into the antennae shroud  
slots, after inserting wires into antennae shrouds (Figure 3).  
• Avoid areas that expose the receiver to moisture.  
• Avoid areas with excessive metal or electrical wiring,  
including furnaces and utility rooms.  
Figure 3.  
Anntennae shrouds  
To mount the receiver, do the following:  
1. Remove the appropriate knockouts on the top of the control  
panel enclosure for the antenna shrouds.  
Antennae  
shrouds  
2. Assemble the antenna shrouds and fit the black O-rings to  
the bottom of each shroud.  
3. Insert the shrouds into the knockout holes (Figure 1).  
Enclosure  
Figure 1.  
Installing the antenna shrouds  
Circuit  
board  
Antenna shroud  
Enclosure top  
O-ring  
Knockout hole  
         
3
9. To install the circuit board onto the back plate (Figure 7),  
insert the antennas into the antenna shrouds, then gently  
slide the top of the circuit board under the two top latches,  
and snap the circuit board in at the bottom latch to secure it  
in place.  
DIP switch settings  
The DIP switches (Figure 7) on the circuit board are used to set  
the receiver module number. Use Table 2 to set the DIP switches  
to the desired module number.  
Table 2.  
DIP switch settings  
Module number 32  
Module number 33  
Figure 7.  
Circuit board and back plate  
Antenna shrouds  
ON  
EDG  
ON  
EDG  
1
2
3
4
1
2
3
4
Module number 34  
Module number 35 (default)  
Top latches  
ON  
EDG  
ON  
1
EDG  
Circuit board  
Back plate  
1
2
3
4
2
3
4
Module number 36  
Module number 37  
ON  
ECE  
DIP switches  
1
2
3
4
ON  
EDG  
ON  
EDG  
Wiring terminals  
LEDs  
1
2
3
4
1
2
3
4
Module number 38  
Module number 39  
ON  
EDG  
ON  
EDG  
Bottom latch  
1
2
3
4
1
2
3
4
Power up  
When you apply power to the control panel, the green (power)  
LED on the receiver (Figure 8) blinks for approximately 10  
seconds. Table 3 describes the receiver status based on LED  
conditions.The lower red LED at the bottom of the receiver  
(Figure 8) may emit a dim glow, but is not used as an indicator.  
Wiring  
To wire the receiver, do the following:  
1. Remove power (if applied) from the control panel.Use 22-  
gauge, or larger, stranded wire to connect the +12, GND,  
and DATA terminals on the receiver (Figure 8) to the power,  
common, and data terminals on the control panel.  
Table 3.  
LED indications  
Green (power) LED status  
Meaning  
Power-up blinks  
LED blinks represent Product Version Number  
(PVN). Long blink on is 1, short blink on is 0. PVN  
is in binary, from most significant to least signif-  
icant bit.  
Figure 8.  
Receiver wiring connections and LEDs  
Off  
No packets from sensors being received.  
Short blink on  
Receiver received a valid packet from an  
unknown sensor.  
+ 12 (to panel POS)  
Long blink on  
Receiver received a valid packet from an  
enrolled sensor.  
GND (to panel COM)  
DATA (to panel DATA)  
Green (power) LED  
Red (data) LED  
Red (data) LED status  
Meaning  
Red (not used) LED  
Off  
No data communication with the control panel.  
Check wiring and power source.  
Short blink on  
Normal data communication with the control  
panel.  
             
4
NetworX NX-548E Receiver  
Installation Instructions  
7. Enter the zone number (1 through 192) and press *. Three  
beeps from the keypad indicate an entry error. This occurs if  
you enter a transmitter number that is not within the  
receiver’s zone block or if the location already has a sensor  
learned into it.  
Programming  
This section describes how to program the units.  
Programming guidelines  
Use the following programming guidelines:  
Note:  
If you change your mind about your entry, terminate  
programming by entering 0 # 0 * and start over at  
step 6.  
• NX-4 and NX-6 control panels can have receivers added  
with zones that overlap those contained in the control panel.  
No hardware expanders can be used.  
• NX-8 control panels can have expansion zones (hardwire or  
wireless) set the same as those contained in the control  
panel. To do this you must disable the onboard control panel  
zones in panel location 37. All zone expansion modules  
must not overlap any blocks of 8 zones.  
8. Trip the desired transmitter (within 250 seconds) as  
described in Table 4. Listen for the ding dong for confirma-  
tion  
.
Note:  
For specific instructions on tripping a transmitter,  
consult the transmitter’s manual.  
• All other control panels can have wireless zones added to  
any zone. If a hardwire input (on either the control panel or  
hardwire expander) is also present on the same zone as an  
enabled wireless zone, the wireless transmitter takes  
priority.  
Table 4.  
Tripping transmitters  
Transmitter  
Action  
Door/window, shock, glass  
guard, freeze, UFT (Universal  
Fire Transmitter)  
Activate tamper switch by removing cover.  
Transmitter programming  
When programming wireless transmitters into the receiver, you  
can set various options and partitions for each transmitter. These  
settings appear in segments of each programming location.  
Door/window with external  
contact  
Activate tamper switch by removing cover.  
Feature 4—Input option 1, must be on.  
Recessed door/window  
Activate tamper switch by removing circuit  
board until tamper switch is exposed.  
Use Table 5 on page 7 to record zone assignments and settings.  
Be sure to circle where each zone resides:  
RM. Receiver module  
HE. Hardwire expander  
P. Panel  
Micro door/window and  
Micro recessed door/window  
Refer to the installation instructions for the  
specific sensor for activation information.  
SlimLine door/window  
PIR  
Remove cover, then press the button on  
the top of the sensor, or activate the  
tamper switch by removing the cover.  
This gives you all the programming information in one place to  
facilitate the programming process.  
Activate tamper switch by removing back  
plate from PIR.  
Zone locations 1 to 192  
Zone locations 1 to 192 are not numbered in Table 5 on page 7  
since these locations vary depending on location 194, Receiver  
zone bank setting.  
Smoke detector without  
tamper switch  
Press and hold the test button.  
Note:  
The default settings shown for segments 1 and 2 in the first  
zone location apply to all zone locations.  
Smoke detector with tamper  
switch  
Trip the tamper switch. Feature 4—Input  
option 1, must be on.  
Add transmitters  
LCD touchpads will display instructions when accomplishing tasks.  
To add transmitters, do the following:  
Heat detector  
Single button panic  
Dual button panic  
Keyfobs  
Press, then release the tamper switch.  
Press and hold the button.  
Press and hold both buttons together.  
1. Enter * 8 at the keypad. On LED touchpads, the five func-  
tion lights start flashing.  
Press and hold the lock and unlock buttons  
together.  
2. Enter the program code (factory default is 9 7 1 3). On LED  
touchpads, the service light flashes and the five function  
lights change from flashing to on steady.  
Repeater  
Press, then release the tamper switch.  
3. Enter the DIP switch setting module number and press #.  
On LED touchpads, the Armed LED turns on, indicating the  
control panel is waiting for a programming location entry.  
9. To program remaining transmitters, repeat steps 6 to 8.  
10. To exit program mode, press EXIT EXIT.  
11. Confirm that the zone types and partition assignments are  
set correctly in the control panel. Refer to the control panel  
installation manual for instructions on how to set zone types  
and partition assignments.  
4. For new installations, enter 9 1 0 # to load factory defaults  
and clear any unwanted information in memory.  
5. For new installations, set the receiver zone bank setting in  
location 194 to determine the starting zone number for the  
specific receiver. This applies only to NX-8E. This must be  
set before learning sensors. For example, if location 194 is  
set to 3, the first available location is 25. The total number  
of available locations depends on the zone limits for both  
the panel and receiver.  
Note:  
When an 80-bit device is added, Feature 6 of Segment 1  
(see Table 5 on page 7) is turned on. But when a 63-bit  
device is added on a zone location that previously had an  
80-bit device, make sure to turn off Feature 6 of Segment 1.  
6. Enter 0 # to enter the sensor learning location. On LED  
touchpads, the Ready LED turns on and the Armed LED  
turns off.  
   
5
UFT settings  
Transmitter options  
Use the following guidelines when setting features 4, 5 and 7  
(see Segment 1 in Table 5 on page 7) for UFTs:  
LCD touchpads will display instructions when accomplishing  
tasks.  
• Feature 4 - Input option 1. For UFTs, turn on this feature to  
disable the transmitter’s primary reed.  
To program the transmitter and partition settings, do the  
following:  
• Feature 5 - Input option 2. For UFTs on this feature to  
disable the transmitter’s secondary reed.  
• Feature 7 - Input option 3. For UFTs that use a normally  
open (NO) external contact, leave this feature off. For UFTs  
that use a normally closed (NC) external contact, turn this  
feature on.  
1. Enter * 8 at the keypad. On LED touchpads, the five func-  
tion lights start flashing.  
2. Enter the program code (factory default is 9713). On LED  
touchpads, the service light flashes and the five function  
lights change from flashing to on steady.  
3. Enter the DIP switch setting module number for the receiver  
and press #. On LED touchpads, the Armed LED turns on to  
indicate the control panel is waiting for a programming  
location entry.  
4. Enter the zone location number and press #. On LED touch-  
pads, the Armed LED turns on and the Zone LEDs display  
the binary data for the current settings.  
5. Press the keypad button that corresponds to the feature  
number you want changed. On LED touchpads, the lights  
corresponding to the feature number will turn on or off  
depending on the previous state. On LCD touchpads, the  
feature number will turn on or off depending on the  
previous state.  
Partition settings for keyfobs  
LCD touchpads will display instructions when accomplishing tasks.  
To program the transmitter and partition settings, do the following:  
1. Enter * 8 at the keypad. On LED touchpads, the five func-  
tion lights start flashing.  
2. Enter the program code (factory default is 9 7 1 3). On LED  
touchpads, the service light flashes and the five function  
lights change from flashing to on steady.  
3. Enter the DIP switch setting module number and press #.  
On LED touchpads, the Armed LED turns on to indicate the  
control panel is waiting for a programming location entry.  
4. Enter the zone location number and press #. On LED touch-  
pads, the Armed LED turns on and the Zone LEDs display  
the binary data for the current settings. On LCD touchpads,  
the display shows Segment 1 and its settings.  
6. Press * to enter the changes and automatically advance to  
segment 2.  
Note:  
If you press # instead of * in step 6, it exits the zone  
location and does not save changes to transmitter  
options.  
5. Press * to advance to Segment 2.  
6. Press the keypad button that corresponds to the partition  
number you want to change. On LED touchpads, lights that  
turn off indicate the keyfob is active in that partition. On  
LCD touchpads, partition numbers that turn on indicate the  
keyfob is active in that partition.  
7. Press # to exit zone location. To continue programming  
other zone locations, repeat steps 4 to7. To exit program  
mode, press EXIT EXIT.  
Door/window transmitter settings  
Use the following guidelines when setting features 4 and 5 (see  
Segment 1 in Table 5 on page 7) for door/window transmitters:  
Note:  
These partition settings apply only to keyfobs.  
Partition assignments for other types of transmitters  
are made in the panel.  
• Feature 4 - Input option 1. Turn on this feature to disable the  
transmitter’s internal reed switches.  
• Feature 5 - Input option 2. For transmitters that use a  
normally open (N/O) external contact, leave this feature off.  
For transmitters that use a normally closed (N/C) external  
contact, turn this feature on.  
7. Press * to enter the changes. To continue programming  
transmitter partition settings, repeat steps 4 to 8.  
Note:  
If you press #, it does not save changes to the current  
segment, but it does save changes to previous  
segments.  
Wireless smoke detector settings  
8. To exit program mode, press EXIT EXIT.  
Use the following guideline when setting feature 4 (see Segment  
1 in Table 5 on page 7) for wireless smoke detectors:  
• Feature 4 - Input option 1. For detectors with tamper  
switches, turn on this feature to enable the tamper feature.  
Note:  
Feature 4 must be off (disabled) when using wireless smoke  
detectors without tamper switches.  
4-button keyfob settings  
The control panel installation manual describes how keyfob  
functions 1 and 2 can be used to control relays, outputs, or X-10  
devices  
.
Use the following guidelines when setting features 4 and 5 (see  
Segment 1 in Table 5 on page 7) for 4-button keyfobs:  
• Feature 4 - Input option 1. Turn on this feature to change the  
Light button to keyfob function 1.  
• Feature 5 - Input option 2. Turn on this feature to change the  
Star button to keyfob function 2.  
6
NetworX NX-548E Receiver  
Installation Instructions  
Transmitter supervision windows  
Delete transmitters  
LCD touchpads will display instructions when accomplishing tasks.  
To change the transmitter supervision windows, do the following:  
1. Enter * 8 at the keypad. On LED touchpads, the five func-  
tion lights start flashing.  
2. Enter the program code (factory default is 9 7 1 3).  
3. Enter the DIP switch setting module number and press #.  
On LED touchpads, the Armed LED turns on to indicate the  
control panel is waiting for a programming location entry.  
LCD touchpads will display instructions when accomplishing tasks.  
The following section describes how to delete transmitters from  
the receiver.  
Note:  
This procedure makes the receiver ignore a transmitter, but  
does not remove the transmitter identification from the  
receiver’s memory. The transmitter can be reactivated by  
turning segment 1 on zone back on, or a new one can be  
learned into the zone.  
To delete transmitters, do the following:  
1. Enter * 8 at the keypad. On LED touchpads, the five function  
4. Enter 195 # to enter location 195, segment 1.  
5. Enter the new normal supervision time (0 to 255 hours) and  
press *. If you choose 0, the normal supervision window is  
set to 256 hours.  
lights start flashing.  
2. Enter the program code (factory default is 9 7 1 3). On LED  
touchpads, the service light flashes and the five function  
lights change from flashing to on steady.  
3. Enter the DIP switch setting module number and press #.  
On LED touchpads, the Armed LED turns on, indicating the  
control panel is waiting for a programming location entry.  
Do not set the normal or fire supervision  
CAUTION  
windows to 1 hour. This causes false trouble  
reports from all learned wireless transmitters.  
4. Enter the zone location number to be deleted and press #.  
On LED touchpads, the Armed LED turns on and the Zone  
LEDs display the binary data for the current settings.  
5. To change transmitter feature 1 (enable sensor), press 1. On  
LED touchpads, the 1 LED turns off to indicate the feature  
change and the Ready LED flashes to indicate the change  
request.  
6. Enter * #. On LED touchpads, the Ready LED stops  
flashing to indicate the new settings are stored in memory  
and the system automatically exits from that location.  
6. Enter the new fire supervision time (0 to 255 hours) and  
press *. If you choose 0, the fire supervision window is set  
to 256 hours.  
7. Enter the new short supervision time (up to 30 minutes).  
The short supervision time prevents arming if a transmitter  
has not checked in within the set time. This applies only to  
specific countries outside the US. Check the control panel  
installation manual to determine if this setting is available.  
If you enter a number higher than 30 (the default value is  
40), you disable the feature.  
7. To continue deleting transmitters, repeat steps 4 to 6.  
8. Press * to save any changes. The panel waits for the next  
8. If you want to delete all transmitters and load factory  
defaults, enter 9 1 0 #.  
9. To exit program mode, press EXIT EXIT.  
location entry.  
Note:  
If you press #, it does not save changes to the current  
segment, but it does save changes made in previous  
segments.  
Testing and troubleshooting  
9. To exit program mode, press EXIT EXIT.  
Test all transmitters to verify programming and operation. Use  
location 200 to troubleshoot transmitters mounted in marginal  
signal strength locations or if the panel has a sensor lost trouble  
condition. To troubleshoot the transmitters, do the following:  
• Delete the transmitter and relearn it back into the receiver.  
• Go to location 200 and check the signal strength. A signal of  
6 or more indicates good signal strength, anything less  
could cause periodic sensor lost trouble conditions.  
• If signal strength is below the acceptable level, delete the  
transmitter and rotate the mounting position (90, 180, or 270  
degrees).  
• Relearn the transmitter into the receiver and check location  
200 for signal strength.  
• If rotating the mounting position does not improve signal  
reception or is not practical, move the transmitter to  
different locations near the desired mounting area.  
• Delete and relearn the transmitter until an acceptable signal  
level is attained, then mount the transmitter.  
   
7
Table 5.  
Location  
Programming settings (continued)  
Programming settings table  
Segment 1  
Segment 2  
Table 5.  
Programming settings  
Zone _____  
1 - Enable sensor  
2 - Supervised  
Partition 1 keyfob  
Partition 2 keyfob  
Partition 3 keyfob  
Partition 4 keyfob  
Partition 5 keyfob  
Partition 6 keyfob  
Partition 7 keyfob  
Partition 8 keyfob  
Location  
Segment 1  
Segment 2  
Assigned to module  
#_____.  
3 - Fire supervision  
4 - Input option 1  
5 - Input option 2  
6 - 80-bit device  
7 - Input option 3  
8 - Not used  
0
None  
None  
(Transmitter to  
program)  
RM HE  
P
Zone _____  
1 - Enable sensor  
(default = off)  
Partition 1 keyfob  
(default = on)  
Assigned to module  
#_____.  
2 - Supervised  
(default = on)  
3 - Fire supervision  
(default = off)  
4 - Input option 1  
(default = off)  
5 - Input option 2  
(default = off)  
Partition 2 keyfob  
(default = off)  
Partition 3 keyfob  
(default = off)  
Partition 4 keyfob  
(default = off)  
Partition 5 keyfob  
(default = off)  
Zone _____  
1 - Enable sensor  
2 - Supervised  
Partition 1 keyfob  
Partition 2 keyfob  
Partition 3 keyfob  
Partition 4 keyfob  
Partition 5 keyfob  
Partition 6 keyfob  
Partition 7 keyfob  
Partition 8 keyfob  
Assigned to module  
#_____.  
3 - Fire supervision  
4 - Input option 1  
5 - Input option 2  
6 - 80-bit device  
7 - Input option 3  
8 - Not used  
RM HE  
P
RM HE  
P
6 - 80-bit device  
(default = off)  
Partition 6 keyfob  
(default = off)  
Partition 7 keyfob  
(default = off)  
Partition 8 keyfob  
(default = off)  
Zone _____  
1 - Enable sensor  
2 - Supervised  
Partition 1 keyfob  
Partition 2 keyfob  
Partition 3 keyfob  
Partition 4 keyfob  
Partition 5 keyfob  
Partition 6 keyfob  
Partition 7 keyfob  
Partition 8 keyfob  
7 - Input option 3  
(default = off)  
8 - Not used  
Assigned to module  
#_____.  
3 - Fire supervision  
4 - Input option 1  
5 - Input option 2  
6 - 80-bit device  
7 - Input option 3  
8 - Not used  
Zone _____  
1 - Enable sensor  
2 - Supervised  
Partition 1 keyfob  
Partition 2 keyfob  
Partition 3 keyfob  
Partition 4 keyfob  
Partition 5 keyfob  
Partition 6 keyfob  
Partition 7 keyfob  
Partition 8 keyfob  
RM HE  
P
Assigned to module  
#_____.  
3 - Fire supervision  
4 - Input option 1  
5 - Input option 2  
6 - 80-bit device  
7 - Input option 3  
8 - Not used  
Zone _____  
1 - Enable sensor  
2 - Supervised  
Partition 1 keyfob  
Partition 2 keyfob  
Partition 3 keyfob  
Partition 4 keyfob  
Partition 5 keyfob  
Partition 6 keyfob  
Partition 7 keyfob  
Partition 8 keyfob  
RM HE  
P
Assigned to module  
#_____.  
3 - Fire supervision  
4 - Input option 1  
5 - Input option 2  
6 - 80-bit device  
7 - Input option 3  
8 - Not used  
Zone _____  
1 - Enable sensor  
2 - Supervised  
Partition 1 keyfob  
Partition 2 keyfob  
Partition 3 keyfob  
Partition 4 keyfob  
Partition 5 keyfob  
Partition 6 keyfob  
Partition 7 keyfob  
Partition 8 keyfob  
RM HE  
P
Assigned to module  
#_____.  
3 - Fire supervision  
4 - Input option 1  
5 - Input option 2  
6 - 80-bit device  
7 - Input option 3  
8 - Not used  
Zone _____  
1 - Enable sensor  
2 - Supervised  
Partition 1 keyfob  
Partition 2 keyfob  
Partition 3 keyfob  
Partition 4 keyfob  
Partition 5 keyfob  
Partition 6 keyfob  
Partition 7 keyfob  
Partition 8 keyfob  
RM HE  
P
Assigned to module  
#_____.  
3 - Fire supervision  
4 - Input option 1  
5 - Input option 2  
6 - 80-bit device  
7 - Input option 3  
8 - Not used  
Zone _____  
1 - Enable sensor  
2 - Supervised  
Partition 1 keyfob  
Partition 2 keyfob  
Partition 3 keyfob  
Partition 4 keyfob  
Partition 5 keyfob  
Partition 6 keyfob  
Partition 7 keyfob  
Partition 8 keyfob  
RM HE  
P
Assigned to module  
#_____.  
3 - Fire supervision  
4 - Input option 1  
5 - Input option 2  
6 - 80-bit device  
7 - Input option 3  
8 - Not used  
Zone _____  
1 - Enable sensor  
2 - Supervised  
Partition 1 keyfob  
Partition 2 keyfob  
Partition 3 keyfob  
Partition 4 keyfob  
Partition 5 keyfob  
Partition 6 keyfob  
Partition 7 keyfob  
Partition 8 keyfob  
RM HE  
P
Assigned to module  
#_____.  
3 - Fire supervision  
4 - Input option 1  
5 - Input option 2  
6 - 80-bit device  
7 - Input option 3  
8 - Not used  
Zone _____  
1 - Enable sensor  
2 - Supervised  
Partition 1 keyfob  
Partition 2 keyfob  
Partition 3 keyfob  
Partition 4 keyfob  
Partition 5 keyfob  
Partition 6 keyfob  
Partition 7 keyfob  
Partition 8 keyfob  
RM HE  
P
Assigned to module  
#_____.  
3 - Fire supervision  
4 - Input option 1  
5 - Input option 2  
6 - 80-bit device  
7 - Input option 3  
8 - Not used  
Zone _____  
1 - Enable sensor  
2 - Supervised  
Partition 1 keyfob  
Partition 2 keyfob  
Partition 3 keyfob  
Partition 4 keyfob  
Partition 5 keyfob  
Partition 6 keyfob  
Partition 7 keyfob  
Partition 8 keyfob  
RM HE  
P
Assigned to module  
#_____.  
3 - Fire supervision  
4 - Input option 1  
5 - Input option 2  
6 - 80-bit device  
7 - Input option 3  
8 - Not used  
Zone _____  
1 - Enable sensor  
2 - Supervised  
Partition 1 keyfob  
Partition 2 keyfob  
Partition 3 keyfob  
Partition 4 keyfob  
Partition 5 keyfob  
Partition 6 keyfob  
Partition 7 keyfob  
Partition 8 keyfob  
RM HE  
P
Assigned to module  
#_____.  
3 - Fire supervision  
4 - Input option 1  
5 - Input option 2  
6 - 80-bit device  
7 - Input option 3  
8 - Not used  
RM HE  
P
   
8
NetworX NX-548E Receiver  
Installation Instructions  
Table 5.  
Location  
Programming settings (continued)  
Table 5.  
Location  
Programming settings (continued)  
Segment 1  
Segment 2  
Segment 1  
Segment 2  
Zone _____  
1 - Enable sensor  
2 - Supervised  
Partition 1 keyfob  
Partition 2 keyfob  
Partition 3 keyfob  
Partition 4 keyfob  
Partition 5 keyfob  
Partition 6 keyfob  
Partition 7 keyfob  
Partition 8 keyfob  
Zone _____  
1 - Enable sensor  
2 - Supervised  
Partition 1 keyfob  
Partition 2 keyfob  
Partition 3 keyfob  
Partition 4 keyfob  
Partition 5 keyfob  
Partition 6 keyfob  
Partition 7 keyfob  
Partition 8 keyfob  
Assigned to module  
#_____.  
Assigned to module  
#_____.  
3 - Fire supervision  
4 - Input option 1  
5 - Input option 2  
6 - 80-bit device  
7 - Input option 3  
8 - Not used  
3 - Fire supervision  
4 - Input option 1  
5 - Input option 2  
6 - 80-bit device  
7 - Input option 3  
8 - Not used  
RM HE  
P
RM HE  
P
Zone _____  
1 - Enable sensor  
2 - Supervised  
Partition 1 keyfob  
Partition 2 keyfob  
Partition 3 keyfob  
Partition 4 keyfob  
Partition 5 keyfob  
Partition 6 keyfob  
Partition 7 keyfob  
Partition 8 keyfob  
Zone _____  
1 - Enable sensor  
2 - Supervised  
Partition 1 keyfob  
Partition 2 keyfob  
Partition 3 keyfob  
Partition 4 keyfob  
Partition 5 keyfob  
Partition 6 keyfob  
Partition 7 keyfob  
Partition 8 keyfob  
Assigned to module  
#_____.  
Assigned to module  
#_____.  
3 - Fire supervision  
4 - Input option 1  
5 - Input option 2  
6 - 80-bit device  
7 - Input option 3  
8 - Not used  
3 - Fire supervision  
4 - Input option 1  
5 - Input option 2  
6 - 80-bit device  
7 - Input option 3  
8 - Not used  
RM HE  
P
RM HE  
P
Zone _____  
1 - Enable sensor  
2 - Supervised  
Partition 1 keyfob  
Partition 2 keyfob  
Partition 3 keyfob  
Partition 4 keyfob  
Partition 5 keyfob  
Partition 6 keyfob  
Partition 7 keyfob  
Partition 8 keyfob  
Zone _____  
1 - Enable sensor  
2 - Supervised  
Partition 1 keyfob  
Partition 2 keyfob  
Partition 3 keyfob  
Partition 4 keyfob  
Partition 5 keyfob  
Partition 6 keyfob  
Partition 7 keyfob  
Partition 8 keyfob  
Assigned to module  
#_____.  
Assigned to module  
#_____.  
3 - Fire supervision  
4 - Input option 1  
5 - Input option 2  
6 - 80-bit device  
7 - Input option 3  
8 - Not used  
3 - Fire supervision  
4 - Input option 1  
5 - Input option 2  
6 - 80-bit device  
7 - Input option 3  
8 - Not used  
RM HE  
P
RM HE  
P
Zone _____  
1 - Enable sensor  
2 - Supervised  
Partition 1 keyfob  
Partition 2 keyfob  
Partition 3 keyfob  
Partition 4 keyfob  
Partition 5 keyfob  
Partition 6 keyfob  
Partition 7 keyfob  
Partition 8 keyfob  
Zone _____  
1 - Enable sensor  
2 - Supervised  
Partition 1 keyfob  
Partition 2 keyfob  
Partition 3 keyfob  
Partition 4 keyfob  
Partition 5 keyfob  
Partition 6 keyfob  
Partition 7 keyfob  
Partition 8 keyfob  
Assigned to module  
#_____.  
Assigned to module  
#_____.  
3 - Fire supervision  
4 - Input option 1  
5 - Input option 2  
6 - 80-bit device  
7 - Input option 3  
8 - Not used  
3 - Fire supervision  
4 - Input option 1  
5 - Input option 2  
6 - 80-bit device  
7 - Input option 3  
8 - Not used  
RM HE  
P
RM HE  
P
Zone _____  
1 - Enable sensor  
2 - Supervised  
Partition 1 keyfob  
Partition 2 keyfob  
Partition 3 keyfob  
Partition 4 keyfob  
Partition 5 keyfob  
Partition 6 keyfob  
Partition 7 keyfob  
Partition 8 keyfob  
Zone _____  
1 - Enable sensor  
2 - Supervised  
Partition 1 keyfob  
Partition 2 keyfob  
Partition 3 keyfob  
Partition 4 keyfob  
Partition 5 keyfob  
Partition 6 keyfob  
Partition 7 keyfob  
Partition 8 keyfob  
Assigned to module  
#_____.  
Assigned to module  
#_____.  
3 - Fire supervision  
4 - Input option 1  
5 - Input option 2  
6 - 80-bit device  
7 - Input option 3  
8 - Not used  
3 - Fire supervision  
4 - Input option 1  
5 - Input option 2  
6 - 80-bit device  
7 - Input option 3  
8 - Not used  
RM HE  
P
RM HE  
P
Zone _____  
1 - Enable sensor  
2 - Supervised  
Partition 1 keyfob  
Partition 2 keyfob  
Partition 3 keyfob  
Partition 4 keyfob  
Partition 5 keyfob  
Partition 6 keyfob  
Partition 7 keyfob  
Partition 8 keyfob  
Zone _____  
1 - Enable sensor  
2 - Supervised  
Partition 1 keyfob  
Partition 2 keyfob  
Partition 3 keyfob  
Partition 4 keyfob  
Partition 5 keyfob  
Partition 6 keyfob  
Partition 7 keyfob  
Partition 8 keyfob  
Assigned to module  
#_____.  
Assigned to module  
#_____.  
3 - Fire supervision  
4 - Input option 1  
5 - Input option 2  
6 - 80-bit device  
7 - Input option 3  
8 - Not used  
3 - Fire supervision  
4 - Input option 1  
5 - Input option 2  
6 - 80-bit device  
7 - Input option 3  
8 - Not used  
RM HE  
P
RM HE  
P
Zone _____  
1 - Enable sensor  
2 - Supervised  
Partition 1 keyfob  
Partition 2 keyfob  
Partition 3 keyfob  
Partition 4 keyfob  
Partition 5 keyfob  
Partition 6 keyfob  
Partition 7 keyfob  
Partition 8 keyfob  
Zone _____  
1 - Enable sensor  
2 - Supervised  
Partition 1 keyfob  
Partition 2 keyfob  
Partition 3 keyfob  
Partition 4 keyfob  
Partition 5 keyfob  
Partition 6 keyfob  
Partition 7 keyfob  
Partition 8 keyfob  
Assigned to module  
#_____.  
Assigned to module  
#_____.  
3 - Fire supervision  
4 - Input option 1  
5 - Input option 2  
6 - 80-bit device  
7 - Input option 3  
8 - Not used  
3 - Fire supervision  
4 - Input option 1  
5 - Input option 2  
6 - 80-bit device  
7 - Input option 3  
8 - Not used  
RM HE  
P
RM HE  
P
9
Table 5.  
Location  
Programming settings (continued)  
Table 5.  
Location  
Programming settings (continued)  
Segment 1  
Segment 2  
Segment 1  
Segment 2  
Zone _____  
1 - Enable sensor  
2 - Supervised  
Partition 1 keyfob  
Partition 2 keyfob  
Partition 3 keyfob  
Partition 4 keyfob  
Partition 5 keyfob  
Partition 6 keyfob  
Partition 7 keyfob  
Partition 8 keyfob  
Zone _____  
1 - Enable sensor  
2 - Supervised  
Partition 1 keyfob  
Partition 2 keyfob  
Partition 3 keyfob  
Partition 4 keyfob  
Partition 5 keyfob  
Partition 6 keyfob  
Partition 7 keyfob  
Partition 8 keyfob  
Assigned to module  
#_____.  
Assigned to module  
#_____.  
3 - Fire supervision  
4 - Input option 1  
5 - Input option 2  
6 - 80-bit device  
7 - Input option 3  
8 - Not used  
3 - Fire supervision  
4 - Input option 1  
5 - Input option 2  
6 - 80-bit device  
7 - Input option 3  
8 - Not used  
RM HE  
P
RM HE  
P
Zone _____  
1 - Enable sensor  
2 - Supervised  
Partition 1 keyfob  
Partition 2 keyfob  
Partition 3 keyfob  
Partition 4 keyfob  
Partition 5 keyfob  
Partition 6 keyfob  
Partition 7 keyfob  
Partition 8 keyfob  
Zone _____  
1 - Enable sensor  
2 - Supervised  
Partition 1 keyfob  
Partition 2 keyfob  
Partition 3 keyfob  
Partition 4 keyfob  
Partition 5 keyfob  
Partition 6 keyfob  
Partition 7 keyfob  
Partition 8 keyfob  
Assigned to module  
#_____.  
Assigned to module  
#_____.  
3 - Fire supervision  
4 - Input option 1  
5 - Input option 2  
6 - 80-bit device  
7 - Input option 3  
8 - Not used  
3 - Fire supervision  
4 - Input option 1  
5 - Input option 2  
6 - 80-bit device  
7 - Input option 3  
8 - Not used  
RM HE  
P
RM HE  
P
Zone _____  
1 - Enable sensor  
2 - Supervised  
Partition 1 keyfob  
Partition 2 keyfob  
Partition 3 keyfob  
Partition 4 keyfob  
Partition 5 keyfob  
Partition 6 keyfob  
Partition 7 keyfob  
Partition 8 keyfob  
Zone _____  
1 - Enable sensor  
2 - Supervised  
Partition 1 keyfob  
Partition 2 keyfob  
Partition 3 keyfob  
Partition 4 keyfob  
Partition 5 keyfob  
Partition 6 keyfob  
Partition 7 keyfob  
Partition 8 keyfob  
Assigned to module  
#_____.  
Assigned to module  
#_____.  
3 - Fire supervision  
4 - Input option 1  
5 - Input option 2  
6 - 80-bit device  
7 - Input option 3  
8 - Not used  
3 - Fire supervision  
4 - Input option 1  
5 - Input option 2  
6 - 80-bit device  
7 - Input option 3  
8 - Not used  
RM HE  
P
RM HE  
P
Zone _____  
1 - Enable sensor  
2 - Supervised  
Partition 1 keyfob  
Partition 2 keyfob  
Partition 3 keyfob  
Partition 4 keyfob  
Partition 5 keyfob  
Partition 6 keyfob  
Partition 7 keyfob  
Partition 8 keyfob  
Zone _____  
1 - Enable sensor  
2 - Supervised  
Partition 1 keyfob  
Partition 2 keyfob  
Partition 3 keyfob  
Partition 4 keyfob  
Partition 5 keyfob  
Partition 6 keyfob  
Partition 7 keyfob  
Partition 8 keyfob  
Assigned to module  
#_____.  
Assigned to module  
#_____.  
3 - Fire supervision  
4 - Input option 1  
5 - Input option 2  
6 - 80-bit device  
7 - Input option 3  
8 - Not used  
3 - Fire supervision  
4 - Input option 1  
5 - Input option 2  
6 - 80-bit device  
7 - Input option 3  
8 - Not used  
RM HE  
P
RM HE  
P
Zone _____  
1 - Enable sensor  
2 - Supervised  
Partition 1 keyfob  
Partition 2 keyfob  
Partition 3 keyfob  
Partition 4 keyfob  
Partition 5 keyfob  
Partition 6 keyfob  
Partition 7 keyfob  
Partition 8 keyfob  
Zone _____  
1 - Enable sensor  
2 - Supervised  
Partition 1 keyfob  
Partition 2 keyfob  
Partition 3 keyfob  
Partition 4 keyfob  
Partition 5 keyfob  
Partition 6 keyfob  
Partition 7 keyfob  
Partition 8 keyfob  
Assigned to module  
#_____.  
Assigned to module  
#_____.  
3 - Fire supervision  
4 - Input option 1  
5 - Input option 2  
6 - 80-bit device  
7 - Input option 3  
8 - Not used  
3 - Fire supervision  
4 - Input option 1  
5 - Input option 2  
6 - 80-bit device  
7 - Input option 3  
8 - Not used  
RM HE  
P
RM HE  
P
Zone _____  
1 - Enable sensor  
2 - Supervised  
Partition 1 keyfob  
Partition 2 keyfob  
Partition 3 keyfob  
Partition 4 keyfob  
Partition 5 keyfob  
Partition 6 keyfob  
Partition 7 keyfob  
Partition 8 keyfob  
Zone _____  
1 - Enable sensor  
2 - Supervised  
Partition 1 keyfob  
Partition 2 keyfob  
Partition 3 keyfob  
Partition 4 keyfob  
Partition 5 keyfob  
Partition 6 keyfob  
Partition 7 keyfob  
Partition 8 keyfob  
Assigned to module  
#_____.  
Assigned to module  
#_____.  
3 - Fire supervision  
4 - Input option 1  
5 - Input option 2  
6 - 80-bit device  
7 - Input option 3  
8 - Not used  
3 - Fire supervision  
4 - Input option 1  
5 - Input option 2  
6 - 80-bit device  
7 - Input option 3  
8 - Not used  
RM HE  
P
RM HE  
P
Zone _____  
1 - Enable sensor  
2 - Supervised  
Partition 1 keyfob  
Partition 2 keyfob  
Partition 3 keyfob  
Partition 4 keyfob  
Partition 5 keyfob  
Partition 6 keyfob  
Partition 7 keyfob  
Partition 8 keyfob  
Zone _____  
1 - Enable sensor  
2 - Supervised  
Partition 1 keyfob  
Partition 2 keyfob  
Partition 3 keyfob  
Partition 4 keyfob  
Partition 5 keyfob  
Partition 6 keyfob  
Partition 7 keyfob  
Partition 8 keyfob  
Assigned to module  
#_____.  
Assigned to module  
#_____.  
3 - Fire supervision  
4 - Input option 1  
5 - Input option 2  
6 - 80-bit device  
7 - Input option 3  
8 - Not used  
3 - Fire supervision  
4 - Input option 1  
5 - Input option 2  
6 - 80-bit device  
7 - Input option 3  
8 - Not used  
RM HE  
P
RM HE  
P
10  
NetworX NX-548E Receiver  
Installation Instructions  
Table 5.  
Location  
Programming settings (continued)  
Table 5.  
Location  
193  
Programming settings (continued)  
Segment 1  
Segment 1  
Segment 2  
Segment 2  
Zone _____  
1 - Enable sensor  
2 - Supervised  
Partition 1 keyfob  
Partition 2 keyfob  
Partition 3 keyfob  
Partition 4 keyfob  
Partition 5 keyfob  
Partition 6 keyfob  
Partition 7 keyfob  
Partition 8 keyfob  
1 - Enable jam detect  
2 - Enable auto  
advance to next  
zone number  
3 - Keyfob user ID (off  
= all keyfobs  
None  
Receiver options (all  
defaults off)  
Assigned to module  
#_____.  
3 - Fire supervision  
4 - Input option 1  
5 - Input option 2  
6 - 80-bit device  
7 - Input option 3  
8 - Not used  
RM HE  
P
report as user 99;  
on = keyfob  
reports as  
learned zone #)  
4 - Enable antenna  
tamper (only  
Zone _____  
1 - Enable sensor  
2 - Supervised  
Partition 1 keyfob  
Partition 2 keyfob  
Partition 3 keyfob  
Partition 4 keyfob  
Partition 5 keyfob  
Partition 6 keyfob  
Partition 7 keyfob  
Partition 8 keyfob  
Assigned to module  
#_____.  
3 - Fire supervision  
4 - Input option 1  
5 - Input option 2  
6 - 80-bit device  
7 - Input option 3  
8 - Not used  
selectable on  
international  
versions; reports  
as box tamper)  
5 - Enable case  
tamper  
6 - Keyfob disarming  
(0 = keyfob  
RM HE  
P
Zone _____  
1 - Enable sensor  
2 - Supervised  
Partition 1 keyfob  
Partition 2 keyfob  
Partition 3 keyfob  
Partition 4 keyfob  
Partition 5 keyfob  
Partition 6 keyfob  
Partition 7 keyfob  
Partition 8 keyfob  
disarm normal; 1  
= disarm only  
during entry or  
partial arm)  
Assigned to module  
#_____.  
3 - Fire supervision  
4 - Input option 1  
5 - Input option 2  
6 - 80-bit device  
7 - Input option 3  
8 - Not used  
7 - Enable wall tamper  
(reports as box  
tamper)  
RM HE  
P
8 - Not used  
Zone _____  
1 - Enable sensor  
2 - Supervised  
Partition 1 keyfob  
Partition 2 keyfob  
Partition 3 keyfob  
Partition 4 keyfob  
Partition 5 keyfob  
Partition 6 keyfob  
Partition 7 keyfob  
Partition 8 keyfob  
194  
Starting zone  
numbers by bank  
setting:  
0 = 1  
1 = 9  
2 = 17  
3 = 25  
4 = 33  
5 = 41  
Receiver zone bank  
setting (default = 0),  
set this before  
learning any sensors.  
Applies only to NX8E.  
Assigned to module  
#_____.  
3 - Fire supervision  
4 - Input option 1  
5 - Input option 2  
6 - 80-bit device  
7 - Input option 3  
8 - Not used  
RM HE  
P
6 = 49  
7 = 57  
8 = 65  
9 = 73  
Zone _____  
1 - Enable sensor  
2 - Supervised  
Partition 1 keyfob  
Partition 2 keyfob  
Partition 3 keyfob  
Partition 4 keyfob  
Partition 5 keyfob  
Partition 6 keyfob  
Partition 7 keyfob  
Partition 8 keyfob  
Assigned to module  
#_____.  
3 - Fire supervision  
4 - Input option 1  
5 - Input option 2  
6 - 80-bit device  
7 - Input option 3  
8 - Not used  
10 = 81  
11 = 89  
12 = 97  
13 = 105  
14 = 113  
15 = 121  
16 = 129  
17 = 137  
18 = 145  
19 = 153  
20 = 161  
21 = 169  
22 = 177  
23 = 185  
RM HE  
P
Zone _____  
1 - Enable sensor  
2 - Supervised  
Partition 1 keyfob  
Partition 2 keyfob  
Partition 3 keyfob  
Partition 4 keyfob  
Partition 5 keyfob  
Partition 6 keyfob  
Partition 7 keyfob  
Partition 8 keyfob  
Assigned to module  
#_____.  
3 - Fire supervision  
4 - Input option 1  
5 - Input option 2  
6 - 80-bit device  
7 - Input option 3  
8 - Not used  
RM HE  
P
Zone _____  
1 - Enable sensor  
2 - Supervised  
Partition 1 keyfob  
Partition 2 keyfob  
Partition 3 keyfob  
Partition 4 keyfob  
Partition 5 keyfob  
Partition 6 keyfob  
Partition 7 keyfob  
Partition 8 keyfob  
195  
Normal ______hours.  
(0 to 255 hours;  
default = 24 hours)  
Fire ______hours.  
(0 to 255 hours;  
default = 4 hours)  
Assigned to module  
#_____.  
Supervision Windows  
3 - Fire supervision  
4 - Input option 1  
5 - Input option 2  
6 - 80-bit device  
7 - Input option 3  
8 - Not used  
Segment 3:  
RM HE  
P
Short supervision time _____minutes (1 to 30  
minutes, default = 40 minutes - disabled)  
Do not change Segment 3 setting unless  
required. See step 7 under Transmitter supervi-  
11  
Table 5.  
Location  
200  
Number of rounds  
received from last  
transmitter learned  
Programming settings (continued)  
Supported devices  
For 80-bit devices, Feature 6 must be on for Segment 1 on zone  
location. For 63-bit devices, Feature 6 must be off for Segment 1  
on zone location.  
Segment 1  
Segment 2  
None  
None  
80-bit devices  
• 60-849-02-95 ESL Smoke Detector  
• 60-917-95 Universal Fire Transmitter  
• 60-832-95R 2 Button Keychain Touchpad *  
63-bit devices  
• NX-450 (60-670-95R) SAW Door/Window Sensor, White  
• NX-451 (60-670-11-95R) SAW Door/Window Sensor, Brown  
• NX-452 (60-499-10-319.5) SlimLine Door/Window Sensor,  
White  
• NX-453 (60-499-11-319.5) SlimLine Door/Window Sensor,  
Brown  
• NX-458 (60-751-95) Recessed Micro Door/Window Sensor  
• 60-741-11-95 Rececessed Micro Door/Window  
Sensor, Brown  
• NX-470 (60-659-95R) 4-Button Keychain Touchpad  
• NX-474 (60-906-95) Micro Multi-Purpose Crystal Panic Button  
• NX-475 (60-578-10-95) Water-Resistant Pendant Panic Sensor  
• NX-480 (60-639-95) Indoor SAW PIR Motion Sensor  
• 60-639-95R-OD Outdoor SAW PIR Motion  
• 60-639-02-95R SAW PIR Mothion w/1.5v  
• NX-487 (60-834-95) Adjustable Dual Technology Sound Sensor  
• NX-490 (60-506-319.5) Wireless Smoke Sensor  
• NX-491NT (60-848-02-95) ESL 560 Series Wireless  
Smoke Sensor  
• NX-495 (60-460-319.5) Rate-of-Rise Heat Sensor  
• NX-650 (60-362-10-319.5) Standard Door/Window Sensor,  
White  
• NX-651 (60-362-11-319.5) Standard Door/Window Sensor,  
Brown  
• NX-652 (60-641-95) Long Life Door/Window Sensor, White  
• NX-653 (60-641-11-95) Long Life Door/Window Sensor,  
Brown  
• NX-454 (60-688-95) Micro Door/Window Sensor, White*  
• NX-455 (60-688-11-95) Micro Door/Window Sensor, Brown*  
• NX-481 (60-807-95R) Indoor SAW PIR Motion Sensor*  
• NX-482 (60-880-95) AP750W PIR Motion Sensor*  
• NX-488 (60-873-95) ShatterPro Crystal Glass Break Sensor*  
• NX-497 (60-652-95) Crystal Carbon Monoxide Sensor*  
• NX-656 (60-462-10-319.5) Glass Guard Crystal Sensor, White*  
• NX-657 (60-462-11-319.5) Glass Guard Crystal Sensor,  
Brown *  
• NX-658 (60-742-95R) Crystal Freeze Sensor*  
• NX-667 (60-886-95) Crystal Learn Mode Shock Sensor,  
White*  
• NX-668 (60-886-11-95) Crystal Learn Mode Shock Sensor,  
Brown*  
• NX-695 (60-744-95R) SAW Water Sensor*  
• NX-706 (80-922) Repeater Kit 319.5*  
• NX-707 (80-922-1) Repeater Kit 319.5 *  
• 60-511-01-95 Learn Mode DS924 PIR Motion Sensor*  
• 60-511-01-95 DS924I Pet Immune PIR*  
• 60-452-10-319.5 Learn Mode Pendant Panic*  
• 60-457-10-319.5 Learn Mode Double Button Panic *  
• 60-458-10-319.5 Learn Mode Single Button Panic*  
* These devices are not listed, investigated, or verified by UL.  
 
12  
NetworX NX-548E Receiver  
Installation Instructions  
Specifications  
Compatibility  
FCC compliance  
This device complies with part 15 of the FCC rules. Operation is subject to the  
following conditions:  
NX-4, NX-6, NX-8, NX-8E control panels  
319.5 MHz  
Frequency  
1. This device may not cause harmful interference.  
2. This device must accept any interference received, including interference  
that may cause undesired operation.  
Changes or modifications not expressly approved by the party responsible for  
compliance could void the user’s authority to operate the equipment.  
Wireless range  
Required power  
Current draw  
1,000 feet (304 m)  
12.0 VDC (provided by panel)  
55 mA maximum  
Operating temperature  
Storage temperature  
Max. relative humidity  
Dimensions  
32 to 120°F (0 to 49°C)  
-30 to 140°F (-34 to 60°C)  
85% noncondensing  
4.65 x 3.20 inches (11.8 x 8.1 cm)  
Listings  
UL  
UL 985, UL 1023  
CUL  
ORD-C1023-1974, ULC-S545-02  
Technical support  
Toll-free: 888.437.3287 (US, including Alaska and Hawaii; Puerto Rico; Canada).  
Outside the toll-free area: Contact your local dealer.  
 

Baxi Potterton WH46 User Manual
Bosch Appliances MCM 5000m User Manual
Bryan Boilers K500 User Manual
Canon IV User Manual
Clarion AUTOMOTIVE INFRARED WH100 User Manual
Directed Video OHV1021 User Manual
Electrolux Thermetic 583394 User Manual
Gitzo GT2932 User Manual
Iiyama L323W User Manual
JVC Car Video System KW AVX840 User Manual