Owner’s Manual
™
SmartOnline 3-Phase 10kVA
Intelligent True On-Line UPS System (Tower)
Input (Voltage/Phase): 270 - 485V AC / Y, 3Ø4W
Output (Voltage/Phase): User-Selectable 220/230/240V AC / 1Ø2W
For all UPS system modules (power module and battery module) sold either separately or combined.
Select UPS system modules may include separate instruction or warning sheets which should be used
in conjunction with this manual.
Important Safety Warnings
Control Panel
2
3
4
Rear Panels
5
Installation
8
Operation (Normal Conditions)
Operation (Special Conditions)
Communications
10
12
14
14
Service
Warranty
Specifications
15
16/31/46/61
Español / Français / Deutsche / Ðóññêèé
1111 W. 35th Street • Chicago, IL 60609 USA
Copyright ©2004 Tripp Lite. All rights reserved. SmartOnline™ is a trademark of Tripp Lite.
Control Panel
There are two separate UPS system modules: a power module and a battery module. Familiarize yourself with the location and function of
the features on each module before installing and operating your UPS system. The power module is the only module which includes front
panel features.
FRONT PANEL
ON
SELECT
OFF
1. "ON/OFF" Switch: This momentary rocker switch turns the UPS System's inverter ON and OFF.
2. "SELECT" Button: This button performs two functions: it allows you to browse through different power readings on the LCD Display
by momentarily pressing the button; it also allows you to silence the UPS alarm by pressing and holding the button for 3 seconds.
3. LCD Display: This backlit (16x2 character) dot matrix display indicates a wide range of UPS operating conditions and diagnostic data.
It will illuminate after you have properly completed installation and start-up and after the "ON/OFF" Switch is turned ON.
4. "I/P" (Input) LED: This green light will illuminate constantly to indicate an AC input supply is present.
5. "AC/DC" (Converter) LED: This green light will illuminate constantly to indicate the UPS's AC/DC converter is activated.
6. "DC/AC" (Inverter) LED: This green light will illuminate constantly to indicate the UPS's DC/AC inverter is activated.
7. "O/P" (Output) LED: This green light will illuminate constantly to indicate your UPS is supplying AC power to connected equipment.
8. "BYPASS" LED: This green light will illuminate when the UPS is providing filtered mains power without engaging its converter or
inverter. Connected equipment will not receive battery power in the event of a blackout.
9. "BATTERY" LED: This red light will illuminate when the UPS is discharging the battery to provide connected equipment with AC
power. An alarm will sound which can be cancelled by pressing and holding the "SELECT" switch for 3 seconds. The alarm will be can-
celled, but the LED will remain illuminated.
3
Rear Panels
14
9
7
6
10
5
8
13
11
1
15
4
18
12
17
REFER TO USER'S MANUAL FOR TORQUING
SPECIFICATIONS, USE COPPER CONDUCTORS ONLY.
UTILISER SEULEMENT LES CONDUCTEURS DE CUIVRE.
3
2
16
19
Power Module Rear Panel
Battery Module Rear Panel
1. Manual Bypass Switch: This switch is used in one step of putting the UPS in "MANUAL BYPASS” mode, which must be done before
performing any maintenance on the UPS with the connected load supported. [See “Operation (Special Conditions)” for step-by-step instruc-
tions for going into "MANUAL BYPASS."] While this switch is on "MANUAL BYPASS," connected equipment will receive filtered AC
mains power, but will not receive battery power in the event of a blackout.
2. Input Terminal Block: Use these terminals to connect your UPS to the AC main power input. Unscrew and remove terminal block plate
for access.
3. Output Terminal Block: Use these terminals to connect your UPS to equipment. A plate covering the terminal block must be unscrewed
and removed for access.
4. External Battery Connector: Use this to connect a Tripp Lite battery module to the power module. Remove the cover for access. The
power module will not start without a connection to a charged battery module. Refer to the battery module owner 's manual for connection
instructions and safety warnings.
5. Exhaust Fan: This cools and ventilates the inside of the UPS.
6. AS-400 Interface Port: This female DB9 port connects your UPS to an IBM AS-400 computer interface via the AS-400 Cable includ-
ed. It uses AS-400 communications to report UPS status and power conditions. Using this port, an IBM AS-400 computer can automati-
cally save open files and shut down its operating system during a blackout. See “Communications” for details.
7. “Smart” RS-232 Interface Port: This female DB9 port connects your UPS to a workstation or server. It uses RS-232 communications
to report UPS and power conditions. It is used with Tripp Lite software and the included RS-232 Cable to monitor and manage network
power and to automatically save open files and shut down equipment during a blackout. See “Communications” for details.
8. Dry Contact Interface Port: This female DB9 port sends contact-closure signals to indicate line-fail and low-battery status. See
“Communications,” for details.
9. Accessory Slot: Remove the small cover panel and use optional accessories to remotely control and monitor your UPS. Contact Tripp
Lite Customer Support for more information and a list of available SNMP, network management and connectivity products.
4
(continued)
Rear Panels
10. “Battery Start” Switch: This momentary rocker switch allows you to “cold-start” your UPS and use it as a stand-alone power source
when utility-supplied AC power is not present. The switch enables the UPS’s DC/AC Inverter. Before “cold-starting” your UPS, make sure
your power module and external battery module(s) are properly installed. Press and hold the “Battery Start” Switch and then press the
“ON/OFF” switch to turn your UPS ON. To turn it OFF after “cold-start,” press the “ON/OFF” Switch.
11. AC Input Breaker: Controls input power to the UPS during normal operation.
12. Bypass AC Input Breaker: Controls input power to the UPS during “BYPASS” operation.
13. Remote “Emergency Power OFF” (EPO) Connector: This modular jack allows remote emergency shutdown. See
“Communications” for details.
14. Inverter Operation DIP Switches: Behind this removable panel are four DIP Switches that should be set to match your input voltage
and input frequency. Your input voltage and frequency DIP switch settings MUST match your input. Your UPS WILL NOT CONVERT
the voltage or frequency.
15. Grounding Terminal: This terminal connects to a grounding electrode conductor. IT IS NOT SAFE TO OPERATE YOUR UPS
WITHOUT CONNECTING IT. The recommended conductor size is 6 AWG based on the UL 1778 standard. Follow all applicable local
electrical wiring regulations.
16. Stabilizers: These supports extend to keep your UPS from rolling or tipping.
17. Battery Module Input Connector: Use this connector to daisy-chain additional battery modules to the first. Remove the cover panel
for access. Refer to the battery module's owner's manual for connection instructions and safety warnings.
18. Battery Module Output Cable: Use this cable to connect the battery module to the power module (or to another battery module when
using more than one). The power module will not start without a connection to a charged battery module. Refer to the battery module
owner's manual for connection instructions and safety warnings.
19. Tower Mounting: For additional stability during tower mounting of BP240V10RT3U External Battery Module, you can order Tripp
Lite base stands (model #: 2-9USTAND) sold separately.
Installation
INVERTER OPERATION DIP SWITCH SETTINGS
Using a small tool, set the four Inverter Operation DIP Switches (located on
the rear panel of your UPS) to match your input voltage, input frequency and
desired operational mode.
Input Voltage Selection
(DIP Switches #1 & #2)
These DIP switches must be set to match your input voltage. Your UPS
WILL NOT CONVERT the voltage.
REFER TO USER'S MANUAL FOR TORQUING
SPECIFICATIONS, USE COPPER CONDUCTORS ONLY.
UTILISER SEULEMENT LES CONDUCTEURS DE CUIVRE.
1
1
1
2
2
2
3
3
3
4
Input Voltage
220V
DIP Switch Position
#1 UP & #2 DOWN
#1 DOWN & #2 UP
#1 DOWN & #2 DOWN
220V
230V
4
240V
230V
Input Frequency Selection
(DIP Switch #3)
4
240V
Your Input Frequency setting MUST match your input frequency. Your UPS
WILL NOT CONVERT the frequency.
1
1
2
2
3
3
4
Input Frequency
50 Hz
DIP Switch Position
#3 UP
50 Hz
60 Hz
4
60 Hz
#3 DOWN
5
(continued)
Installation
Operational Mode Selection
(DIP Switch #4)
The "On-Line" Mode provides on-line operation with zero transfer time. The "Economy" Mode provides line-interactive operation for
increased efficiency when on-line protection is unnecessary, thus reducing operating costs without affecting your UPS's output reliability
during a power outage.
1
2
3
4
Operational Mode
On-Line
DIP Switch Position
#4 UP
On-Line
Economy
1
2
3
4
Economy
#4 DOWN
UPS LOCATION
Move your UPS over short distances using its wheels. Stabilize the UPS by releasing the stabilizers on each side of the unit. NOTE: Do not
stack the UPS System power module or external battery modules.
INPUT AND OUTPUT CONNECTION
WIRING SELECTION
Choose appropriate cabling (cabling should have a temperature rating of 70° C and 6 AWG size) to connect your UPS to an AC power
supply and your equipment to your UPS.
WIRING CONNECTIONS
Connect your wiring to the input and output terminal blocks located on the lower rear panel of your UPS (see figure below).
CAUTION!
Qualified personnel should follow all procedures prescribed by N.E.C. and other local codes for hardwiring devices to a utility source.
Ensure that cables are fitted with cable sleeves and are secured by connector clamps. Tighten connections with a torque of not less
than 35 inch-pounds.
NOTE: when shipped from the factory, bypass input and main R phase terminals
are shorted together.
CAUTION: Observe the appropriate cable connection regulations [e.g.
National Electrical Code (NEC) in the U.S.] at all times. Using cables of
improper size may damage your equipment and cause fire hazards. Ground
the UPS and the load equipment as shown in the figure.
6
(continued)
Installation
EXTERNAL BATTERY MODULE CONNECTION (required)
Connect the battery module to the power module. Consult the owner's man-
ual that came with your battery module. Fully insert the connector on the end
of the battery module's cable into the connector on the rear panel of the
power module. Small sparks may occur; this is normal. NOTE: the power
module does not contain internal batteries and will not start until a battery
module is connected. The battery modules are fully charged prior to ship-
ping. However, before expecting full backup capability (particularly if the
battery module has been stored for an extended period) after the UPS sys-
tem is connected to a utility power source, allow the battery module to
recharge for 12 hours. Once the UPS system is in use, it will charge the bat-
teries and maintain the charge level automatically. If needed, connect addi-
tional battery modules in a daisy-chain with each module's cable inserted
into the previous module's connector.
REFER TO USER'S MANUAL FOR TORQUING
SPECIFICATIONS, USE COPPER CONDUCTORS ONLY.
UTILISER SEULEMENT LES CONDUCTEURS DE CUIVRE.
Battery Module
Rear Panel
Power Module
Rear Panel
BATTERY CONDITION VERIFICATION
When the UPS is operating from battery power, the alarm and LCD Display will both alert you to the UPS battery’s charge condition.
Battery Charge Condition
FULL
Alarm
LCD Display
Short Beep (every 2 seconds)
ON BATTERY
BATT = XXV XX%
LOW
Short Beep (every 1/2 second)
Continuous Beep
BATTERY LOW
BATT = XXV XX%
UNDER
BATTERY UNDER
SHUT DOWN
7
Operation (Normal Conditions)
TURNING THE UPS ON
• Make sure the UPS is properly installed (see Installation section) and the Manual Bypass Key is set to NORMAL.
• Turn the AC Input and Bypass AC Input Circuit Breakers ON.
• If your AC input is providing power normally within your selected range (see Input Voltage Selection, and Specifications), your
connected load will energize. However, the UPS's inverter is not yet on. Press the front "ON/OFF" switch ON to begin inverter
operation.
• If your AC input is not providing power normally, you have the option of starting from battery. (Your battery must be at least
partially charged for this operation to succeed.) Press and hold both the "Battery Start" switch and the "ON/OFF" switch for three
seconds to start your UPS in "ON BATTERY" mode. Note that some electronic equipment may draw more amps during startup;
when starting from battery, consider reducing the initial load on the UPS.
• The UPS will perform a brief self-test and show the results on the LCD Display. (See Self-Test section, for display sequence.)
After a successful self-test, the UPS will provide AC power from the inverter to your load.
TURNING THE UPS OFF
• Press the front “ON/OFF” Switch OFF. Your load will still be energized. The inverter is now off, but your UPS is not fully
deactivated. The LCD Display will show “ON BYPASS."
• Turn the AC Input and Bypass AC Input Circuit Breakers OFF. Your load will no longer be energized, and the LCD display
will be dark.
8
(continued)
Operation (Normal Conditions)
SELF-TESTING
When you turn the UPS ON, it will perform a brief (about 25 second) self-test. See figure below for display sequence.*
*Note: If starting from battery, the BATTERY LED will be lit and the I/P and BYPASS LEDs will not. The final LCD display in the
diagram below appears when the UPS is operating normally under utility-supplied AC input power.
FREQ OUT = XXHz
AC INPUT OK!
OR
BATTERY OK!
BATTERY FAILURE!
CHARGER FAILURE!
AC/DC FAILURE!
OR
OR
CHARGER OK!
AC/DC OK!
WAIT!
TESTING INVERTER
ON INVERTER
LOAD = XXX% X.XXKW
9
(continued)
Operation (Normal Conditions)
LCD DISPLAY SELECT SWITCH
Momentarily press the “SELECT” switch on the front panel to browse through different power readings on the LCD Display. The LCD
Display will show which one of four operational modes your UPS is currently in: Normal, Economy, On-Battery, or Bypass. Also, as you
press the “SELECT” switch, the LCD Display will browse through load, input, bypass, output and battery conditions.
"NORMAL" MODE OPERATION
"ON-BATTERY" MODE OPERATION
ON INVERTER
LOAD = XXX% X.XXKW
ON BATTERY
LOAD = XXX% X.XXKW
PRESS SELECT KEY
PRESS SELECT KEY
ON INVERTER
IN R = XXXV XX.XHz
ON BATTERY
IN R = XXXV XX.XHz
PRESS SELECT KEY
PRESS SELECT KEY
ON BATTERY
IN S = XXXV T=XXXV
ON INVERTER
IN S = XXXV T=XXXV
PRESS SELECT KEY
PRESS SELECT KEY
ON BATTERY
OUT = XXXV XX.XHz
ON INVERTER
OUT = XXXV XX.XHz
PRESS SELECT KEY
PRESS SELECT KEY
ON BATTERY
BATT = XXXV XXX%
ON INVERTER
BATT = XXXV XXX%
PRESS SELECT KEY
PRESS SELECT KEY
"ECONOMY" MODE OPERATION
"ON BYPASS" MODE OPERATION
ECONOMY MODE
LOAD = XXX% X.XXKW
ON BYPASS
LOAD = XXX% X.XXKW
PRESS SELECT KEY
PRESS SELECT KEY
ECONOMY MODE
IN R = XXXV XX.XHz
ON BYPASS
BYPS = XXXV XX.XHz
PRESS SELECT KEY
PRESS SELECT KEY
ECONOMY MODE
IN S = XXXV T=XXXV
ON BYPASS
OUT = XXXV XXX%
PRESS SELECT KEY
PRESS SELECT KEY
ECONOMY MODE
OUT = XXXV XX.XHz
PRESS SELECT KEY
ECONOMY MODE
BATT = XXXV XXX%
PRESS SELECT KEY
Operation (Special Conditions)
OPERATION ON BYPASS—VOLTAGE OUT OF RANGE
While in Bypass Mode, the UPS monitors the input voltage, which on Bypass equals the output voltage. If the output voltage passes out of
an acceptable range (between 15% higher and 20% lower than nominal), the UPS displays the condition on its LCD and stops supplying
output power to its load. If power levels return to an acceptable level, the UPS resumes supplying power to the load, and its LCD reports
that output voltage was too high or too low at one time, but has returned to nominal.
Bypass Voltage Condition
>15% Higher than Nominal
>20% Lower than Nominal
Was Too High, Now Nominal
Was Too Low, Now Nominal
LCD Display Message
BYPASS HI NO O/P
BYPASS LO NO O/P
BYPASS WAS HI
BYPASS WAS LO
10
(continued)
Operation (Special Conditions)
OPERATION ON OVERLOAD
When the UPS detects an output overload, it will commence a countdown (the length of time depending on the severity of the overload).
If the UPS is still overloaded at the end of the countdown, the UPS will automatically shut down and go into Bypass Mode.
Overload Condition
102% - 125%
LCD Display Message
Countdown to Shutdown
1 minute
OVERLOAD 102%
LOAD=XXX% X.XXKW
125% - 150%
>150%
OVERLOAD 125%
30 seconds
2 seconds
LOAD=XXX% X.XXKW
OVERLOAD 150%
LOAD=XXX% X.XXKW
BATTERY CHARGE WARNINGS
Since your UPS can provide battery backup only for as long as the batteries remain charged, these warnings should be acted on immediately.
Battery Charge Warning
Battery charge nearly depleted
Low battery shutdown
LCD Display Message
BATTERY LOW
LOW BATTERY! SHUT DOWN…
OPERATION UNDER SHUTDOWN
Your UPS will shut down and the LCD will display a message if it detects one of the following conditions. Note: For all conditions, the
“Input,” “Output” and “Bypass” LEDs will be illuminated.
Condition
LCD Display Message
Extended Overload (>150%)
OVERLOAD XX%
SHUT DOWN…
Output Short Circuit
SHORT CIRCUIT!
SHUT DOWN…
Remote Shutdown Command
(from DB9 interface)
REMOTE
SHUT DOWN…
Remote Shutdown Command
(from RJ11 interface)
EMERGENCY STOP!
SHUT DOWN…
Internal Faults
INVERTER TOO LO
SHUT DOWN…
INVERTER TOO HI
SHUT DOWN…
DC BUS +/- HIGH/LOW
SHUT DOWN…
OVER TEMPERATURE
SHUT DOWN…
11
(continued)
Operation (Special Conditions)
OPERATION OF MANUAL BYPASS SWITCH
Turn this switch to “BYPASS” before performing any maintenance on the UPS with the connected load supported. Connected equipment
will receive filtered AC mains power, but will not receive battery power in the event of a blackout.
SWITCHING UPS TO “BYPASS” MODE
• Turn the “ON/OFF” Switch OFF. (LCD will read "ON BYPASS.")
• Turn the “Manual Bypass” Switch clockwise from NORMAL to BYPASS.
• Turn the AC Input Circuit Breaker OFF.
SWITCHING UPS TO “NORMAL” MODE
• Turn the AC Input Circuit Breaker ON.
• Turn the “Manual Bypass” Switch counterclockwise from BYPASS back to NORMAL.
• Turn the “ON/OFF” Switch ON.
Communications
RS-232 INTERFACE
This female DB9 port connects your UPS via an RS-232 cable to a workstation or server equipped with Tripp Lite software. The port uses
RS-232 communications to report UPS status and power conditions. Using this port, Tripp Lite software can monitor and manage network
power and automatically save open files and shut down equipment during a blackout. Contact Tripp Lite Customer Support at (773) 869-
1234 for information on available SNMP, network management and connectivity software and products.
RS-232 signals and operations include: load level, battery status, battery level, operation mode, AC input voltage, AC output voltage, AC
input frequency, temperature inside unit, set shut-down delay time, enable/disable alarm and remote shutdown.
Hardware:
Baud Rate:
Data Length:
Stop Bit:
2400 BPS
8 bits
1 bit
Parity:
NONE
Pin assignment:
Pin 2: TXD (Transmit Data)
Pin 3: RXD (Receive Data)
Pin 5: GND (Signal Ground)
12
(continued)
Communications
AS-400 INTERFACE
This female DB9 port connects your UPS to an IBM AS-400
computer via the included AS-400 cable. The port uses AS-400
communications to report UPS status. It can be used to allow an
AS-400 to automatically save open files and shut down its operat-
ing system during a blackout. AS-400 protocol includes: operation
on inverter, operation on AC power supply, operation on battery
and low battery alarm.
Pin assignment:
Pin 5: Common
Pin 6: Operation on AC power supply
Pin 7: Low battery alarm
Pin 8: Operation on inverter
Pin 9: Operation on battery
AS-400 INTERFACE TABLE
Pin 6,5
OFF
OFF
ON
Pin 7,5
*
Pin 8,5
ON
Pin 9,5
ON
Battery
Low Battery
Direct Mains Supply
Inverter
ON
OFF
*
ON
ON
OFF
ON
OFF
*
OFF
* Inactive: may be in either state.
DRY CONTACT INTERFACE
This female DB9 contact-closure port allows your UPS to
send contact-closure signals to indicate that it is on battery
back-up mode and if its batteries are running low. The port
can also receive a remote shutdown signal.
Pin assignment:
DRY CONTACT INTERFACE TABLE
UPS Operating
Mode
Pin 8,3
Pin 1,3
+ 3 V
Normal
OPEN
CLOSE
CLOSE
OPEN
*
-
Back Up
Low Battery
CLOSE
* Inactive: may be in either state.
13
(continued)
Communications
REMOTE EMERGENCY POWER OFF (EPO)
This optional feature is only for those applications which require connection to a facility's Emergency Power Off (EPO)circuit. When the
power module is connected to this circuit, it enables emergency shutdown of the output. Using the included cable, connect the power mod-
ule's EPO port to a user-supplied remote switch. The pin assignments for the EPO port are shown in the following diagram. Note: if there
is a short between pins 2 and 3, 2 and 5, 4 and 5, or 3 and 4, the UPS system will power off.
Pin assignment:
Service
Your SmartOnline UPS is covered by the 2-year limited warranty period described below. A variety of service contracts is also available
from Tripp Lite, including start-up service contracts and 3- to 5-year SafeSure on-site service contracts. For more information, call Tripp
Lite Customer Service at (773) 869-1234.
Warranty
2-Year Limited Warranty
TRIPP LITE warrants its products including batteries to be free from defects in materials and workmanship for a period of two years from the date of initial purchase. After 90 days
from the date of purchase, TRIPP LITE’s obligation under this warranty is limited to replacing parts on such defective products. To obtain service under this warranty, you must call
TRIPP LITE or an authorized TRIPP LITE service center. Products must be returned to TRIPP LITE or an authorized TRIPP LITE service center with transportation charges pre-
paid and must be accompanied by a brief description of the problem encountered and proof of date and place of purchase. This warranty does not apply to equipment which has
been damaged by accident, negligence or misapplication or has been altered or modified in any way. This warranty applies only to the original purchaser who must have properly
registered the product within 10 days of purchase.
The warranties of all TRIPP LITE surge suppressors are null and void if they have been connected to the output of any UPS system. The warranties of all TRIPP LITE UPS Systems
are null and void if a surge suppressor has been connected to its output receptacles.
EXCEPT AS PROVIDED HEREIN, TRIPP LITE MAKES NO WARRANTIES, EXPRESS OR IMPLIED, INCLUDING WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A
PARTICULAR PURPOSE. Some states do not permit limitation or exclusion of implied warranties; therefore, the aforesaid limitation(s) or exclusion(s) may not apply to the purchaser.
EXCEPT AS PROVIDED ABOVE, IN NO EVENT WILL TRIPP LITE BE LIABLE FOR DIRECT, INDIRECT, SPECIAL, INCIDENTAL OR CONSEQUENTIAL DAMAGES ARISING
OUT OF THE USE OF THIS PRODUCT, EVEN IF ADVISED OF THE POSSIBILITY OF SUCH DAMAGE. Specifically, TRIPP LITE is not liable for any costs, such as lost profits or
revenue, loss of equipment, loss of use of equipment, loss of software, loss of data, costs of substitutes, claims by third parties, or otherwise.
The policy of TRIPP LITE is one of continuous improvement. Specifications are subject to change without notice.
14
Specifications
The specifications listed below are for Tripp Lite model SU10K3/1X which includes two modules: a power module and a battery mod-
ule. The two modules are also sold separately with their own individual model numbers: power module (individual model #:
SU10K3/1INTPM) and battery module (individual model #: BP240V10RT3U).
Model: SU10K3/1X
Includes: • Power Module
• Battery Module
Model: SU10K3/1INTPM
Model: BP240V10RT3U
Series: AGBP240V7RT3U
Series: AGPS4984
Input
Input Voltage
270-485V, Y, 3Ø4W
Input Frequency
50/60 Hz 3 Hz (selectable)
Input Current
15A
Inrush Current
<200A
>0.95
>90%
Power Factor (Full Load)
Efficiency (Full Load/On-Line)
Circuit Breakers
32A 3 pole (AC Input Breaker), 63A 1 pole (Bypass AC Input Breaker)
Output
VA
10000
Watts (Power Factor: 0.8)
Waveform (On-Line)
Waveform (On-Battery)
Output Voltage (RMS)
Output Frequency
8000
Sinewave
Sinewave
220/230/240V AC 1Ø2W
50/60 Hz ( 0.2 Hz on battery)
Voltage Regulation
2%
Max. Harmonic Distortion (Non-Linear Full Load)
Overload Capabilities
Short Circuit Capability
Crest Factor
<3%
<
>
102% (continuous), 102%~125% (1 min.), 125%~150% (30 sec.), >150% (2 sec.)
160A
3:1
Battery
Battery Type
Battery Quantity
12V/9 AH
20
Protection
Typical Backup Time (Full Load)
Typical Backup Time (Half Load)
2x 30A/600V fuse
6+ min.
18+ min.
Operation
On-Line Transfer Time (Line to Battery, Battery to Line)
Audible Noise (Full Load @ 1 meter)
0 ms
<55 dBA
Indicators
Includes an LCD Display and LEDs (AC Line In, AC to DC, DC to AC, AC Output, Battery Back-Up, Bypass).
Communications
Includes an RS-232 DB9 female connector, an AS-400 DB9 female connector, a dry contact DB9 female connector and an accessory slot.
Connections
Input Terminal Block
Output Terminal Block
60A
60A
Physical Specifications
Power Module Dimensions (H x W x D):
Power Module Shipping Weight:
56.5 x 28 x 63 cm (22.2 x 11 x 24.8 in)
46 kg (101.3 lb)
Battery Module Dimensions (H x W x D):
44.5 x 13.3 x 57.2 cm (17.5 x 5.25 x 22.5 in)
Battery Module Shipping Weight:
86 kg (189.6 lb)
+ Backup times are expandable with additional Battery Modules (model: BP240V10RT3U) sold separately.
The policy of Tripp Lite is one of continuous improvement. Specifications are subject to change without notice.
15
1111 W. 35th Street, Chicago, IL 60609 USA
773.869.1234 (USA) • 773.869.1212 (International)
2009XXXXX 93-2228_EN
|