Tripp Lite Power Supply 220 230 240V AC 12W User Manual

Owner’s Manual  
SmartOnline 3-Phase 10kVA  
Intelligent True On-Line UPS System (Tower)  
Input (Voltage/Phase): 270 - 485V AC / Y, 3Ø4W  
Output (Voltage/Phase): User-Selectable 220/230/240V AC / 1Ø2W  
For all UPS system modules (power module and battery module) sold either separately or combined.  
Select UPS system modules may include separate instruction or warning sheets which should be used  
in conjunction with this manual.  
Register on-line for a chance to win a FREE Tripp Lite product! www.tripplite.com/warranty  
Important Safety Warnings  
Control Panel  
2
3
4
Rear Panels  
5
Installation  
8
Operation (Normal Conditions)  
Operation (Special Conditions)  
Communications  
10  
12  
14  
14  
Service  
Warranty  
Specifications  
15  
16/31/46/61  
Español / Français / Deutsche / Ðóññêèé  
1111 W. 35th Street • Chicago, IL 60609 USA  
Copyright ©2004 Tripp Lite. All rights reserved. SmartOnline™ is a trademark of Tripp Lite.  
 
Control Panel  
There are two separate UPS system modules: a power module and a battery module. Familiarize yourself with the location and function of  
the features on each module before installing and operating your UPS system. The power module is the only module which includes front  
panel features.  
FRONT PANEL  
ON  
SELECT  
OFF  
1. "ON/OFF" Switch: This momentary rocker switch turns the UPS System's inverter ON and OFF.  
2. "SELECT" Button: This button performs two functions: it allows you to browse through different power readings on the LCD Display  
by momentarily pressing the button; it also allows you to silence the UPS alarm by pressing and holding the button for 3 seconds.  
3. LCD Display: This backlit (16x2 character) dot matrix display indicates a wide range of UPS operating conditions and diagnostic data.  
It will illuminate after you have properly completed installation and start-up and after the "ON/OFF" Switch is turned ON.  
4. "I/P" (Input) LED: This green light will illuminate constantly to indicate an AC input supply is present.  
5. "AC/DC" (Converter) LED: This green light will illuminate constantly to indicate the UPS's AC/DC converter is activated.  
6. "DC/AC" (Inverter) LED: This green light will illuminate constantly to indicate the UPS's DC/AC inverter is activated.  
7. "O/P" (Output) LED: This green light will illuminate constantly to indicate your UPS is supplying AC power to connected equipment.  
8. "BYPASS" LED: This green light will illuminate when the UPS is providing filtered mains power without engaging its converter or  
inverter. Connected equipment will not receive battery power in the event of a blackout.  
9. "BATTERY" LED: This red light will illuminate when the UPS is discharging the battery to provide connected equipment with AC  
power. An alarm will sound which can be cancelled by pressing and holding the "SELECT" switch for 3 seconds. The alarm will be can-  
celled, but the LED will remain illuminated.  
3
 
Rear Panels  
14  
9
7
6
10  
5
8
13  
11  
1
15  
4
18  
12  
17  
REFER TO USER'S MANUAL FOR TORQUING  
SPECIFICATIONS, USE COPPER CONDUCTORS ONLY.  
UTILISER SEULEMENT LES CONDUCTEURS DE CUIVRE.  
3
2
16  
19  
Power Module Rear Panel  
Battery Module Rear Panel  
1. Manual Bypass Switch: This switch is used in one step of putting the UPS in "MANUAL BYPASS” mode, which must be done before  
performing any maintenance on the UPS with the connected load supported. [See “Operation (Special Conditions)” for step-by-step instruc-  
tions for going into "MANUAL BYPASS."] While this switch is on "MANUAL BYPASS," connected equipment will receive filtered AC  
mains power, but will not receive battery power in the event of a blackout.  
2. Input Terminal Block: Use these terminals to connect your UPS to the AC main power input. Unscrew and remove terminal block plate  
for access.  
3. Output Terminal Block: Use these terminals to connect your UPS to equipment. A plate covering the terminal block must be unscrewed  
and removed for access.  
4. External Battery Connector: Use this to connect a Tripp Lite battery module to the power module. Remove the cover for access. The  
power module will not start without a connection to a charged battery module. Refer to the battery module owner 's manual for connection  
instructions and safety warnings.  
5. Exhaust Fan: This cools and ventilates the inside of the UPS.  
6. AS-400 Interface Port: This female DB9 port connects your UPS to an IBM AS-400 computer interface via the AS-400 Cable includ-  
ed. It uses AS-400 communications to report UPS status and power conditions. Using this port, an IBM AS-400 computer can automati-  
cally save open files and shut down its operating system during a blackout. See “Communications” for details.  
7. “Smart” RS-232 Interface Port: This female DB9 port connects your UPS to a workstation or server. It uses RS-232 communications  
to report UPS and power conditions. It is used with Tripp Lite software and the included RS-232 Cable to monitor and manage network  
power and to automatically save open files and shut down equipment during a blackout. See “Communications” for details.  
8. Dry Contact Interface Port: This female DB9 port sends contact-closure signals to indicate line-fail and low-battery status. See  
“Communications,” for details.  
9. Accessory Slot: Remove the small cover panel and use optional accessories to remotely control and monitor your UPS. Contact Tripp  
Lite Customer Support for more information and a list of available SNMP, network management and connectivity products.  
4
 
(continued)  
Rear Panels  
10. “Battery Start” Switch: This momentary rocker switch allows you to “cold-start” your UPS and use it as a stand-alone power source  
when utility-supplied AC power is not present. The switch enables the UPS’s DC/AC Inverter. Before “cold-starting” your UPS, make sure  
your power module and external battery module(s) are properly installed. Press and hold the “Battery Start” Switch and then press the  
“ON/OFF” switch to turn your UPS ON. To turn it OFF after “cold-start,” press the “ON/OFF” Switch.  
11. AC Input Breaker: Controls input power to the UPS during normal operation.  
12. Bypass AC Input Breaker: Controls input power to the UPS during “BYPASS” operation.  
13. Remote “Emergency Power OFF” (EPO) Connector: This modular jack allows remote emergency shutdown. See  
“Communications” for details.  
14. Inverter Operation DIP Switches: Behind this removable panel are four DIP Switches that should be set to match your input voltage  
and input frequency. Your input voltage and frequency DIP switch settings MUST match your input. Your UPS WILL NOT CONVERT  
the voltage or frequency.  
15. Grounding Terminal: This terminal connects to a grounding electrode conductor. IT IS NOT SAFE TO OPERATE YOUR UPS  
WITHOUT CONNECTING IT. The recommended conductor size is 6 AWG based on the UL 1778 standard. Follow all applicable local  
electrical wiring regulations.  
16. Stabilizers: These supports extend to keep your UPS from rolling or tipping.  
17. Battery Module Input Connector: Use this connector to daisy-chain additional battery modules to the first. Remove the cover panel  
for access. Refer to the battery module's owner's manual for connection instructions and safety warnings.  
18. Battery Module Output Cable: Use this cable to connect the battery module to the power module (or to another battery module when  
using more than one). The power module will not start without a connection to a charged battery module. Refer to the battery module  
owner's manual for connection instructions and safety warnings.  
19. Tower Mounting: For additional stability during tower mounting of BP240V10RT3U External Battery Module, you can order Tripp  
Lite base stands (model #: 2-9USTAND) sold separately.  
Installation  
INVERTER OPERATION DIP SWITCH SETTINGS  
Using a small tool, set the four Inverter Operation DIP Switches (located on  
the rear panel of your UPS) to match your input voltage, input frequency and  
desired operational mode.  
Input Voltage Selection  
(DIP Switches #1 & #2)  
These DIP switches must be set to match your input voltage. Your UPS  
WILL NOT CONVERT the voltage.  
REFER TO USER'S MANUAL FOR TORQUING  
SPECIFICATIONS, USE COPPER CONDUCTORS ONLY.  
UTILISER SEULEMENT LES CONDUCTEURS DE CUIVRE.  
1
1
1
2
2
2
3
3
3
4
Input Voltage  
220V  
DIP Switch Position  
#1 UP & #2 DOWN  
#1 DOWN & #2 UP  
#1 DOWN & #2 DOWN  
220V  
230V  
4
240V  
230V  
Input Frequency Selection  
(DIP Switch #3)  
4
240V  
Your Input Frequency setting MUST match your input frequency. Your UPS  
WILL NOT CONVERT the frequency.  
1
1
2
2
3
3
4
Input Frequency  
50 Hz  
DIP Switch Position  
#3 UP  
50 Hz  
60 Hz  
4
60 Hz  
#3 DOWN  
5
 
(continued)  
Installation  
Operational Mode Selection  
(DIP Switch #4)  
The "On-Line" Mode provides on-line operation with zero transfer time. The "Economy" Mode provides line-interactive operation for  
increased efficiency when on-line protection is unnecessary, thus reducing operating costs without affecting your UPS's output reliability  
during a power outage.  
1
2
3
4
Operational Mode  
On-Line  
DIP Switch Position  
#4 UP  
On-Line  
Economy  
1
2
3
4
Economy  
#4 DOWN  
UPS LOCATION  
Move your UPS over short distances using its wheels. Stabilize the UPS by releasing the stabilizers on each side of the unit. NOTE: Do not  
stack the UPS System power module or external battery modules.  
INPUT AND OUTPUT CONNECTION  
WIRING SELECTION  
Choose appropriate cabling (cabling should have a temperature rating of 70° C and 6 AWG size) to connect your UPS to an AC power  
supply and your equipment to your UPS.  
WIRING CONNECTIONS  
Connect your wiring to the input and output terminal blocks located on the lower rear panel of your UPS (see figure below).  
CAUTION!  
Qualified personnel should follow all procedures prescribed by N.E.C. and other local codes for hardwiring devices to a utility source.  
Ensure that cables are fitted with cable sleeves and are secured by connector clamps. Tighten connections with a torque of not less  
than 35 inch-pounds.  
NOTE: when shipped from the factory, bypass input and main R phase terminals  
are shorted together.  
CAUTION: Observe the appropriate cable connection regulations [e.g.  
National Electrical Code (NEC) in the U.S.] at all times. Using cables of  
improper size may damage your equipment and cause fire hazards. Ground  
the UPS and the load equipment as shown in the figure.  
6
 
(continued)  
Installation  
EXTERNAL BATTERY MODULE CONNECTION (required)  
Connect the battery module to the power module. Consult the owner's man-  
ual that came with your battery module. Fully insert the connector on the end  
of the battery module's cable into the connector on the rear panel of the  
power module. Small sparks may occur; this is normal. NOTE: the power  
module does not contain internal batteries and will not start until a battery  
module is connected. The battery modules are fully charged prior to ship-  
ping. However, before expecting full backup capability (particularly if the  
battery module has been stored for an extended period) after the UPS sys-  
tem is connected to a utility power source, allow the battery module to  
recharge for 12 hours. Once the UPS system is in use, it will charge the bat-  
teries and maintain the charge level automatically. If needed, connect addi-  
tional battery modules in a daisy-chain with each module's cable inserted  
into the previous module's connector.  
REFER TO USER'S MANUAL FOR TORQUING  
SPECIFICATIONS, USE COPPER CONDUCTORS ONLY.  
UTILISER SEULEMENT LES CONDUCTEURS DE CUIVRE.  
Battery Module  
Rear Panel  
Power Module  
Rear Panel  
BATTERY CONDITION VERIFICATION  
When the UPS is operating from battery power, the alarm and LCD Display will both alert you to the UPS battery’s charge condition.  
Battery Charge Condition  
FULL  
Alarm  
LCD Display  
Short Beep (every 2 seconds)  
ON BATTERY  
BATT = XXV XX%  
LOW  
Short Beep (every 1/2 second)  
Continuous Beep  
BATTERY LOW  
BATT = XXV XX%  
UNDER  
BATTERY UNDER  
SHUT DOWN  
7
 
Operation (Normal Conditions)  
TURNING THE UPS ON  
• Make sure the UPS is properly installed (see Installation section) and the Manual Bypass Key is set to NORMAL.  
• Turn the AC Input and Bypass AC Input Circuit Breakers ON.  
• If your AC input is providing power normally within your selected range (see Input Voltage Selection, and Specifications), your  
connected load will energize. However, the UPS's inverter is not yet on. Press the front "ON/OFF" switch ON to begin inverter  
operation.  
• If your AC input is not providing power normally, you have the option of starting from battery. (Your battery must be at least  
partially charged for this operation to succeed.) Press and hold both the "Battery Start" switch and the "ON/OFF" switch for three  
seconds to start your UPS in "ON BATTERY" mode. Note that some electronic equipment may draw more amps during startup;  
when starting from battery, consider reducing the initial load on the UPS.  
• The UPS will perform a brief self-test and show the results on the LCD Display. (See Self-Test section, for display sequence.)  
After a successful self-test, the UPS will provide AC power from the inverter to your load.  
TURNING THE UPS OFF  
• Press the front “ON/OFF” Switch OFF. Your load will still be energized. The inverter is now off, but your UPS is not fully  
deactivated. The LCD Display will show “ON BYPASS."  
• Turn the AC Input and Bypass AC Input Circuit Breakers OFF. Your load will no longer be energized, and the LCD display  
will be dark.  
8
 
(continued)  
Operation (Normal Conditions)  
SELF-TESTING  
When you turn the UPS ON, it will perform a brief (about 25 second) self-test. See figure below for display sequence.*  
*Note: If starting from battery, the BATTERY LED will be lit and the I/P and BYPASS LEDs will not. The final LCD display in the  
diagram below appears when the UPS is operating normally under utility-supplied AC input power.  
FREQ OUT = XXHz  
AC INPUT OK!  
OR  
BATTERY OK!  
BATTERY FAILURE!  
CHARGER FAILURE!  
AC/DC FAILURE!  
OR  
OR  
CHARGER OK!  
AC/DC OK!  
WAIT!  
TESTING INVERTER  
ON INVERTER  
LOAD = XXX% X.XXKW  
9
 
(continued)  
Operation (Normal Conditions)  
LCD DISPLAY SELECT SWITCH  
Momentarily press the “SELECT” switch on the front panel to browse through different power readings on the LCD Display. The LCD  
Display will show which one of four operational modes your UPS is currently in: Normal, Economy, On-Battery, or Bypass. Also, as you  
press the “SELECT” switch, the LCD Display will browse through load, input, bypass, output and battery conditions.  
"NORMAL" MODE OPERATION  
"ON-BATTERY" MODE OPERATION  
ON INVERTER  
LOAD = XXX% X.XXKW  
ON BATTERY  
LOAD = XXX% X.XXKW  
PRESS SELECT KEY  
PRESS SELECT KEY  
ON INVERTER  
IN R = XXXV XX.XHz  
ON BATTERY  
IN R = XXXV XX.XHz  
PRESS SELECT KEY  
PRESS SELECT KEY  
ON BATTERY  
IN S = XXXV T=XXXV  
ON INVERTER  
IN S = XXXV T=XXXV  
PRESS SELECT KEY  
PRESS SELECT KEY  
ON BATTERY  
OUT = XXXV XX.XHz  
ON INVERTER  
OUT = XXXV XX.XHz  
PRESS SELECT KEY  
PRESS SELECT KEY  
ON BATTERY  
BATT = XXXV XXX%  
ON INVERTER  
BATT = XXXV XXX%  
PRESS SELECT KEY  
PRESS SELECT KEY  
"ECONOMY" MODE OPERATION  
"ON BYPASS" MODE OPERATION  
ECONOMY MODE  
LOAD = XXX% X.XXKW  
ON BYPASS  
LOAD = XXX% X.XXKW  
PRESS SELECT KEY  
PRESS SELECT KEY  
ECONOMY MODE  
IN R = XXXV XX.XHz  
ON BYPASS  
BYPS = XXXV XX.XHz  
PRESS SELECT KEY  
PRESS SELECT KEY  
ECONOMY MODE  
IN S = XXXV T=XXXV  
ON BYPASS  
OUT = XXXV XXX%  
PRESS SELECT KEY  
PRESS SELECT KEY  
ECONOMY MODE  
OUT = XXXV XX.XHz  
PRESS SELECT KEY  
ECONOMY MODE  
BATT = XXXV XXX%  
PRESS SELECT KEY  
Operation (Special Conditions)  
OPERATION ON BYPASS—VOLTAGE OUT OF RANGE  
While in Bypass Mode, the UPS monitors the input voltage, which on Bypass equals the output voltage. If the output voltage passes out of  
an acceptable range (between 15% higher and 20% lower than nominal), the UPS displays the condition on its LCD and stops supplying  
output power to its load. If power levels return to an acceptable level, the UPS resumes supplying power to the load, and its LCD reports  
that output voltage was too high or too low at one time, but has returned to nominal.  
Bypass Voltage Condition  
>15% Higher than Nominal  
>20% Lower than Nominal  
Was Too High, Now Nominal  
Was Too Low, Now Nominal  
LCD Display Message  
BYPASS HI NO O/P  
BYPASS LO NO O/P  
BYPASS WAS HI  
BYPASS WAS LO  
10  
 
(continued)  
Operation (Special Conditions)  
OPERATION ON OVERLOAD  
When the UPS detects an output overload, it will commence a countdown (the length of time depending on the severity of the overload).  
If the UPS is still overloaded at the end of the countdown, the UPS will automatically shut down and go into Bypass Mode.  
Overload Condition  
102% - 125%  
LCD Display Message  
Countdown to Shutdown  
1 minute  
OVERLOAD 102%  
LOAD=XXX% X.XXKW  
125% - 150%  
>150%  
OVERLOAD 125%  
30 seconds  
2 seconds  
LOAD=XXX% X.XXKW  
OVERLOAD 150%  
LOAD=XXX% X.XXKW  
BATTERY CHARGE WARNINGS  
Since your UPS can provide battery backup only for as long as the batteries remain charged, these warnings should be acted on immediately.  
Battery Charge Warning  
Battery charge nearly depleted  
Low battery shutdown  
LCD Display Message  
BATTERY LOW  
LOW BATTERY! SHUT DOWN…  
OPERATION UNDER SHUTDOWN  
Your UPS will shut down and the LCD will display a message if it detects one of the following conditions. Note: For all conditions, the  
“Input,” “Output” and “Bypass” LEDs will be illuminated.  
Condition  
LCD Display Message  
Extended Overload (>150%)  
OVERLOAD XX%  
SHUT DOWN…  
Output Short Circuit  
SHORT CIRCUIT!  
SHUT DOWN…  
Remote Shutdown Command  
(from DB9 interface)  
REMOTE  
SHUT DOWN…  
Remote Shutdown Command  
(from RJ11 interface)  
EMERGENCY STOP!  
SHUT DOWN…  
Internal Faults  
INVERTER TOO LO  
SHUT DOWN…  
INVERTER TOO HI  
SHUT DOWN…  
DC BUS +/- HIGH/LOW  
SHUT DOWN…  
OVER TEMPERATURE  
SHUT DOWN…  
11  
 
(continued)  
Operation (Special Conditions)  
OPERATION OF MANUAL BYPASS SWITCH  
Turn this switch to “BYPASS” before performing any maintenance on the UPS with the connected load supported. Connected equipment  
will receive filtered AC mains power, but will not receive battery power in the event of a blackout.  
SWITCHING UPS TO “BYPASS” MODE  
• Turn the “ON/OFF” Switch OFF. (LCD will read "ON BYPASS.")  
• Turn the “Manual Bypass” Switch clockwise from NORMAL to BYPASS.  
• Turn the AC Input Circuit Breaker OFF.  
SWITCHING UPS TO “NORMALMODE  
• Turn the AC Input Circuit Breaker ON.  
• Turn the “Manual Bypass” Switch counterclockwise from BYPASS back to NORMAL.  
• Turn the “ON/OFF” Switch ON.  
Communications  
RS-232 INTERFACE  
This female DB9 port connects your UPS via an RS-232 cable to a workstation or server equipped with Tripp Lite software. The port uses  
RS-232 communications to report UPS status and power conditions. Using this port, Tripp Lite software can monitor and manage network  
power and automatically save open files and shut down equipment during a blackout. Contact Tripp Lite Customer Support at (773) 869-  
1234 for information on available SNMP, network management and connectivity software and products.  
RS-232 signals and operations include: load level, battery status, battery level, operation mode, AC input voltage, AC output voltage, AC  
input frequency, temperature inside unit, set shut-down delay time, enable/disable alarm and remote shutdown.  
Hardware:  
Baud Rate:  
Data Length:  
Stop Bit:  
2400 BPS  
8 bits  
1 bit  
Parity:  
NONE  
Pin assignment:  
Pin 2: TXD (Transmit Data)  
Pin 3: RXD (Receive Data)  
Pin 5: GND (Signal Ground)  
12  
 
(continued)  
Communications  
AS-400 INTERFACE  
This female DB9 port connects your UPS to an IBM AS-400  
computer via the included AS-400 cable. The port uses AS-400  
communications to report UPS status. It can be used to allow an  
AS-400 to automatically save open files and shut down its operat-  
ing system during a blackout. AS-400 protocol includes: operation  
on inverter, operation on AC power supply, operation on battery  
and low battery alarm.  
Pin assignment:  
Pin 5: Common  
Pin 6: Operation on AC power supply  
Pin 7: Low battery alarm  
Pin 8: Operation on inverter  
Pin 9: Operation on battery  
AS-400 INTERFACE TABLE  
Pin 6,5  
OFF  
OFF  
ON  
Pin 7,5  
*
Pin 8,5  
ON  
Pin 9,5  
ON  
Battery  
Low Battery  
Direct Mains Supply  
Inverter  
ON  
OFF  
*
ON  
ON  
OFF  
ON  
OFF  
*
OFF  
* Inactive: may be in either state.  
DRY CONTACT INTERFACE  
This female DB9 contact-closure port allows your UPS to  
send contact-closure signals to indicate that it is on battery  
back-up mode and if its batteries are running low. The port  
can also receive a remote shutdown signal.  
Pin assignment:  
DRY CONTACT INTERFACE TABLE  
UPS Operating  
Mode  
Pin 8,3  
Pin 1,3  
+ 3 V  
Normal  
OPEN  
CLOSE  
CLOSE  
OPEN  
*
-
Back Up  
Low Battery  
CLOSE  
* Inactive: may be in either state.  
13  
 
(continued)  
Communications  
REMOTE EMERGENCY POWER OFF (EPO)  
This optional feature is only for those applications which require connection to a facility's Emergency Power Off (EPO)circuit. When the  
power module is connected to this circuit, it enables emergency shutdown of the output. Using the included cable, connect the power mod-  
ule's EPO port to a user-supplied remote switch. The pin assignments for the EPO port are shown in the following diagram. Note: if there  
is a short between pins 2 and 3, 2 and 5, 4 and 5, or 3 and 4, the UPS system will power off.  
Pin assignment:  
Service  
Your SmartOnline UPS is covered by the 2-year limited warranty period described below. A variety of service contracts is also available  
from Tripp Lite, including start-up service contracts and 3- to 5-year SafeSure on-site service contracts. For more information, call Tripp  
Lite Customer Service at (773) 869-1234.  
Warranty  
2-Year Limited Warranty  
TRIPP LITE warrants its products including batteries to be free from defects in materials and workmanship for a period of two years from the date of initial purchase. After 90 days  
from the date of purchase, TRIPP LITE’s obligation under this warranty is limited to replacing parts on such defective products. To obtain service under this warranty, you must call  
TRIPP LITE or an authorized TRIPP LITE service center. Products must be returned to TRIPP LITE or an authorized TRIPP LITE service center with transportation charges pre-  
paid and must be accompanied by a brief description of the problem encountered and proof of date and place of purchase. This warranty does not apply to equipment which has  
been damaged by accident, negligence or misapplication or has been altered or modified in any way. This warranty applies only to the original purchaser who must have properly  
registered the product within 10 days of purchase.  
The warranties of all TRIPP LITE surge suppressors are null and void if they have been connected to the output of any UPS system. The warranties of all TRIPP LITE UPS Systems  
are null and void if a surge suppressor has been connected to its output receptacles.  
EXCEPT AS PROVIDED HEREIN, TRIPP LITE MAKES NO WARRANTIES, EXPRESS OR IMPLIED, INCLUDING WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A  
PARTICULAR PURPOSE. Some states do not permit limitation or exclusion of implied warranties; therefore, the aforesaid limitation(s) or exclusion(s) may not apply to the purchaser.  
EXCEPT AS PROVIDED ABOVE, IN NO EVENT WILL TRIPP LITE BE LIABLE FOR DIRECT, INDIRECT, SPECIAL, INCIDENTAL OR CONSEQUENTIAL DAMAGES ARISING  
OUT OF THE USE OF THIS PRODUCT, EVEN IF ADVISED OF THE POSSIBILITY OF SUCH DAMAGE. Specifically, TRIPP LITE is not liable for any costs, such as lost profits or  
revenue, loss of equipment, loss of use of equipment, loss of software, loss of data, costs of substitutes, claims by third parties, or otherwise.  
The policy of TRIPP LITE is one of continuous improvement. Specifications are subject to change without notice.  
14  
 
Specifications  
The specifications listed below are for Tripp Lite model SU10K3/1X which includes two modules: a power module and a battery mod-  
ule. The two modules are also sold separately with their own individual model numbers: power module (individual model #:  
SU10K3/1INTPM) and battery module (individual model #: BP240V10RT3U).  
Model: SU10K3/1X  
Includes: • Power Module  
• Battery Module  
Model: SU10K3/1INTPM  
Model: BP240V10RT3U  
Series: AGBP240V7RT3U  
Series: AGPS4984  
Input  
Input Voltage  
270-485V, Y, 3Ø4W  
Input Frequency  
50/60 Hz 3 Hz (selectable)  
Input Current  
15A  
Inrush Current  
<200A  
>0.95  
>90%  
Power Factor (Full Load)  
Efficiency (Full Load/On-Line)  
Circuit Breakers  
32A 3 pole (AC Input Breaker), 63A 1 pole (Bypass AC Input Breaker)  
Output  
VA  
10000  
Watts (Power Factor: 0.8)  
Waveform (On-Line)  
Waveform (On-Battery)  
Output Voltage (RMS)  
Output Frequency  
8000  
Sinewave  
Sinewave  
220/230/240V AC 1Ø2W  
50/60 Hz ( 0.2 Hz on battery)  
Voltage Regulation  
2%  
Max. Harmonic Distortion (Non-Linear Full Load)  
Overload Capabilities  
Short Circuit Capability  
Crest Factor  
<3%  
<
>
102% (continuous), 102%~125% (1 min.), 125%~150% (30 sec.), >150% (2 sec.)  
160A  
3:1  
Battery  
Battery Type  
Battery Quantity  
12V/9 AH  
20  
Protection  
Typical Backup Time (Full Load)  
Typical Backup Time (Half Load)  
2x 30A/600V fuse  
6+ min.  
18+ min.  
Operation  
On-Line Transfer Time (Line to Battery, Battery to Line)  
Audible Noise (Full Load @ 1 meter)  
0 ms  
<55 dBA  
Indicators  
Includes an LCD Display and LEDs (AC Line In, AC to DC, DC to AC, AC Output, Battery Back-Up, Bypass).  
Communications  
Includes an RS-232 DB9 female connector, an AS-400 DB9 female connector, a dry contact DB9 female connector and an accessory slot.  
Connections  
Input Terminal Block  
Output Terminal Block  
60A  
60A  
Physical Specifications  
Power Module Dimensions (H x W x D):  
Power Module Shipping Weight:  
56.5 x 28 x 63 cm (22.2 x 11 x 24.8 in)  
46 kg (101.3 lb)  
Battery Module Dimensions (H x W x D):  
44.5 x 13.3 x 57.2 cm (17.5 x 5.25 x 22.5 in)  
Battery Module Shipping Weight:  
86 kg (189.6 lb)  
+ Backup times are expandable with additional Battery Modules (model: BP240V10RT3U) sold separately.  
The policy of Tripp Lite is one of continuous improvement. Specifications are subject to change without notice.  
15  
 
1111 W. 35th Street, Chicago, IL 60609 USA  
773.869.1234 (USA) • 773.869.1212 (International)  
2009XXXXX 93-2228_EN  
 

Telex Stereo Receiver MXR290 User Manual
TIMEX Weather Products Thermometer TX3100 User Manual
Toshiba CRT Television 20A42 User Manual
TRENDnet Computer Accessories TRENDnet User Manual
Tripp Lite Fan MKH 800 P 48 User Manual
Tripp Lite Surge Protector 200401086 User Manual
Tripp Lite Surge Protector TLM406NC User Manual
Tripp Lite TV Cables U233 008 User Manual
Viper Remote Starter VSM200 User Manual
Vizio Video Games E420d A0 User Manual