INSTALLATION AND MAINTENANCE INSTRUCTIONS
FTX-P1 Filtrex® Intelligent
Photoelectronic Smoke Detector
A Division of Pittway
3825 Ohio Avenue, St. Charles, Illinois 60174
1-800-SENSOR2, FAX: 630-377-6495
Specifications
Operating Voltage Range:
Detector Current:
15 to 32 VDC
230 µA @ 24 VDC (without communication)
285 µA @ 24 VDC (one communication every 5 sec. with LED enabled)
Auxiliary Power Supply Voltage:
Auxilary Power Supply Current –
Peak:
15 to 30 VDC filtered; Ripple voltage may not drop below 15 volts.
123 mA max.
Average:
27 mA max.
Operating Humidity Range:
Operating Temperature Range:
Height:
10% to 93% Relative Humidity, noncondensing
0° to 50° C (32° to 122°F)
2.8 inches (43 mm)
Diameter:
6.1 inches (155 mm) installed in B501B-FTX
4.0 inches (102 mm) installed in B524FTXE
7.3 oz. (207 g)
Weight:
Compatibility:
Backwards compatible with 200 and 500 series products’ protocol
Mounting Base:
Requires B501B-FTX (U.S.), B524FTXE (Europe)
Before Installing
This detector must be installed in compliance with the
control panel system installation manual. The installation
must meet the requirements of the Authority Having Juris-
diction (AHJ). Detectors offer maximum performance
when installed in compliance with the National Fire Pro-
tection Association (NFPA); see NFPA 72.
General Description
Filtrex® uses a small air intake fan and a high density re-
placeable filter. Air and smoke are drawn into a photoelec-
tric sensing chamber while airborne particulate and water
mist are removed. The addressable-analog detector trans-
mits an analog representation of smoke density over a com-
munication line to a control panel. Rotary-decade switches
are provided for setting the sensor’s address. Two LEDs on
the sensor are controlled by the panel to indicate sensor
status.
Spacing
Filtrex smoke detector is intended for use in normal en- System Sensor recommends spacing detectors in compli-
vironmental conditions, where dust and other airborne ance with NFPA 72. In low air flow applications with
particulate are present at elevated levels. These elevated smooth ceilings, space detectors 30 feet apart. For specific
levels tend to cause false alarms and high maintenance information regarding sensor spacing, placement, and spe-
in standard detectors. Filtrex provides a protective enclo- cial applications, refer to NFPA 72 or the System Sensor
sure for a photoelectric smoke detector chamber and al- Guide For Proper Use of System Smoke Detectors, available
lows smoke detection in areas that tended to use from System Sensor (P/ N I56-407-XX).
exclusively heat detection.
WARNING
Filtrex requires compatible addressable communications
to function properly. Connect this detector to listed-com-
patible control panels only.
Filtrex is not designed to operate in explosive environments.
D200-72-00
1
I56-1184-04R
Figure 2. Rotary decade address switches:
the detector still fails any test, have its filter replaced (see in-
structions below) and retested. Finally, if the detector contin-
ues to fail after replacing the filter, it must be returned for
repair or replacement.
4
5
4 5
3
2
3
2
6
7
6
When testing is complete, restore the system to normal op-
eration and notify the proper authorities that the system is
back in operation.
7
Cleaning
8
8
1
1
The unique design of Filtrex eliminates the need for typical
detector cleaning. The only maintenance necessary is re-
placing the filter, which is signaled by a trouble condition
at the panel (see below).
0
9
0
9
A78-2460-00
Figure 3. Test magnet position:
Filtrex has been designed to maximize the amount of time
before maintenance is required. Filtrex utilizes a replaceable
filter that may become clogged over time. Filtrex monitors
itself to insure that the filter has not become clogged. Be-
cause environmental conditions can vary significantly, the
amount of time before maintenance could vary significantly
as well. To fully understand the maintenance requirements
of Filtrex in its installed location, it is recommended that the
following test program be conducted.
TEST MAGNET
MARKER
1. Install Filtrex in the desired location.
2. Connect Filtrex to the fire alarm control panel.
3. Maintain a record for at least 90 days of any mainte-
nance performed on or required by Filtrex.
4. At the end of the test period, use the record to develop
and schedule maintenance. Filtrex detectors should be
serviced at regular intervals to insure that the fire alarm
system provides continuous protection.
Replacing the Filter
IMPORTANT:
When the filter becomes too clogged to draw ad-
equate air into Filtrex, power is automatically cut
from the detector, sending a trouble signal to the
fire control panel. After 5 minutes, power is re-
stored to the detector for 72 hours. After 72 hours,
power is cut again and the detector will remain off-
line until the filter is replaced.
Figure 4. Replacing the filter cover:
Note: The unit has two filters. The replaceable filter is in-
side the cover. A permanent filter is mounted to the unit.
1. Grasp the Filtrex housing with one hand and the cover
with the other. Turn the cover counterclockwise fully
(approx. 30 degrees) and remove cover by pulling it
away from detector unit (see Figure 4).
Cover is keyed to
fit into 4 matching
size slots.
Alignment marks are
provided on the cap
and top of the
2.Replace with new filter and cover assembly. The cover is
keyed so it fits in place only one way. Turn the cover
clockwise until it stops.
permanent filter.
NOTE: The base is equipped with an optional tamperproof
feature which can be used to prevent unintentional removal
of Filtrex while replacing the filter.
D200-72-00
3
I56-1184-04R
If a clogged filter was the cause of the trouble condition, Figure 5: Installing Filtrex detector into base:
normal detector operation should resume automatically
within five minutes. If the trouble condition persists, the
detector must be returned for repair or replacement.
Installing Filtrex Into Base
1. Align the detector at a right angle to the base, with the
five wires and connector adjacent to the connector re-
ceptacle as shown in Figure 5.
2. Plug the wired connector into the receptacle.
3. Rotate the detector into the base, making sure detector
and base keyed fit is lined up. Turn the detector clock-
wise until it snaps into place.
IMPORTANT: Filtrex will only operate with B501B-FTX/
B524FTXE Mounting Base.
Please refer to insert for the Limitations of Fire Alarm Systems
Three-Year Limited Warranty
System Sensor warrants its enclosed smoke detector to be free from de-
fects in materials and workmanship under normal use and service for a
period of three years from date of manufacture. System Sensor makes no
other express warranty for this smoke detector. No agent, representative,
dealer, or employee of the Company has the authority to increase or alter
the obligations or limitations of this Warranty. The Company’s obligation
of this Warranty shall be limited to the repair or replacement of any part of
the smoke detector which is found to be defective in materials or work-
manship under normal use and service during the three year period com-
mencing with the date of manufacture. After phoning System Sensor’s toll
free number 800-SENSOR2 (736-7672) for a Return Authorization number,
send defective units postage prepaid to: System Sensor, Repair Depart-
ment, RA #__________, 3825 Ohio Avenue, St. Charles, IL 60174. Please
include a note describing the malfunction and suspected cause of failure.
The Company shall not be obligated to repair or replace units which are
found to be defective because of damage, unreasonable use, modifica-
tions, or alterations occurring after the date of manufacture. In no case
shall the Company be liable for any consequential or incidental damages
for breach of this or any other Warranty, expressed or implied whatsoever,
even if the loss or damage is caused by the Company’s negligence or fault.
Some states do not allow the exclusion or limitation of incidental or conse-
quential damages, so the above limitation or exclusion may not apply to
you. This Warranty gives you specific legal rights, and you may also have
other rights which vary from state to state.
FCC Statement
This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interfer-
ence, and (2) this device must accept any interference received, including interference that may cause undesired operation.
Note: This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to Part 15 of the FCC Rules. These limits
are designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates, uses and can
radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio commu-
nications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interfer-
ence to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the
interference by one or more of the following measures:
– Reorient or relocate the receiving antenna.
– Increase the separation between the equipment and receiver.
– Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.
– Consult the dealer or an experienced radio/ TV technician for help.
D200-72-00
4
I56-1184-04R