INSTALLATION AND MAINTENANCE INSTRUCTIONS
DH200RPL Intelligent Air Duct Smoke Detector
with Extended Air Speed Range
3825 Ohio Avenue, St. Charles, Illinois 60174
800/736-7672, FAX: 630-377-6495
Before installing detectors, please thoroughly read the NEMA Guide for
Proper Use of Smoke Detectors in Duct Applications, which provides
detailed information on detector spacing, placement, zoning, wiring,
and special applications. Copies of this manual are available from
NEMA (National Electrical Manufacturers Association, 2101 L Street NW,
Washington, DC 20037). NFPA Standards 72 and 90A should also be ref-
erenced for detailed information.
The DH200RPL air duct smoke detector is photoelectric detector. This
smoke detection method combines with an efficient housing design that
samples air passing through a duct and allows detection of a developing
hazardous condition. When sufficient smoke is sensed, an alarm signal is
initiated at the fire control panel monitoring the detector, and appropriate
action can be taken to shut off fans, blowers and change over air handling
systems, etc. This can prevent the distribution or it can isolate toxic smoke
and fire gases throughout the areas served by the duct system.
NOTICE: This manual shall be left with the owner/user of this
equipment.
Two LEDs on each detector may illuminate, if programmed by the system
control panel, to provide a local alarm indication. There is also a remote
alarm output for use with auxiliary devices. The DH200RPL has remote
test capability with the RTS451/RTS451KEY Remote Test Station.
IMPORTANT: This detector must be tested and maintained regularly fol-
lowing NFPA 72 requirements. The detector should be cleaned at least
once a year.
The DH200RPL incorporates a cover tamper feature. When the cover is
removed for more than 20 minutes, the unit loses communication at the
panel, a trouble is indicated at the panel and the alarm relay switches
states thereby shutting down fans, dampers and blowers. In the case
when the sensor is removed or when there is no power to the unit, only a
trouble is indicated at the panel (alarm relay does not work any longer).
General Description
An HVAC system supplies conditioned air to virtually every area of
a building. Smoke introduced into this air duct system is distrib-
uted to the entire building. Smoke detectors designed for use in air
duct systems are used to sense the presence of smoke in the duct.
Contents of the Duct Smoke Detector Housing Kit
The DH200RPL Duct Smoke Detector consists of the following items
(See Figure 1.):
Contents Of The Duct Smoke Detector
1. Complete duct smoke detector assembly with
sensor
Figure 1. Exploded View Of Duct Smoke Detector Components:
1
2. Two #10 x 1 ⁄4″ sheet metal mounting screws
FOAM
GASKETS
3. Two sampling tube filters
4. One test magnet
CONDUIT HOLES
DETECTOR
5. Drilling template
SAMPLING TUBE
FILTERS
HOUSING
6. Two foam gaskets
7. Four #6-self tapping mounting screws for the
sampling tube and optional exhaust tube
extension
SAMPLING TUBE
TERMINAL STRIP
POWER BOARD
8. One sampling tube end cap
9. One plastic sampling tube
10. One #8 self-tapping screw for plastic sampling
tube
COVER MOUNTING
SCREWS
DETECTOR BOARD
NOTE: A detector sensor board DOES NOT need to
be ordered separately.
DETECTOR
COVER
1
NOTE:
For ducts over 1 ⁄2 feet (0.46m), longer sampling tubes must be ordered to complete the installation. They must be the correct length for the
width of the duct where they will be installed. See Table 1 on page 3 to determine the sampling tube required for different duct widths.
D200-39-00
1
I56-1977-004R
2. Slide the tube into the housing bushing that meets the air flow first.
Position the tube so that the arrow points into the air flow, as shown
in Figure 4.
Figure 5. Tube mounting configurations with varying
air flow direction:
DOTS INDICATE POSITION OF
SAMPLING TUBE HOLES
3. Secure the tube flange to the housing bushing with two #6 self-tapping
screws.
AIR FLOW
AIR FLOW
DIRECTION
DIRECTION
DETECTOR
HOUSING
DETECTOR
HOUSING
4. For tubes longer than the width of the air duct, the tube should extend
out of the opposite side of the duct. If there are more than 2 holes in
the section of the tube extending out of the duct, select a different
length using Table 1. Otherwise, trim the end of the tube protruding
through the duct so that 1″ to 2″ (25 to 50mm) of the tube extend
outside the duct. Plug this end with the end cap and tape closed any
holes in the protruding section of the tube. Be sure to seal the duct
where the tube protrudes.
B.
A.
SAMPLING
TUBE
EXHAUST
TUBE
EXHAUST
TUBE
SAMPLING
TUBE
HORIZONTAL MOUNTING OF HOUSING
DETECTOR
HOUSING
EXHAUST
TUBE
AIR FLOW
DIRECTION
AIR FLOW
DIRECTION
NOTE: The sampling tube end cap is critical to the proper operation of the
duct smoke detectors. The end cap is needed to create the proper air flow
to the sensor of the duct smoke detector.
SAMPLING
DETECTOR
HOUSING
TUBE
D.
C.
VERTICAL MOUNTING OF HOUSING
NOTE: Only metal sampling tubes can be installed in
orientations C and D.
Figure 3. Installation of foam gaskets over
sampling tube bushings:
SCREW HOLES FOR
ATTACHING HOUSING
TO DUCT WORK.
[4.2] Installation For Ducts More Than 8 Feet (2.4m) Wide
NOTE:
To install sampling tubes in ducts more than 8 feet (2.4m) wide,
work must be performed inside the air duct. Sampling of air in
ducts wider than 8 feet (2.4m) is accomplished by using the
ST-10 sampling tube. If the tube is shorter than the width of the
air duct, install the end cap into the sampling tube as shown
in Figure 4 and support the end opposite the duct smoke detec-
tor.
Install the sampling tube as follows:
3
1. Drill a ⁄4-inch (19mm) hole in the duct directly opposite the hole
Table 1. Sampling tubes recommended for different
duct widths:
already drilled for the sampling tube. Make sure the hole is 1″ to 2″
(25 to 50mm) below the inlet hole on the opposite side of the duct to
allow for moisture drainage.
Outside Duct Width
1 to 2 ft. (0.3 to 0.6 m)
2 to 4 ft. (0.6 to 1.2 m)
4 to 8 ft. (1.2 to 2.4 m)
8 to 12 ft. (2.4 to 3.7 m)
Sampling Tube Recommended*
ST-1.5
ST-3
2. Slide the sampling tube with the flange into the housing bushing that
meets the air flow first. Position the tube so that the arrow points into
the air flow. Secure the tube flange to the housing bushing with two
#6 self-tapping screws.
ST-5
ST-10
*Must extend a minimum of 2⁄3 the duct width
3. From inside the duct, couple the other sections of the sampling tube
to the section already installed using the 1⁄2-inch conduit fittings sup-
plied. Make sure that the holes on both of the sampling tubes are lined
up and facing into the air flow.
Figure 4. Air duct detector sampling tube:
AIR HOLES
FLANGE
SAMPLING
TUBE
END CAP
4. Trim the end of the tube protruding through the duct so that 1″ to 2″
(25 to 50mm) of the tube extend outside the duct. Plug this end with
the end cap and tape closed any holes in the protruding section of the
tube. Be sure to seal the duct where the tube protrudes.
ARROW
NOTE:
An alternate method to using the ST-10 is to use two ST-5 sam-
pling tubes. Remove the flange from one of the tubes and install
as described above. After the installation, use electrical tape to
close off some of the sampling holes so that there are a total of
10 to 12 holes spaced as evenly as possible across the width of
the duct.
AIR FLOW DIRECTION
MUST FACE
INTO AIR FLOW
H0108-02
D200-39-00
3
I56-1977-004R
NOTE:
Air currents inside the duct may cause excessive vibration,
especially when the longer sampling tubes are used. In these
cases a 3 inch (75mm) floor flange (available at most plumb-
ing supply stores) may be used to fasten the sampling tube to
the other side of the duct. When using the flange/connector
Two LEDs on each duct smoke detector may light, if programmed by the
system control panel, to provide a local, visible indication. Remote LED
annunciator capability is available as an option. Each duct smoke detector
can only be wired to one remote accessory.
1
mounting technique, drill a 1-inch to 1 ⁄4-inch (25 to 32mm)
Different panel manufacturers offer different feature sets across their dif-
ferent panel models. As a result, certain features of the DH200RPL may be
available on some control panels, but not on others. The possible features
available in the DH200RPL, if supported by the control panel are:
hole where the flange will be used.
[5] Install The Filters
To install the sampling tube filters, simply push the filters into the sam-
pling and exhaust tube holes, as shown in Figure 6. If a metal sampling
tube is used, install the filters into the tube end.
1. Panel controls the LED operation on sensor. Operational modes are
RED blink, RED continuous, and off.
2. The remote output of the RA400Z does not follow the condition of the
duct smoke detector LED while in standby. When in alarm, the LED
output of the detector and remote will be identical.
CAUTION
Filters require periodic cleaning or replacement, depending on the amount
of dust and dirt accumulated. Visually inspect the filters at least quarterly;
inspect them more often if the dust accumulation warrants it. See Section
[9.1.2] for more information. Replacement filters can be ordered (filter
P/N F36-09-11).
Please refer to the operation manual for the UL
listed control panel for specific operation of the DH200RPL.
Wiring Instructions
Disconnect power from the communication line before installing the
Figure 6. Sampling tube filter installation:
DH200RPL duct smoke detector.
Wire the DH200RPL duct smoke detector per the Control Panel Installation
Manual and Figures 9, 10 or 11.
Set the desired address on the sensor board address code wheel switches
(see Figure 7).
[6] Field Wiring Installation Guidelines
All wiring must be installed in compliance with the National Electrical
Code and the local codes having jurisdiction. Proper wire gauges should
be used. The conductors used to connect smoke detectors to control
panels and accessory devices should be color-coded to prevent wiring
mistakes. Improper connections can prevent a system from responding
properly in the event of a fire.
Figure 7. Rotary Address Switches
[7] Perform Detector Check
1. Perform STANDBY AND TROUBLE TEST per Section [9.2.1].
2. Perform MAGNET TEST per Section [9.2.2.1]. The
RTS451 test of Section [9.2.2.2] may substitute for this requirement.
3. Perform AIR FLOW TEST per Section [9.1].
For signal wiring, (the wiring between detectors or from detectors to auxil-
iary devices), it is usually recommended that single conductor wire be no
smaller than 18 gauge. The duct smoke detector terminals accommodate
wire sizes up to 12 gauge. The last foot (0.3m) of conduit should be flex-
ible conduit (available in electrical supply houses), which facilitates easier
installation and puts less strain on the conduit holes in the housing. Solid
conduit connections may be used if desired.
4. Perform SMOKE RESPONSE TEST per Section [9.1.1].
[8] Install The Cover
Install the cover using the six screws that are captured in the housing
cover. Be certain filters are installed as specified in Section [5]. Make sure
that the cover fits into the base groove and that all gaskets are in their
proper positions. Tighten the six screws.
Smoke detectors and alarm system control panels have specifications for
Signaling-Line Circuit (SLC) wiring. Consult the control panel manufactur-
er’s specifications for wiring requirements for the particular model control
panel being used before wiring the detector loop.
[9] Duct Smoke Detector Maintenance and Test Procedures
Test and maintain duct smoke detectors as recommended in NFPA 72. The
tests contained in this manual were devised to assist maintenance person-
nel in verification of proper detector operation.
The DH200RPL detector is designed for ease of wiring. The housing
provides a terminal strip with clamping plates. Wiring connections are
made by stripping about 3⁄8-inch (9mm) of insulation from the end of the
wire, sliding the bare end under the plate, and tightening the clamping
plate screw.
Before conducting these tests, notify the proper authorities that the smoke
detection system will be temporarily out of service. Disable the device or
system under test to prevent unwanted alarms.
D200-39-00
4
I56-1977-004R
[9.1] Smoke Entry Tests
[9.1.4] Air Flow Test using Dwyer Series 607 Differential Pressure
Transmitter
[9.1.1] Air Flow
This product is designed to operate over an extended air speed range of 100
to 4000 FPM. To verify sufficient sampling of ducted air, turn the air han-
dler on and use a manometer to measure the differential pressure between
the two sampling tubes. The differential pressure should measure at least
0.0015 inches of water and no more than 1.2 inches of water. Because most
commercially available manometers cannot accurately measure very low
pressure differentials, applications with less than 500 FPM of duct air speed
may require one of the following: 1) the use of a current-sourcing pressure
transmitter (Dwyer Series 607) per Section 9.1.4 or; 2) the use of aerosol
smoke per section 9.1.2.
Verify the air speed of the duct using an anemometer. Air speed must be at
least 100 FPM. Wire the Dwyer transmitter as shown in Figure 8. Connect
the leads of the meter to either side of the 1000Ω resistor. Allow unit to
warm up for 15 seconds. With both HIGH and LOW pressure ports open
to ambient air, measure and record the voltage drop across the 1000Ω
resistor (measurement 1), 4.00 volts is typical. Using flexible tubing and
rubber stoppers, connect the HIGH side of the transmitter to the sampling
tube of the duct smoke detector housing, and the LOW side of the trans-
mitter to the exhaust tube of the duct smoke detector housing. Measure
and record the voltage drop across the 1000Ω resistor (measurement 2).
Subtract the voltage recorded in measurement 1 from the voltage recorded
in measurement 2. If the difference is greater than 0.15 volts, there is
enough air flow through the duct smoke detector for proper operation.
[9.1.2] Air Flow Test using Aerosol Smoke
This test is intended for low-flow systems (100-500 FPM). If the air speed
is greater than 500 FPM, use a conventional manometer to measure differ-
ential pressure between the sampling tubes, as described in 9.1.1.
Figure 8. Procedure for verifying air flow:
TO SAMPLING TUBE
1
Drill a ⁄4″ hole 3 feet upstream from the duct smoke detector. With the
TO EXHAUST TUBE
air handler on, measure the air velocity with an anemometer. Air speed
must be at least 100 FPM. Spray aerosol smoke* into the duct through the
1⁄4″ hole for five seconds. Wait two minutes for the duct smoke detector
to alarm. If the duct smoke detector alarms, air is flowing through the
detector. Remove the duct smoke detector cover and blow out the residual
aerosol smoke from the chamber and reset the duct smoke detector. Use
duct tape to seal the aerosol smoke entry hole.
HIGH
LOW
DIFFERENTIAL
PRESSURE
TRANSMITTER
MODEL #607-01
15 TO 36VDC
SUPPLY
9 VOLT
BATTERY
9 VOLT
BATTERY
1000 OHM 5% 1 WATT RESISTOR
9 VOLT
BATTERY
*Aerosol smoke can be purchased from Home Safeguard Industries,
Malibu, CA. Phone: 310/457-5813.
VOLT METER
FLUKE MODEL 87
OR EQUIVALENT
[9.1.3] Smoke Entry Test
To determine if smoke is capable of entering the sensing chamber, visually
identify any obstructions. Plug the exhaust and sampling tube holes to
prevent ducted air from carrying smoke away from the detector head, then
blow smoke such as cigarette, cotton wick, or punk directly at the head to
cause an alarm. REMEMBER TO REMOVE THE PLUGS AFTER THIS TEST,
OR THE DETECTOR WILL NOT FUNCTION PROPERLY.
H0163-01
[9.1.5] Filter Replacement
The filters do not substantially affect smoke performance even when up
to 90% of the filter is clogged. Quarterly visual inspection usually suf-
fices to determine whether the filters should be replaced because only a
high percentage of contamination affects performance. If further testing
is required, compare differential pressure readings with and without the
filters installed. If the difference exceeds 10% replace the filters. In no case
should the pressure differential fall below 0.0015 inches of water.
Figure 9. Wiring Diagram for DH200RPL Duct Smoke Detector using a UL listed control panel:
NOTE: Jumper J1 shunt must be installed for 2-W applications. J1 shunt must be removed for power PCB supervision.
NOTE: J1 JUMPER MUST
BE INSTALLED FOR 2W
APPLICATIONS. THE
J1 JUMPER MUST BE
REMOVED FOR POWER
BOARD SUPERVISION.
1
2
1
2
+
–
COMMUNICATION
LINE
UL LISTED CONTROL
PANEL
J1 JUMPER
1ST DETECTOR
IN LOOP
J1 JUMPER
2ND DETECTOR
IN LOOP
D200-39-00
5
I56-1977-004R
[9.2] Standby, Alarm, And Sensitivity Tests
[9.2.1] Standby And Trouble
Figure 10. Wiring Diagram for DH200RPL Duct
Detector with optional RA400Z:
Standby —
If the system control panel is programmed, look for the
presence of the flashing LEDs through the transparent
housing cover. The LED will flash with each communicat-
ion.
RA400Z
5 7
DO NOT BREAK TAB ON RA400Z
Trouble —
If the detector LEDs do not flash, then the de-tector lacks
power (check wiring, panel pro-gramming, or power sup
ply), the detector board is missing (replace), or the unit
is defec-tive (return for repair). Additionally, if the cover
is removed for more than 20 minutes, the LEDs of the
detector will not flash.
5 = Alarm Signal
7 = Aux. Power (–)
Test —
The trouble condition can be caused intentionally to veri-
fy correct operation of the system. Remove the detector
board to cause a trouble condition locally and at the sys-
tem control panel.
Figure 11. System Wiring Diagram for DH200RPL
Duct Smoke Detector with RTS451/RTS451KEY:
RTS 451/RTS451KEY
[9.2.2] Alarm Tests
1
[9.2.2.1] M02-04-00 Magnet Test
ALARM SIGNAL
1. Place the painted surface of the magnet onto the TEST locator on the
bottom of the detector housing (Figure 13).
3
NOT USED
5
7
4
3
6
2
4
5
2. Verify system control panel alarm status and control panel execution
of all intended auxiliary functions (i.e. fan shutdown, damper control,
etc.)
ALARM SIGNAL
AUX. POWER (–)
NOT USED
CIRCUIT
REFERENCE
TEST +
TEST –
3. The detector is self-restoring when the magnet is removed. Verify that
the system control panel has reset; panel may have to be reset.
TEST
SWITCH
Figure 13. Testing detector alarm:
FOR RTS451, TERMINAL 3 IS NOT
USED. (RTS451 DOES NOT HAVE
A TERMINAL 6.) FOR RTS451KEY,
TERMINALS 3 AND 6 ARE NOT USED.
Figure 12. Wiring Diagram for DH200RPL with
optional PA400:
PA400
5 7
Figure 14. Insulator Card for DH200RPL Duct Smoke
Detector:
5 = Alarm Signal
7 = Aux. Power (–)
D200-39-00
6
I56-1977-004R
[10] Board Replacement
[9.2.2.2] RTS451/RTS451KEY Remote Station Test
[10.1] Sensor Board Replacement
The RTS451/RTS451KEY Remote Test Station facilitates test of the alarm
capability of the duct smoke detector. These accessories provide the
stimulus to initiate an alarm condition at the detector. The detector is
self-restoring when the accessory test stimulus is removed. Verify that the
system control panel has reset; panel may need to be reset.
1. Remove the two sensor board mounting screws.
2. Pull gently on the board to remove it.
3. To replace the board, align the board mounting features, holes, and the
interconnect terminals. Push the board into place.
4. Secure board with the two mounting screws.
[9.2.3] Sensitivity Tests
[10.2] Power Board Replacement
Notify the proper authorities that the smoke detector system is undergo-
ing maintenance, and that the system will temporarily be out of service.
Disable the device or system undergoing maintenance to prevent unwant-
ed alarms and possible dispatch of the fire department.
1. Disconnect wiring from the terminal block.
2. Remove the two power board mounting screws.
3. Pull gently on the board to remove it.
4. To replace the board, align the board mounting features, holes, and the
interconnect terminals. Push the board into place.
5. Secure board with the two mounting screws.
6. Re-connect wiring to terminal block.
[9.3] Maintenance of Duct Smoke Detectors [9.3.1] Air Filters
1. Turn off power to the system.
2. Remove and inspect sampling tube filters.
3. If filters are heavily coated with dirt, replace them with new filters
(p/n F36-09-11). If they are not heavily coated, use a vacuum cleaner
or compressed air nozzle to remove dust, then reinstall the filters.
[11] Model DH200RPL Air Duct Smoke Detector Specifications
Operating Temperature Range 32° to 131°F (0° to 55°C)
Storage Temperature Range
Humidity Range
Air Velocity
-22º to 158ºF (-30º to 70ºC)
[9.3.2] Photo Detector Boards
10% to 93% (non-condensing)
100 to 4000 ft/min (0.5 to 20.32 m/sec.)
143⁄8″ L x 51⁄2″ W x 23⁄4″ D (37 cm L x
14 cm W x 7 cm D)
1. Remove the screen by gently grasping on each side and pulling straight
off
Dimensions
2. Lift the photo chamber in the same fashion. Vacuum the screen and
cover. Use clean, compressed air to loosen and blow out any remaining
debris. Replacement screens (p/n S08-39-01) are available.
3. Vacuum photo chamber, then use clean compressed air to blow area
clean.
4. Replace the chamber by pressing it onto the base. Press the screen into
place. It should fit tightly on the chamber.
D200-39-00
7
I56-1977-004R
Current Requirements (using no accessories)
Power supply voltage:
Max. standby current:
Max. alarm current:
20-30 VDC
26 mA
24 VAC, 50-60 Hz
65 mA RMS
182 mA RMS
3 to 10 Sec.
2 Sec.
120 VAC, 50-60Hz
44 mA RMS
52 mA RMS
3 to 10 Sec.
2 Sec.
220/240 VAC, 50-60Hz
25 mA RMS
30 mA RMS
3 to 10 Sec.
87 mA
Alarm response time:
3 to 10 Sec.
2 Sec.
Power up time:
2 Sec.
Contact Ratings
Accessory Current Loads at 24 VDC
Alarm auxiliary contacts* (DPDT)
10 A @ 30 VDC
Device
Standby
0 mA
Alarm
10 A @ 277 VAC (.75 power factor)
240 VA @ 249 VAC (0.4 power factor)
1/8 HP @ 120 VAC
PA400
15 mA Max.
12 mA Max.
10 mA Max.
RA400Z
0 mA
RTS451/RTS451KEY
0 mA
1/4 HP @ 240 VAC
Supervisory contact (SPST)
2.0 A @ 30 VDC (resistive)
*Minimum switching current for auxiliary contact must be 100 mA DC minimum @ 5 VDC.
Programming Specifications/Requirements for Intelligent System
Control Panels
There are a limited number of devices that can have their LEDs pro-
grammed to illuminate. The actual number of devices is determined
by the control panel and its ability to supply LED current.
Refer to the Control Panel Installation Manual for details.
Accessories
Part No.
Accessories
Part No.
RA400Z
Replacement Photo Insect Screen
S08-39-01
P48-61-00
P48-21-00
A5053
Remote LED
Replacement End Cap for Plastic Sampling Tube
Replacement End Cap for Metal Sampling Tubes
Replacement Photoelectric Sensor Board
Replacement Power Board (w/relay)
Magnetic Remote Test
Key-Activated Remote Test
Replacement Filters
Replacement Test Magnet
RTS451
RTS451KEY
F36-09-11
M02-04-00
A5060
Please refer to insert for the Limitations of Fire Alarm Systems
Three-Year Limited Warranty
System Sensor warrants its enclosed air duct smoke detector to be free from defects
in materials and workmanship under normal use and service for a period of three
years from date of manufacture. System Sensor makes no other express warranty
for this air duct smoke detector. No agent, representative, dealer, or employee of the
Company has the authority to increase or alter the obligations or limitations of this
Warranty. The Company’s obligation of this Warranty shall be limited to the repair or
replacement of any part of the air duct smoke detector which is found to be defective
in materials or workmanship under normal use and service during the three year
period commencing with the date of manufacture. After phoning System Sensor’s
toll free number 800-SENSOR2 (736-7672) for a Return Authorization number, send
defective units postage prepaid to: System Sensor, Returns Department, RA #______
____, 3825 Ohio Avenue, St. Charles, IL 60174. Please include a note describing the
malfunction and suspected cause of failure. The Company shall not be obligated to
repair or replace units which are found to be defective because of damage, unrea-
sonable use, modifications, or alterations occurring after the date of manufacture.
In no case shall the Company be liable for any consequential or incidental damages
for breach of this or any other Warranty, expressed or implied whatsoever, even if
the loss or damage is caused by the Company’s negligence or fault. Some states do
not allow the exclusion or limitation of incidental or consequential damages, so the
above limitation or exclusion may not apply to you. This Warranty gives you specific
legal rights, and you may also have other rights which vary from state to state.
To keep your equipment in excellent working order, ongoing maintenance is required
per the manufacturer’s recommendations and UL and NFPA standards. At a mini-
mum, the requirements of Chapter 7 of NFPA 72, the National Fire Alarm Code, shall
be followed. A preventative maintenance agreement should be arranged through
the local manufacturer’s representative. Though smoke detectors are designed for
long life, they may fail at any time. Any smoke detector, fire alarm equipment, or
any component of that system which fails shall be repaired or replaced as soon as
possible.
FCC Statement
This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful inter-
ference, and (2) this device must accept any interference received, including interference that may cause undesired operation.
Note: This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to Part 15 of the FCC Rules. These
limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates, uses
and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio
communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful
interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct
the interference by one or more of the following measures:
– Reorient or relocate the receiving antenna.
– Increase the separation between the equipment and receiver.
– Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.
– Consult the dealer or an experienced radio/TV technician for help.
D200-39-00
8
I56-1977-004R
© 2004 System Sensor
|